Plan Review Stops For Permit 18040133 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-06-22 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-06-22 |
Time |
10:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-07 |
Time |
19:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-07 |
Time |
19:19 |
Sent To |
|
|
Notes |
2018-06-07 19:21:31 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SEE COMMENTS FROM PREVIOUS LIST. THE COST BREAKDOWN | | DOES NOT HAVE QUANTITIES SO CANNOT BE VERIFIED WITHOUT | | EXTENSIVE WORK ON THE PLAN REVIEWER'S PART. THIS SHOULD | | BE INFORMATION WHICH THE CONTRACTOR HAS READILY | | AVAILABLE. | | | | PROVIDE A COST BREAKDOWN IN A FORMAT WHICH CAN BE | | VERIFIED USING MARSHALL & SWIFT OR OTHER INDUSTRY | | STANDARDS. | | | | ALSO PROVIDE THE COST BREAKDOWN FOR THE ITEMS WHICH | | APPLICANT IS CONSIDERING A PART OF THE 20%. FOR THE | | ITEMS WHICH ARCHITECT STATES EXCEED 20%, PROVIDE A COST | | BREAKDOWN TO DEMONSTRATE DISPROPORTIONATE COST. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-04-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-09 |
Time |
17:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-06 |
Time |
18:58 |
Sent To |
|
|
Notes |
2018-04-09 17:31:13 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC ACCESSIBILITY SECTION 404.2.4.1 REQUIRES 18" | | MANEUVERING CLEARANCES ON THE PULL SIDE OF RECESSED | | DOORS. SEE THE TWO DOORS ACROSS THE CORRIDOR FROM ROOM | | 505 AND THE ONE IN OFFICE 506. | | | | 2) FBC ACCESSIBILITY SECTION 404.2.6 REQUIRES THE | | DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES | | TO BE 48" MINIMUM PLUS THE WIDTH OF THE DOORS SWINGING | | INTO THE SPACE. SEE THE DOORS IN THE MEN'S BATHROOM. | | | | 3) THE MICROWAVE THAT IS LOCATED IN THE UPPER CABINETS | | IN THE BREAK ROOM DOES NOT COMPLY WITH FBC | | ACCESSIBILITY SECTIONS 309.3 AND 308.3.2 FOR OBSTRUCTED | | HIGH SIDE REACH RANGES TO OPERABLE PARTS OF THE | | APPLIANCE. | | | | 4) PROVIDE AN ITEMIZED COST LIST TO SHOW THAT THE | | REQUIRED 20 PERCENT DISPROPORTIONATE COST TOWARD | | REQUIRED ACCESSIBILITY WILL BE MET. FBC ACCESSIBILITY | | SECTION 202.3 ALTERATIONS. WHERE EXISTING ELEMENTS OR | | SPACES OR COMMON AREAS ARE ALTERED, EACH ALTERED | | ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE APPLICABLE | | REQUIREMENTS OF CHAPTER 2 AND SECTION 201.1.1. FBC | | ACCESSIBILITY SECTION 202.4.1 DISPROPORTIONATE COST. | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-06-22 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-06-22 |
Time |
11:12 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-06-05 |
Time |
12:24 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-06-05 |
Time |
12:24 |
Sent To |
|
|
Notes |
2018-06-05 12:23:57 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. DESIGNATE ON PLAN ANY ROOMS USED FOR PATIENT CARE | | AND SHOW THE REQUIRED WIRING METHODS FOR THESE ROOMS. | | NEC 517.13; WPB FBC 107.2.1 | | 2. PLAN STATES THIS IS A DIAGNOSTIC FACILITY, BUT THE | | PLAN REVIEWER DOES NOT SEE ANY DIAGNOSTIC EQUIPMENT | | INCLUDED IN THE LOAD CALCULATION. CLARIFY AND/OR | | CORRECT. NEC 220, 517.73; WPB FBC 107.2.1 | | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | EC C405.6.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-04-08 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-04-08 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-04-08 |
Time |
12:20 |
Sent To |
|
|
Notes |
2018-04-08 12:20:05 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | 471.025; WPB FBC 107.1, 107.2.1, 107.3.5 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-05-25 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-05-25 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-04-06 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-04-06 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-04-06 |
Time |
12:40 |
Sent To |
|
|
Notes |
2018-04-06 12:45:24 | PERMIT # 18040133 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | AMENDMENTS. | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-06-22 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-06-20 |
Time |
14:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-07 |
Time |
19:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-22 |
Time |
13:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-04-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-16 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-04 |
Time |
11:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2018-04-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-16 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-16 |
Time |
17:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-06-22 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-06-22 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-05-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-24 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-24 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-04-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-04-10 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-04-10 |
Time |
11:45 |
Sent To |
|
|
Notes |
2018-04-10 11:59:59 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18040133 | | 4/10/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET A410: NO VENTILATION, COOLING AND HEATING, | | PROVIDED FOR OFFICE 504; AND RETURN AIR GRILLS MISSING | | IN OFFICES 501, 502, 503, 504, 505, AND 507. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-06-22 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-06-22 |
Time |
10:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-07 |
Time |
07:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-06 |
Time |
16:59 |
Sent To |
|
|
Notes |
2018-06-07 07:44:28 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE COST BREAKDOWN THAT YOU PROVIDED TO COMPLY WITH | | FBC ACC 202.4.1, 202.4.2 DISPROPORTIONATE COST DOES NOT | | COMPLY EACH ITEM ON YOUR BREAK DOWN SHALL BE AS FOLLOWS | | IN ORDER (I) COSTS ASSOCIATED WITH PROVIDING AN | | ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | A) PLEASE CLARIFY WHAT GENERAL CONDITIONS ARE AND | | PROVIDE A SPECIFIC BREAKDOWN ON EACH ITEM. | | B) THE GRAB BARS THAT ARE BEING INSTALLED IN THE TOILET | | STALL THAT IS TOO SMALL TO MEET ACCESSIBLE DIMENSION | | CANNOT COUNT TOWARD YOUR 20% | | C) IF YOU ARE NOT ENLARGING THE STALLS OR BATHROOMS TO | | COMPLY WITH THE REQUIRED CLEAR FLOOR SPACE AT THE | | FIXTURES THEN THE COST OF PAINTING, TILE WORK, DRYWALL | | TOILET PARTITIONS AND ACCESSORIES OR FEES CANNOT COUNT | | TOWARD YOUR 20%. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-04-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-16 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-16 |
Time |
16:41 |
Sent To |
|
|
Notes |
2018-04-16 17:00:55 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE SCOPE OF THE PLUMBING TO BE DONE IS UNCLEAR | | PLEASE PROVIDE PLUMBING PLAN INCLUDING A SANITARY AND | | WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC | | 107.3.5.1.3(13) | | | | 2. PLEASE PROVIDE COST BREAK DONE TO SHOW COMPLIANCE | | WITH FBC ACC 202.4.1 DISPROPORTIONATE COST. | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|