Plan Review Details - Permit 18040706
Plan Review Stops For Permit 18040706 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2018-05-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-02 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-02 |
Time |
17:16 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-04-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-04-24 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-04-24 |
Time |
07:47 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2018-07-06 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-07-06 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-07-06 |
Time |
15:35 |
Sent To |
|
|
Notes |
2018-07-06 15:36:01 | APPROVED UNDER 18060554/ GPJ |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-04-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-04-25 |
Time |
07:01 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-04-25 |
Time |
06:03 |
Sent To |
|
|
Notes |
2018-04-25 07:00:44 | 1) CITY RECORDS SHOW A PREVIOUS GAS PERMIT FOR THIS | | ADDRESS. THE PLANS INDICATE AN EXISTING GAS METER. THE | | BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO | | THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | ***NOTE: I HAVE INCLUDED A COPY OF THE EXISTING GAS | | PLAN FOR YOUR USE TO REVISE YOUR GAS DRAWING. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-02 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-17 |
Time |
13:01 |
Sent To |
|
|
Notes |
2018-04-18 13:01:59 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-04-19 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2018-04-19 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2018-04-19 |
Time |
|
Sent To |
B |
|
Notes |
|
|
|