Plan Review Details - Permit 18040797
Plan Review Stops For Permit 18040797
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-09-24 Cont ID  
Sent By jpearson Date 2018-09-24 Time 08:33 Rev Time 0.00
Received By jpearson Date 2018-09-24 Time 08:33 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-09-05 Cont ID  
Sent By jpearson Date 2018-09-05 Time 07:53 Rev Time 0.00
Received By jpearson Date 2018-09-05 Time 07:53 Sent To  
Notes
2018-09-05 07:52:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. WILL CAMERAS HAVE HIGH VOLTAGE WIRING IN ADDITION TO
 LOW VOLTAGE WIRING? PROVIDE CLARIFICATION. FBC 107.2.1
 (BASED ON COMMENT RESPONSE, PROVIDE DETAIL OF
 SEPARATION FOR LOW VOLTAGE WIRING FROM POWER WIRING.
 NEC 725.136)(3RD REVIEW: DETAIL PROVIDED SHOWS WHAT
 APPEARS TO BE A CORD FEEDING THE 120 VOLT SUPPLY. CORD
 IS NOT PERMITTED AS A SUBSTITUTE FOR FIXED WIRING
 METHODS. PROVIDE CORRECTION. NEC 400.8)
 3. CORRECTED.
 4. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-29 Cont ID  
Sent By jpearson Date 2018-06-29 Time 15:53 Rev Time 0.00
Received By jpearson Date 2018-06-29 Time 15:35 Sent To  
Notes
2018-06-29 15:35:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CONSERVATION IN RELATION
 TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO COMPLY
 WITH CODE. FBC EC C405.5.1 (COMMENT RESPONSE STATES
 THAT THIS CODE REFERS TO INTERIOR LIGHTING. I'M NOT
 SURE WHICH YEAR CODE YOU ARE LOOKING AT, BUT IN THE
 2017 FBC ENERGY CONSERVATION, THIS SECTION IS FOR
 EXTERIOR LIGHTING. IT APPEARS THAT YOU ARE REQUESTING
 EXEMPTION THAT IS USED FOR THEME ELEMENTS IN
 AMUSEMENT/THEME PARKS, WHICH DOES NOT APPLY TO THIS
 SUBMITTAL. PROVIDE AS PREVIOUSLY REQUESTED. YOU ARE
 WELCOME TO DISCUSS THIS WITH THE BUILDING OFFICIAL IF
 YOU DISAGREE.)
 2. WILL CAMERAS HAVE HIGH VOLTAGE WIRING IN ADDITION TO
 LOW VOLTAGE WIRING? PROVIDE CLARIFICATION. FBC 107.2.1
 (BASED ON COMMENT RESPONSE, PROVIDE DETAIL OF
 SEPARATION FOR LOW VOLTAGE WIRING FROM POWER WIRING.
 NEC 725.136)
 3. CORRECTED.
 4. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 11:34 Rev Time 0.00
Received By jpearson Date 2018-05-05 Time 11:34 Sent To  
Notes
2018-05-05 11:34:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CONSERVATION IN RELATION
 TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO COMPLY
 WITH CODE. FBC EC C405.5.1
 2. WILL CAMERAS HAVE HIGH VOLTAGE WIRING IN ADDITION TO
 LOW VOLTAGE WIRING? PROVIDE CLARIFICATION. FBC 107.2.1
 3. PROVIDE DETAILS OF CONDUIT AND WIRE SIZE TO FIXTURES
 ON PLAN. FBC 107.2.1
 4. PROVIDE VOLTAGE DROP CALCULATIONS FOR EACH CIRCUIT
 IN COMPLIANCE WITH ENERGY CODE. FBC EC C405.6.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-06-29 Cont ID  
Sent By jpearson Date 2018-06-29 Time 15:53 Rev Time 0.00
Received By jpearson Date 2018-06-29 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-09-24 Time   Rev Time 0.00
Received By lmarchan Date 2018-09-21 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-20 Cont ID  
Sent By lmarchan Date 2018-09-20 Time 10:49 Rev Time 0.00
Received By lmarchan Date 2018-08-21 Time 13:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-11 Cont ID  
Sent By cpuell Date 2018-07-11 Time 08:58 Rev Time 0.00
Received By cpuell Date 2018-06-11 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-23 Cont ID  
Sent By lmarchan Date 2018-05-23 Time 07:43 Rev Time 0.00
Received By lmarchan Date 2018-04-18 Time 08:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-09-05 Cont ID  
Sent By shill Date 2018-09-05 Time 10:09 Rev Time 0.00
Received By jpearson Date 2018-08-25 Time 10:09 Sent To  
Notes
2018-09-05 07:41:47SHEET Y-401 IS DIGITALLY SIGNED BY A PERSON THAT
 APPEARS TO NOT BE LICENSED AS AN ENGINEER, NO TITLE
 BLOCK EXISTS FOR THIS PERSON ON PLAN. PROVIDE
 CORRECTION. FS 471.031

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By jpearson Date 2018-06-29 Time 15:52 Rev Time 0.00
Received By jpearson Date 2018-06-29 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 11:30 Rev Time 0.00
Received By jpearson Date 2018-05-05 Time 11:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-09-20 Cont ID  
Sent By jroach Date 2018-09-20 Time 10:28 Rev Time 0.00
Received By jroach Date 2018-09-20 Time 09:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-11 Cont ID  
Sent By jroach Date 2018-07-11 Time 08:52 Rev Time 0.00
Received By jroach Date 2018-07-11 Time 08:52 Sent To  
Notes
2018-07-11 08:54:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.11.2018
 PERMIT NO.: 18040797
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A PHOTOMETRIC PLAN SHALL BE PROVIDED. THE
 PHOTOMETRIC LEVELS SHALL NOT EXCEED 1.0 FOOTCANDLES
 WHEN MEASURED AT THE PROPERTY LINE AND SHALL NOT EXCEED
 0.5 FOOTCANDLES WHEN MEASURED IN A RESIDENTIAL ZONING
 DISTRICT. - THE RESUBMITTAL RESPONSES INDICATED THAT
 THIS WAS SHOWN ON SHEET EP-200; HOWEVER, THERE IS NO
 SHEET EP-200 INCLUDED IN THE SUBMITTED DRAWINGS. PLEASE
 PROVIDE THE SHEET, OR OTHERWISE CLARIFY WHERE THE
 PHOTOMETRIC LEVELS CAN BE FOUND.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By jroach Date 2018-05-22 Time 17:14 Rev Time 0.00
Received By jroach Date 2018-05-22 Time 17:14 Sent To  
Notes
2018-05-22 17:14:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.22.2018
 PERMIT NO.: 18040797
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A PHOTOMETRIC PLAN SHALL BE PROVIDED. THE
 PHOTOMETRIC LEVELS SHALL NOT EXCEED 1.0 FOOTCANDLES
 WHEN MEASURED AT THE PROPERTY LINE AND SHALL NOT EXCEED
 0.5 FOOTCANDLES WHEN MEASURED IN A RESIDENTIAL ZONING
 DISTRICT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved