Plan Review Details - Permit 18040638
Plan Review Stops For Permit 18040638
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 13:40 Rev Time 0.00
Received By shill Date 2018-04-28 Time 13:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-19 Cont ID  
Sent By shill Date 2018-04-19 Time 07:52 Rev Time 0.00
Received By shill Date 2018-04-19 Time 07:52 Sent To  
Notes
2018-04-19 08:04:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B TABLE 1510.10, COMPLIANCE NOT CLEAR. IT
 APPEARS THAT THE UNIT EXCEEDS 9' IN WIDTH; IT APPEARS
 THAT 3' CLEARANCE IS PROPOSED, BUT THE TABLE REQUIRES
 CLEARANCE OF 48" MINIMUM. EITHER REVISE PLAN
 ACCORDINGLY OR CONTACT ME TO DISCUSS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 13:40 Rev Time 0.00
Received By shill Date 2018-04-25 Time 13:14 Sent To  
Notes
2018-04-26 13:14:48RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-19 Cont ID  
Sent By shill Date 2018-04-19 Time 08:04 Rev Time 0.00
Received By shill Date 2018-04-13 Time 12:44 Sent To  
Notes
2018-04-16 12:44:29BLDG MISC 1