Plan Review Details - Permit 18040509
Plan Review Stops For Permit 18040509
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2018-06-26 Cont ID  
Sent By spalmer Date 2018-06-26 Time 16:39 Rev Time 0.00
Received By spalmer Date 2018-04-12 Time 08:30 Sent To  
Notes
2018-04-12 08:26:27NEW SINGLE FAMILY RESIDENCE ADDRESS NOT ASSIGNED LT 10
 BLK 30. PLEASE SEE ATTACHED DOCUMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By skennedy Date 2018-06-20 Time 16:00 Rev Time 0.00
Received By skennedy Date 2018-06-20 Time 16:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By skennedy Date 2018-05-09 Time 17:03 Rev Time 0.00
Received By skennedy Date 2018-05-02 Time 16:35 Sent To  
Notes
2018-05-02 17:07:151ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
  
 18040509 - 816 SUNSET RD
  
 1) PLEASE PROVIDE A SOIL TEST PER FBC 401.4
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 2) THE SITE PLAN HAS LIMITED INFORMATION RELATIVE TO
 DRAINAGE. PLEASE PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN PER FBC-110.9 IMPACT OF CONSTRUCTION. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 NOTE PER R401.1 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 3) PLEASE NOTE A DRIVEWAY APPROACH DETAIL IS PROVIDED.
 A SEPARATE PERMIT AND DESIGN IS REQUIRED FOR THE
 DRIVEWAY PERMIT, IT IS NOT INCLUDED IN THIS REVIEW.
 PLEASE ACKNOWLEDGE THIS IN YOUR RESPONSE TO THESE
 COMMENTS; ALSO SEE ZONING COMMENTS THAT MAY APPLY.
  
 4) PLEASE NOTE A LANDSCAPE PLAN IS PROVIDED. A SEPARATE
 PERMIT AND DESIGN IS REQUIRED FOR THE LANDSCAPE PERMIT,
 IT IS NOT INCLUDED IN THIS REVIEW. PLEASE ACKNOWLEDGE
 THIS IN YOUR RESPONSE TO THESE COMMENTS; ALSO SEE
 ZONING COMMENTS THAT MAY APPLY.
  
 5) PERMIT VALUATION ? THE CALCULATED VALUE OF THE
 IMPROVEMENT IS $271,520.00 PER THE ICC-BVD PUBLISHED
 FEBRUARY 2018 AND ADOPTED FOR USE BY CITY RESOLUTION
 367-09. THIS COVERS THE DWELLING ONLY AND NO OTHER
 SEPARATELY REQUIRED PERMITS. VALUE AND FEES DUE ARE
 ADJUSTED TO THIS FIGURE. PLEASE REFERENCE FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 6) SHEETS A-1, A-2, S-1, & S-2 CONTAIN REFERENCES TO
 THE FBC 2014 FIFTH EDITION ? PLEASE CORRECT TO THE FBC
 2017 6TH EDITION RESIDENTIAL. PLEASE NOTE SHEET A-3
 CONTAINS DESIGN PRESSURE INFORMATION AND SHOULD
 ACCORDINGLY BE SIGNED AND SEALED BY THE ENGINEER OF
 RECORD.
  
 7) THE WALL SECTION ON SHEET A-2 INDICATES THE USE OF
 ASPHALT SHINGLES AS A ROOF COVERING IN CONFLICT WITH
 THE NOTES ON SHEET A-4 AND THE PRODUCT INFORMATION
 PROVIDED WHICH INDICATE THE USE OF A SPANISH S TILE.
 PLEASE CLARIFY.
  
 8) SHEET A-1 ? NO BATHROOM DOOR MEETS THE 29? MINIMUM
 WIDTH REQUIREMENT: FBCR-320.1.1 - ALL NEW SINGLE-FAMILY
 HOUSES, DUPLEXES, TRIPLEXES, CONDOMINIUMS AND
 TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED
 WITH MAXIMUM POSSIBLE PRIVACY, WHERE BATHROOMS ARE
 PROVIDED ON HABITABLE GRADE LEVELS, WITH A DOOR THAT
 HAS A 29-INCH (737 MM) CLEAR OPENING. HOWEVER, IF ONLY
 A TOILET ROOM IS PROVIDED AT GRADE LEVEL, SUCH TOILET
 ROOMS SHALL HAVE A CLEAR OPENING OF NOT LESS THAN 29
 INCHES (737 MM).
  
 9) SHEET A-1 CONTAINS A NOTE RELATIVE TO BEDROOM EGRESS
 WINDOW SQUARE FOOTAGE. PLEASE INCLUDE ADDITIONAL NOTES
 AS TO MINIMUM SILL HEIGHT, AND OPENING HEIGHT AND WIDTH
 OR SELECT THE PGT WINDOW TYPE IN THE CORRESPONDING
 PRODUCT APPROVAL TO ASSURE COMPLIANCE WITH FBCR-310.2.1
 -
 EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET
 CLEAR OPENING OF NOT LESS THAN 5.0 SQUARE FEET. THE NET
 CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL
 BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY
 ESCAPE AND RESCUE OPENING FROM THE INSIDE. THE NET
 CLEAR HEIGHT OPENING SHALL BE NOT LESS THAN 24 INCHES
 (610 MM) AND THE NET CLEAR WIDTH SHALL BE NOT LESS THAN
 20 INCHES (508 MM). FBCR-310.2.2 ? THE MAXIMUM SILL
 HEIGHT IS 44?.
  
 10) SHEET A-1 THE DOOR SEPARATING THE GARAGE FROM THE
 UTILITY ROOM IS UNSPECIFIED IN TERMS OF FIRE
 RESISTANCE. PLEASE SPECIFY TO ASSURE COMPLIANCE WITH
 FBCR-302.5.1 OPEN PROTECTION. OPENINGS BETWEEN THE
 GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD
 DOORS NOT LESS THAN 13/8 INCHES (35 MM) IN THICKNESS,
 SOLID OR HONEYCOMB-CORE STEEL DOORS NOT LESS THAN 13/8
 INCHES (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS.
  
 11) SHEET A-2 THE WALL SECTION DOES NOT SPECIFY THE
 WALL INSULATION TYPE OR VALUE. PLEASE PROVIDE AN
 INDICATION CONSISTENT WITH THAT SPECIFIED IN THE ENERGY
 SUBMITTAL. ADDITIONALLY, THE NOTE RELATIVE TO CEILING
 INSULATION IS SLIGHTLY INCONSISTENT WITH BOTH THE
 ENERGY SUBMITTAL AND THE PRODUCT INFORMATION SUBMITTED.
 THE NOTE SPECIFIES AN R-19 VALUE WHERE THE ENERGY
 SUBMITTAL SPECIFIES R-20. PLEASE RECONCILE. PRESUMABLY
 R-20 IS TO BE USED IN A 5? THICKNESS PER TABLE 1 ON
 PAGE 6 OF 7 OF ESR-1826, PLEASE CONFIRM BY NOTATION OF
 THE USE OF CLASSIC PLUS. FBC-107; PLEASE PROVIDE THIS
 CONSISTENT MINIMUM PLAN REVIEW CRITERIA.
  
 12) SHEET A-2 CONTAINS A NOTE RELATIVE TO A WATER
 RESISTIVE BARRIER. ASSURE THE PROPOSED METHOD COMPLIES
 WITH FBCR-703.7.3 WATER-RESISTIVE BARRIERS SHALL BE
 INSTALLED AS REQUIRED IN SECTION R703.2 AND, WHERE
 APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE A
 WATER-RESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF GRADE
 D PAPER. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION R703.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 13) PLEASE NOTE THE TRUSS MANUFACTURER SUBMITTAL
 DOCUMENTS AS NOTED ON SHEET S-2 MAY BE A DEFERRED
 SUBMITTAL PRIOR TO TRUSS ERECTION PER FBCR802.10.1.
 TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE TO
 SECTION R802.10.1, SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. TRUSS
 DESIGN DRAWINGS SHALL BE PROVIDED WITH THE SHIPMENT OF
 TRUSSES DELIVERED TO THE JOB SITE.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By ppetty Date 2018-05-17 Time 11:09 Rev Time 0.00
Received By ppetty Date 2018-05-17 Time 11:09 Sent To  
Notes
2018-05-17 11:09:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK SEE COMMENTS BELOW.
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6. CORRECTED
 7. CORRECTED
 8. CORRECTED
 9. CORRECTED
 10. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By jpearson Date 2018-05-01 Time 09:04 Rev Time 0.00
Received By jpearson Date 2018-05-01 Time 07:16 Sent To  
Notes
2018-05-01 09:04:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 3. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE, INCLUDING GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PROVIDE ACCURATE LOAD CALCULATION FOR A DWELLING
 UNIT USING FORMAT IN THE FBC RESIDENTIAL. NEC 220; FBC
 RE E3602.2
 6. RISER DIAGRAM IS NOT CODE COMPLIANT. THE SERVICE
 CONDUCTORS MUST HAVE OVERCURRENT PROTECTION AND THE
 PANEL IS SHOWN AS MAIN LUG ONLY IN PANEL SCHEDULE.
 SERVICE CONDUCTORS ARE NOT PERMITTED TO EXTEND FURTHER
 THAN 8 FEET INTO A STRUCTURE WITHOUT OVERCURRENT
 PROTECTION. IF THIS OVERCURRENT PROTECTION IS LOCATED
 ON THE EXTERIOR OF THE DWELLING, THAN THE CONDUIT TO
 THE INTERIOR PANEL MUST INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. IF THE CONDUCTORS ARE RUN UNDERGROUND FROM
 THE METER TO THE INTERIOR PANEL, AND THAT PANEL HAS A
 MAIN BREAKER, THE CONDUCTORS MUST NOT EXCEED 8 FEET IN
 LENGTH BEFORE TERMINATION TO THE MAIN BREAKER. PROVIDE
 CORRECTION. NEC 230.70, 250.122; FBC RE E601.6,
 E3704.6, 3607.3.1
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. A NOTE WILL SUFFICE. NEC 210.12; FBC RE
 E3902.16
 8. CIRCUIT 18 IN PANEL SCHEDULE SHOWS #14 WIRE ON A 20
 AMP BREAKER FOR THE BATH GFCI CIRCUIT. THE #14 WIRE IS
 NOT RATED FOR 20 AMPS. PROVIDE CORRECTION. NEC
 240.4(D); FBC RE E3705.5.3
 9. CIRCUIT 1,3 IN PANEL SCHEDULE SHOWS #10 WIRE ON A 30
 AMP BREAKER FOR THE AHU WITH 10KW HEAT. THE #10 WIRE IS
 NOT RATED TO HANDLE THIS LOAD. THE BREAKER IS NOT SIZED
 PROPERLY. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 10. CIRCUIT 6,8 IN PANEL SCHEDULE SHOWS #10 WIRE ON A
 30 AMP BREAKER FOR THE RANGE WITH A 8.2KW LOAD. THE #10
 WIRE IS NOT RATED TO HANDLE THIS LOAD. THE BREAKER IS
 NOT SIZED PROPERLY. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE E3705.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-06-21 Cont ID  
Sent By gjohnson Date 2018-06-21 Time 09:14 Rev Time 0.00
Received By gjohnson Date 2018-06-21 Time 09:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 15:37 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 15:09 Sent To  
Notes
2018-06-06 16:04:552ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. ON THE RISER PLEASE SHOW EACH CUT SECTION OF PIPE,
 THE RISER YOU PROVIDED DOES NOT SHOW THE DROP SECTIONS
 OF PIPE DOWN FROM THE ATTIC TO THE APPLIANCE OR METER.
 SHOW THE LENGTH OF EACH CUT SECTION. WHEN I SCALED THE
 DISTANCE FROM THE METER TO THE RANGE IT WAS ABOUT 40'
 EACH DROP SECTION WOULD ADD 8'-10' TO YOUR OVERALL
 DISTANCE FROM THE METER TO THE FURTHEST APPLIANCE. THIS
 IS REQUIRED TO DETERMINE SIZE OF THE PIPING. PER
 FBC-RES SEC. G2413.4.1, G2413.4.2.
  
 2. PROVIDE SIZING TABLE USED, YOU LISTED LESS THAN 2PSI
 WITH A 1PSI PRESSURE DROP I COULD NOT FIND A TABLE IN
 THE FUEL GAS CODE TO MATCH UP TO THESE PRESSURES. PER
 FBC-RES SEC. G2413.4.1, G2413.4.2.
  
 3. SHOW BTU LOAD OF THE RANGE ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By lcrespo Date 2018-04-30 Time 16:43 Rev Time 0.00
Received By lcrespo Date 2018-04-30 Time 16:43 Sent To  
Notes
2018-04-30 16:45:2704/30/18 DENIED GAS BY PLUMBING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1. THE LOCATION OF THE TANKLESS WATER HEATER AND THE
 LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS
 IN RELATION TO THE WATER HEATER COULD NOT BE VERIFIED
 AS INSTALLATION MANUAL IS NOT AVAILABLE. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. PLEASE PROVIDE INSTALLATION MANUAL FOR TANKLESS
 WATER HEATER, SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
 3. PLEASE SPECIFICATION FOR ALL ALLIANCES AND LABELING,
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS SEC. 402.2 AND 301.3 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.2 AND G2404.3.
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 5. A SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED FOR
 A CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMENDMENTS TO FBC
 SEC. 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By fmittner Date 2018-05-23 Time 09:59 Rev Time 0.00
Received By fmittner Date 2018-05-23 Time 09:59 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By fmittner Date 2018-04-18 Time 15:42 Rev Time 0.00
Received By fmittner Date 2018-04-18 Time 15:42 Sent To  
Notes
2018-04-18 15:43:23VENT/SCUPPER AND GARAGE DOOR DETAIL NOT ADDRESSED PER
 HPB COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-26 Cont ID  
Sent By skennedy Date 2018-06-26 Time 16:22 Rev Time 0.00
Received By skennedy Date 2018-06-25 Time 14:31 Sent To  
Notes
2018-06-26 14:31:50IMPACT FEES ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By skennedy Date 2018-06-20 Time 16:00 Rev Time 0.00
Received By skennedy Date 2018-05-14 Time 16:20 Sent To  
Notes
2018-05-15 16:20:30R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-09 Cont ID  
Sent By skennedy Date 2018-05-09 Time 17:05 Rev Time 0.00
Received By skennedy Date 2018-04-12 Time 15:08 Sent To  
Notes
2018-04-13 15:09:05R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-06-26 Cont ID  
Sent By skennedy Date 2018-06-26 Time 16:22 Rev Time 0.00
Received By skennedy Date 2018-06-26 Time 16:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By skennedy Date 2018-05-02 Time 16:29 Rev Time 0.00
Received By skennedy Date 2018-05-02 Time 16:29 Sent To  
Notes
2018-05-02 16:32:131ST REVIEW: FBC 2017 5TH EDITION
 1ST REVIEW: FBC 2017 5TH ED. RESIDENTIAL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-01 Cont ID  
Sent By cmontell Date 2018-05-01 Time 13:55 Rev Time 0.00
Received By cmontell Date 2018-05-01 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-21 Cont ID  
Sent By gjohnson Date 2018-06-21 Time 09:15 Rev Time 0.00
Received By gjohnson Date 2018-06-21 Time 09:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 15:08 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 15:08 Sent To  
Notes
2018-06-06 16:13:132ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-1 THE SHOWER IN THE MASTER BATHROOM SHALL
 CONNECT DOWN STREAM OF THE LAVATORY'S THERE CAN BE ONLY
 ONE FIXTURE UPSTREAM OF THE VENT. PER FBC RES P3108.2.1
  
 2. SHT P-1 THERE SHALL BE A VENT BETWEEN THE TUB AND
 THE SHOWER FOR THE GUEST BATHROOMS. PER FBC RES
 P3108.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By lcrespo Date 2018-04-30 Time 16:40 Rev Time 0.00
Received By lcrespo Date 2018-04-30 Time 07:07 Sent To  
Notes
2018-04-30 16:40:3804/30/18 DENIED BY PLUMBING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 1. PLUMBING RISER DIAGRAM NEEDS VENTS FOR LAUNDRY TRAY,
 GUESS BATH AND MASTER NEED TO BE VENTED CORRECTLY, 2017
 FBC R3004, R3005,
 2. PLEASE PROVIDE WATER SUPPLY AND DISTRIBUTION SYSTEM
 DESIGN FOR WATER RISER DIAGRAM, WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING
 3. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 4. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; FBC 107.2.1,
 107.3.5
 5. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
 6. ON THE ROOM LABELLED POWER AND MASTER THE SHOWER PAN
 IS NOT RECEDED IT WILL REQUIRE LINING, 2017 FBC R
 2709.2
 7. SHOWER MEASUREMENT IN POWER IS AT 30? PLUS 4? FOR
 CURB WHICH IS NOT SHOWN AND WATER CLOSET SHALL NOT BE
 SET CLOSER THAN 15? INCHES FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER
 THAN 30? INCHES CENTER TO CENTER BETWEEN ADJACENT
 FIXTURES. THE SHOWER MAY BE SMALLER AS LONG AS IT
 COMPLIES WITH A SHOWER COMPARTMENT THAT IS NOT LESS
 THAN 900 SQUARE INCHES, PLEASE PROVIDE SHOWER DRAIN
 DETAILS AND COMPLIANCE. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By skennedy Date 2018-06-20 Time 15:55 Rev Time 0.00
Received By skennedy Date 2018-06-20 Time 15:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By skennedy Date 2018-05-09 Time 17:03 Rev Time 0.00
Received By skennedy Date 2018-05-09 Time 17:03 Sent To  
Notes
2018-05-09 17:05:371ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
  
 18040509 - 816 SUNSET RD
  
 THE WALL SECTION ON SHEET A-2 INDICATES THE USE OF
 ASPHALT SHINGLES AS A ROOF COVERING IN CONFLICT WITH
 THE NOTES ON SHEET A-4 AND THE PRODUCT INFORMATION
 PROVIDED WHICH INDICATE THE USE OF A SPANISH S TILE.
 PLEASE CLARIFY.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By fmittner Date 2018-05-23 Time 09:59 Rev Time 0.00
Received By fmittner Date 2018-05-23 Time 09:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By fmittner Date 2018-04-18 Time 15:44 Rev Time 0.00
Received By fmittner Date 2018-04-18 Time 15:44 Sent To  
Notes
2018-04-18 15:44:23LOT SPLIT NOT COMPLETED.