Plan Review Details - Permit 18040346
Plan Review Stops For Permit 18040346
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-04 Cont ID  
Sent By shill Date 2018-06-04 Time 18:27 Rev Time 0.00
Received By shill Date 2018-06-04 Time 18:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-21 Cont ID  
Sent By rmcdouga Date 2018-05-21 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2018-05-21 Time 17:27 Sent To I
Notes
2018-05-21 19:02:372017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18040346
 ADD: 525 S. FLAGLER DR. SUITE: 15A
 CONT: JEFFERY GOMERSALL BLDG. CO.
 TEL: 561-718-7866
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 5/21/2018
 ACTION: DENIED
  
 1) PARTIAL COMPLIANCE. PLEASE SHOW ON THE A-3 FLOOR
 PLAN WHICH OPENINGS ARE TO HAVE STORM SHUTTERS
 INSTALLED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) NEW COMMENT: THE WINDLOADS, COMPONENT AND CLADDING
 PRESSURES FOR A HIGH RISE BUILDING ARE REQUIRED TO BE
 SIGNED AND SEALED BY AN ENGINEER. FS 471 PLEASE NOTE
 THIS IS A 30 STORY PLUS HIGHRISE WITH A D EXPOSURE.
 PLEASE PROVIDE CODE COMPLIANCE WITH:
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3A)COMPLIED
  
 3B) STORM SHUTTERS PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL IMPACT OR
 NON-IMPACT GLAZING. FBC 1609.1.2.
 FL BLD CODE 2017 SECTION 107.2.5. 1609.1.2, 1715.8 &
 EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC.
  
 3C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) PARTIAL COMPLIANCE. PLEASE PROVIDE (2) SETS OF
 DOCUMENTATION (TEST REPORTS) FOR CODE COMPLIANCE WITH
 THESE CODE SECTIONS:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING, ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 6) NEW COMMENT: ON SHEET A-4, THE KITCHEN SOFFIT DETAIL
 SPECIFIES THAT THE NEW METAL SOFFIT FRAMING IS TO BE
 ATTACHED TO THE CONCRETE DECK WITH 2 #8 SCREWS AT 2'
 O.C. PLEASE SPECIFY ANCHORS FOR USE IN CONCRETE. FBC
 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-20 Cont ID  
Sent By jwitmer Date 2018-04-20 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2018-05-21 Time 17:27 Sent To  
Notes
2018-04-20 09:12:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18040346
 ADD: 525 S. FLAGLER DR. SUITE: 15A
 CONT: JEFFERY GOMERSALL BLDG. CO.
 TEL: 561-718-7866
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. APRIL 20/ 2018
 ACTION: DENIED
  
 1) IN THIS 1ST SUBMISSION THERE IS (2) FLORIDA PRODUCT
 APPROVAL FOR ROLLUP SHUTTERS, FL 12246-R4. ONLY THE
 COVERSHEETS WERE SUBMITTED NOT THE TECHNICAL SHEETS.
 THERE IS NO MENTION OF STORM SHUTTERS ON THE PERMIT
 APPLICATION NOR IN THE SET OF PLANS. PLEASE SHOW ON THE
 A-3 FLOOR PLAN WHICH OPENINGS ARE TO HAVE STORM
 SHUTTERS INSTALLED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) PLEASE NOTE THIS IS A 30 STORY PLUS HIGHRISE WITH A
 D EXPOSURE. PLEASE PROVIDE CODE COMPLIANCE WITH:
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3A) PLEASE PROVIDE THE WHOLE PRODUCT APPROVAL FOR
 COMPLIANCE WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(E) SHUTTERS.
  
 3B) STORM SHUTTERS
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL IMPACT OR NON-IMPACT
 GLAZING. FBC 1609.1.2.
 FL BLD CODE 2010 SECTION 107.2.5. 1609.1.2, 1715.8 &
 EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC.
  
 3C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 4) SHEET A-2 THE DEMOLITION SHEET INDICATES THE REMOVAL
 OF THE EXISTING FLOORING NOTE IS ASSUMED TO BE IN THE
 LIVING ROOM, DINING ROOM & KITCHEN. SHEET A-3 THE FLOOR
 PLAN DOES NOT INDICATE WHAT AREAS OF NEW FLOORING ARE
 TO BE INSTALLED NOR THE TYPES OF FLOOR FINISHES. PLEASE
 PROVIDE DOCUMENTATION FOR CODE COMPLIANCE WITH THESE
 CODE SECTIONS:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By jpearson Date 2018-05-15 Time 10:36 Rev Time 0.00
Received By jpearson Date 2018-05-15 Time 09:43 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 12:53 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 09:54 Sent To I
Notes
2018-04-30 12:53:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IT APPEARS THAT THE WRONG CODE WAS USED FOR DESIGN
 AS THERE ARE SEVERAL CODE SECTIONS QUOTED FROM THE FBC,
 RESIDENTIAL. THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, RESIDENTIAL SHALL APPLY TO THE CONSTRUCTION,
 ALTERATION, MOVEMENT, ENLARGEMENT, REPLACEMENT, REPAIR,
 EQUIPMENT, USE AND OCCUPANCY, LOCATION, REMOVAL AND
 DEMOLITION OF DETACHED ONE- AND TWO-FAMILY DWELLINGS
 AND TOWNHOUSES NOT MORE THAN THREE STORIES ABOVE GRADE
 PLANE IN HEIGHT WITH A SEPARATE MEANS OF EGRESS AND
 THEIR ACCESSORY STRUCTURES NOT MORE THAN THREE STORIES
 ABOVE GRADE PLANE IN HEIGHT. REMOVE ANY NOTES THAT
 QUOTE THE FBC RESIDENTIAL CODE.PROVIDE CORRECTION. FBC
 RE R101.2; FBC 107.2.1
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 4. SHOW LOCATION OF PANEL TO BE RELOCATED TO CONFIRM
 CODE COMPLIANCE. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-13 Cont ID  
Sent By pleduc Date 2018-04-13 Time   Rev Time 0.00
Received By pleduc Date 2018-04-12 Time 17:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-21 Cont ID  
Sent By rmcdouga Date 2018-05-21 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2018-05-10 Time 10:51 Sent To  
Notes
2018-05-14 10:51:22RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-10 Time 14:07 Sent To  
Notes
2018-04-11 14:07:09B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-04-20 Cont ID  
Sent By jwitmer Date 2018-04-20 Time 09:12 Rev Time  
Received By jwitmer Date 2018-04-20 Time 07:58 Sent To  
Notes
2018-04-20 10:59:59BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-18 Cont ID  
Sent By cmontell Date 2018-04-18 Time 14:11 Rev Time 0.00
Received By cmontell Date 2018-04-18 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 08:57 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 06:00 Sent To  
Notes
***NONE***