2018-04-06 17:29:01 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. FLAT ROOF - THE ENGINEERING SUBMITTED (PREPARED BY |
| STEPHEN WARTER) IS A PAPER PRINTOUT OF A DIGITALLY |
| SIGNED AND SEALED DOCUMENT. PER FBPE, THE SEAL IS TO |
| INCLUDE A STATEMENT THAT A PRINTED COPY OF THE DIGITAL |
| PLAN IS NOT A SIGNED AND SEALED DOCUMENT. PAPER PLANS |
| REQUIRE AN INK SEAL AND WET SIGNATURE; DIGITAL |
| DOCUMENTS REQUIRE A DIGITAL SEAL. YOU MAY SEND THE |
| ORIGINAL DIGITALLY SIGNED AND SEALED ENGINEERING |
| DIRECTLY TO ME VIA EMAIL TO RESOLVE THIS COMMENT. |
| INCLUDE THE PERMIT NUMBER IN THE SUBJECT LINE. |
| |
| 2. FLAT ROOF - CALCULATIONS STATE THAT EDGE STRIP (A) = |
| 3 FT, ENGINEER OF RECORD SPECIFIES 7.7' ON SHEET S004, |
| PLEASE CORRELATE. ALSO DESIGN PRESSURES ARE NOT |
| CONSISTENT WITH SEOR'S PRESSURES. THEY CAN BE HIGHER |
| BUT NOT LOWER, PLEASE REVISE. CALCULATIONS HAVE NOT |
| BEEN REVIEWED AT THIS TIME DUE TO LOWER DESIGN |
| PRESSURES ON THE DELEGATED ENGINEERING THAN SPECIFIED |
| BY SEOR. |
| |
| 3. METAL ROOF - THE AREA ATTRIBUTED TO A FASTENER IS TO |
| BE USED TO DETERMINE DESIGN PRESSURES. SEE SHEET S004, |
| DESIGN PRESSURES, ZONE 5 (PITCHED ROOF) DP REQUIREMENT |
| IS -72.10 FOR ZONE 2H, 20SF. THE FASTENING PROPOSED HAS |
| A LIMITATION OF -60PSF; PLEASE ADDRESS. |
| |
| 4. |
| |
| 2. THERE ARE TWO DIFFERENT PANEL WIDTHS; AREA |
| ATTRIBUTABLE TO A FASTENER C |