Plan Review Details - Permit 18040117
Plan Review Stops For Permit 18040117
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 13:52 Rev Time 0.00
Received By shill Date 2018-05-27 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 13:28 Rev Time 0.00
Received By shill Date 2018-05-03 Time 13:28 Sent To  
Notes
2018-05-03 13:30:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 3. METAL ROOF - THE AREA ATTRIBUTED TO A FASTENER IS TO
 BE USED TO DETERMINE DESIGN PRESSURES. SEE SHEET S004,
 DESIGN PRESSURES, ZONE 5 (PITCHED ROOF) DP REQUIREMENT
 IS -72.10 FOR ZONE 2H, 20SF. THE FASTENING PROPOSED HAS
 A LIMITATION OF -60PSF; PLEASE ADDRESS.
  
 IN THE FUTURE, PLEASE CONSIDER SUBMITTING DIGITALLY AS
 YOUR ENGINEER (WARTER, PE) HAS A DIGITAL SIGNATURE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By shill Date 2018-04-06 Time 14:49 Rev Time 0.00
Received By shill Date 2018-04-06 Time 12:55 Sent To  
Notes
2018-04-06 17:29:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FLAT ROOF - THE ENGINEERING SUBMITTED (PREPARED BY
 STEPHEN WARTER) IS A PAPER PRINTOUT OF A DIGITALLY
 SIGNED AND SEALED DOCUMENT. PER FBPE, THE SEAL IS TO
 INCLUDE A STATEMENT THAT A PRINTED COPY OF THE DIGITAL
 PLAN IS NOT A SIGNED AND SEALED DOCUMENT. PAPER PLANS
 REQUIRE AN INK SEAL AND WET SIGNATURE; DIGITAL
 DOCUMENTS REQUIRE A DIGITAL SEAL. YOU MAY SEND THE
 ORIGINAL DIGITALLY SIGNED AND SEALED ENGINEERING
 DIRECTLY TO ME VIA EMAIL TO RESOLVE THIS COMMENT.
 INCLUDE THE PERMIT NUMBER IN THE SUBJECT LINE.
  
 2. FLAT ROOF - CALCULATIONS STATE THAT EDGE STRIP (A) =
 3 FT, ENGINEER OF RECORD SPECIFIES 7.7' ON SHEET S004,
 PLEASE CORRELATE. ALSO DESIGN PRESSURES ARE NOT
 CONSISTENT WITH SEOR'S PRESSURES. THEY CAN BE HIGHER
 BUT NOT LOWER, PLEASE REVISE. CALCULATIONS HAVE NOT
 BEEN REVIEWED AT THIS TIME DUE TO LOWER DESIGN
 PRESSURES ON THE DELEGATED ENGINEERING THAN SPECIFIED
 BY SEOR.
  
 3. METAL ROOF - THE AREA ATTRIBUTED TO A FASTENER IS TO
 BE USED TO DETERMINE DESIGN PRESSURES. SEE SHEET S004,
 DESIGN PRESSURES, ZONE 5 (PITCHED ROOF) DP REQUIREMENT
 IS -72.10 FOR ZONE 2H, 20SF. THE FASTENING PROPOSED HAS
 A LIMITATION OF -60PSF; PLEASE ADDRESS.
  
 4.
  
 2. THERE ARE TWO DIFFERENT PANEL WIDTHS; AREA
 ATTRIBUTABLE TO A FASTENER C

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 13:54 Rev Time 0.00
Received By shill Date 2018-05-23 Time 12:56 Sent To  
Notes
2018-05-24 12:56:46RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 13:30 Rev Time 0.00
Received By shill Date 2018-04-30 Time 13:03 Sent To  
Notes
2018-05-01 13:03:25RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-06 Cont ID  
Sent By shill Date 2018-04-06 Time 17:29 Rev Time 0.00
Received By shill Date 2018-04-03 Time 10:36 Sent To  
Notes
2018-04-04 10:36:33SUBMITTAL ROUTED TO SHILL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 14:10 Rev Time 0.00
Received By shill Date 2018-05-27 Time 14:10 Sent To  
Notes
2018-05-27 14:11:18DIGITALLY SIGNED & SEALED ORIGINAL RECEIVED VIA EMAIL
  