Plan Review Details - Permit 18040104
Plan Review Stops For Permit 18040104 |
Review Stop |
AIPP |
ART IN PUBLIC PLACES |
Rev No |
1 |
Status |
P |
Date |
2019-03-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-03-26 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-03-26 |
Time |
15:47 |
Sent To |
|
|
Notes |
2019-03-26 15:47:13 | AIPP SATISFIED PER EMAIL FROM S.WELTER DATED 2/11/19 | | ROUTED EMAIL TO FILENET | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2018-10-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-10-31 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-10-31 |
Time |
16:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-10-23 |
Time |
19:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-10-19 |
Time |
06:50 |
Sent To |
|
|
Notes |
2018-10-23 19:03:39 | ****PROVISOS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC EC = FBC ENERGY CONSERVATION | | | | SEVERAL COMMENTS WERE NOT ADDRESSED. PRIOR TO CO OR | | TCO, SUBMIT A REVISION ADDRESSING THE FOLLOWING: | | | | 1. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF | | COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS, | | IBC2000 OR IBC2003). | | | | 2. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER | | TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING | | SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN | | IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS | | OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4), | | SO THIS EXCEPTION CANNOT BE UTILIZED. | | | | RESPONSE LETTER STATES TO SEE ATTACHED LETTER. THIS WAS | | AGREED TO BY BUILDING OFFICIAL WITH RATIONALE TO BE | | PRESENTED IN A SIGNED AND SEALED LETTER, PLEASE | | PROVIDE. | | | | 3. ALS.1.1, REGARDING THE EXISTING STAIR: FBC EB 805.2 | | EXCEPTION 2, THIS WAS COMPLIANT UNDER THE CODE UNDER | | WHICH IT WAS CONSTRUCTED. INSPECTOR WILL VERIFY THAT | | DEVIATION BETWEEN STAIR TREADS WILL ADJUSTED IF UNSAFE. | | PER ARCHITECT, THE GUARDRAIL AND HANDRAIL WILL BE | | CONSTRUCTED TO COMPLY WITH FBC B 2014. | | | | 4. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE I | | OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED, SEE | | FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON | | COMBUSTIBLE BUILDING. | | | | RESPONSE LETTER STATES THAT SPEC SHEETS SHOWING | | COMPLIANCE ARE ATTACHED; UNABLE TO LOCATE. | | | | 5. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO | | PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP. | | | | 6. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE | | ACCORDINGLY: | | A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING | | COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT | | DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE | | EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING. | | B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA | | FOR THE OTHERS? | | C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR | | THE OTHERS? | | D. NO DOORS SHOWN. | | E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES | | OF ROOFS ON THIS BUILDING? | | F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS. | | | | 7. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY | | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING | | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. | | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 | | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, | | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS | | COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE | | SUBMITTED (LIST MAY NOT BE COMPREHENSIVE): | | NANAWALL | | STOREFRONT | | GLAZED DOORS | | OPAQUE DOORS | | OVERHEAD DOORS | | | | WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION | | PLAN. | | | | 8. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | REQUIRED FOR: | | LIGHT POLES/SITE LIGHTING | | FIRE ALARM | | FIRE SPRINKLER | | LOW VOLTAGE | | ACCESS | | LANDSCAPING | | IRRIGATION | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | *************************** | | INTERNAL USE ONLY: | | | | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | SQUARE FEET - 36706 | | | | CONSTRUCTION TYPE: IIA | | UNITS: | | FLOORS: 4 | | BEDROOMS: | | ROOMS: | | SQ FT LIVABLE: 36706 | | SQ FT FOOTPRINT: 36706 | | SQ FT ROOF: 36706 | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | KNOWN): | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | XX.XX | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | XX.XX | | OCC LOAD: | | PROP USE: OFFICE | | SPRINKLER SYS? Y | | SPRK REQ'D? Y | | BATHRMS: | | | | BLDG CODE: FL 2014 | | OCC CLASS: 5TH ED B | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-08-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-22 |
Time |
18:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-21 |
Time |
18:25 |
Sent To |
|
|
Notes |
2018-08-24 06:47:41 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1-3. OK | | | | 4. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF | | COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS, | | IBC2000 OR IBC2003). | | | | 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS ON | | ALS.1.4, UNABLE TO LOCATE SELECTION. IT APPEARS THAT | | PLAN WAS REVISED TO COMPLY, BUT PLEASE INDICATE | | SELECTION. REVIEW OF ACCESSIBLE MEANS OF EGRESS WILL BE | | DONE AFTER METHOD (IBC2000 OR IBC2003) IS INDICATED. | | | | 5. OK | | | | 6-7. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER | | TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING | | SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN | | IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS | | OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4), | | SO THIS EXCEPTION CANNOT BE UTILIZED. | | | | 8. OK | | | | 9. FBC 107.3.5.1.1(5), FBC EB 904, PROVIDE FIRE | | PROTECTION PLANS TO SHOW COMPLIANCE WITH STANDPIPES FBC | | B 905.3.1(1) AND NFPA13 SPRINKLERS FBC B 903.2.11.3. | | | | 10. FBC 107.3.5.1.1(6), FBC EB 904, PROVIDE FIRE ALARM | | PLANS TO SHOW COMPLIANCE WITH FBC B 907.2.2. | | | | 11. ALS.1.1, FBC 107, NOTE STATES THAT "2014 FBC | | SECTION 1004.4 FIXED SEATING" (CONFERENCE ROOM), IS | | THIS CORRECT? IF THIS IS NOT FIXED SEATING, REVISE NOTE | | AND REVISE OCCUPANT LOAD ACCORDINGLY. | | | | 2ND REVIEW, THIS LANGUAGE IS STILL ON THIS PAGE. THIS | | WILL BE REDLINED IF NOT REMOVED. RESPONSE LETTER REFERS | | TO "REVISED ALS1.1" BUT A NEW SHEET WAS NOT PROVIDED. | | | | 12. ALS.1.1, PLAN INDICATES SIGNAGE AT STAIR INDICATING | | NO ACCESS. IT DOES NOT APPEAR THAT A SIGN WILL BE | | ADEQUATE TO PREVENT USE OF THE STAIR. ADDITIONAL MEANS | | MAY BE REQUIRED. PRIOR TO C.O. ADDITIONAL INFORMATION | | WILL BE REQUIRED REGARDING HOW OCCUPANTS WILL BE | | PREVENTED FROM ACCESSING THE STAIR. UNLESS YOU WISH TO | | REVISE THE PLAN OR PROPOSE SOMETHING AT THIS TIME, THIS | | WILL BE A PROVISO ITEM. | | | | OR, SEE FBC EB 805.2 EXCEPTION 2. | | | | 13. OK | | | | 14. ALS.1.2, FBC A 202.4, IT APPEARS THAT A PORTION OF | | THE 2ND FLOOR LACKS VERTICAL ACCESSIBILITY. PROVIDE | | RATIONALE. PLEASE PROVIDE VIA EMAIL PRIOR TO | | RESUBMITTAL. | | | | 2ND REVIEW, RESPONSE LETTER STATES THAT THIS WAS | | REVISED, BUT SHEET ALS1.2 WAS NOT REVISED (NOR WAS | | A1.2.1, ALSO OTHER 2ND FLOOR PAGES). | | | | 15-16. OK | | | | 17. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE | | I OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED, | | SEE FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON | | COMBUSTIBLE BUILDING. | | | | 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED. | | | | 18-21. OK | | | | 22. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO | | PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP. | | | | 23-24. OK | | | | 25. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE | | ACCORDINGLY: | | A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING | | COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT | | DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE | | EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING. | | B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA | | FOR THE OTHERS? | | C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR | | THE OTHERS? | | D. NO DOORS SHOWN. | | E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES | | OF ROOFS ON THIS BUILDING? | | F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS. | | | | 2ND REVIEW, NEW ENERGY CALCS WERE NOT PROVIDED. | | | | NEW COMMENT: | | | | 26. ALS0.1, OCCUPANCY CALCULATIONS, CLOUD OBSTRUCTS THE | | OCCUPANT LOAD. | | | | | | 27. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING | | PROVISOS: | | | | A. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY | | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING | | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. | | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 | | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, | | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS | | COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE | | SUBMITTED (LIST MAY NOT BE COMPREHENSIVE): | | NANAWALL | | STOREFRONT | | GLAZED DOORS | | OPAQUE DOORS | | OVERHEAD DOORS | | | | WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION | | PLAN. | | | | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | REQUIRED FOR: | | LIGHT POLES/SITE LIGHTING | | FIRE ALARM | | FIRE SPRINKLER | | LOW VOLTAGE | | ACCESS | | LANDSCAPING | | IRRIGATION | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | *************************** | | INTERNAL USE ONLY: | | | | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | SQUARE FEET - 36706 | | | | CONSTRUCTION TYPE: ??? | | UNITS: | | FLOORS: 4 | | BEDROOMS: | | ROOMS: | | SQ FT LIVABLE: 36706 | | SQ FT FOOTPRINT: 36706 | | SQ FT ROOF: 36706 | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | KNOWN): | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | XX.XX | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | XX.XX | | OCC LOAD: | | PROP USE: OFFICE | | SPRINKLER SYS? Y | | SPRK REQ'D? Y | | BATHRMS: | | | | BLDG CODE: FL 2014 | | OCC CLASS: 5TH ED B | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-09 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-09 |
Time |
09:34 |
Sent To |
|
|
Notes |
2018-06-09 15:51:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. SP1.0.1 AREA FOR THE ROOF TERRACE OPEN TO AIR (4685 | | SF) IS NOT CONSISTENT WITH THE ROOF PLAN WHICH SHOWS | | 1845 SF, REVISE OR CLARIFY, FBC B 1004. | | | | 2. SP1.0.1 PARKING IS SHOWN AS 48 SPACES AND 1 HANDICAP | | SPACE. FBC A TABLE 208.2, TWO ACCESSIBLE SPACES ARE | | REQUIRED. | | | | 3. SP1.0.1 FBC B TABLE 705.8, REVISE PLAN TO SHOW | | COMPLIANCE. DISTANCE TO CENTER OF ROAD IS NOT CLEAR | | (ALLEY). | | | | 4. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF | | COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS, | | IBC2000 OR IBC2003). | | | | 5. ALS.0.1, CHANGE OF OCCUPANCY IS NOTED FOR THE 4TH | | FLOOR. THE AREAS WHICH WERE ENCLOSED BUT NOT | | CONDITIONED ARE ALSO CHANGE OF OCCUPANCY. THE | | CONVERSION OF EXTERIOR SPACE UNDER ROOF TO INTERIOR | | SPACE IS AN ADDITION. REVISE CODE SUMMARY TO CLARIFY | | SCOPE OF WORK. | | | | 6. ALS.0.1, COMPLIANCE WITH FBC B TABLE 503 NOT CLEAR. | | SHEET ALS 0.1 STATES THAT THIS IS NON SEPARATED MIXED | | USE "BUSINESS: 9000 SF/STORY X 3 = 27,000 SF/FLOOR". | | | | SEE FBC B 508.3.2, COMPLIANCE WITH THE MOST STRINGENT | | OCCUPANCY IS TO BE SHOWN; IN THIS CASE ASSEMBLY. 9000 | | SF IS THE LIMITATION FOR BUSINESS, TYPE V CONSTRUCTION | | WHICH WITH SPRINKLER INCREASE IS LIMITED TO 3 STORIES. | | REVISE PLAN TO INCLUDE BUILDING TYPE AND SHOW | | COMPLIANCE WITH FBC B TABLE 503. | | | | 7. ALS.0.1, FBC 107, REVISE PLAN TO INCLUDE BUILDING | | TYPE, OR ADVISE WHERE THIS INFORMATION CAN BE FOUND. | | | | 8. ALS.0.1, "SMOKE EVACUATION REQUIREMENT", NFPA101 IS | | REFERENCED. REVISE TO INCLUDE FBC. PROVIDE A SECTION SO | | EXCEPTION TO SMOKE CONTROL IS CLEAR, FBC B 404.5. | | | | 9. FBC 107.3.5.1.1(5), FBC EB 904, PROVIDE FIRE | | PROTECTION PLANS TO SHOW COMPLIANCE WITH STANDPIPES FBC | | B 905.3.1(1) AND NFPA13 SPRINKLERS FBC B 903.2.11.3. | | | | 10. FBC 107.3.5.1.1(6), FBC EB 904, PROVIDE FIRE ALARM | | PLANS TO SHOW COMPLIANCE WITH FBC B 907.2.2. | | | | 11. ALS.1.1, FBC 107, NOTE STATES THAT "2014 FBC | | SECTION 1004.4 FIXED SEATING" (CONFERENCE ROOM), IS | | THIS CORRECT? IF THIS IS NOT FIXED SEATING, REVISE NOTE | | AND REVISE OCCUPANT LOAD ACCORDINGLY. | | | | 12. ALS.1.1, PLAN INDICATES SIGNAGE AT STAIR INDICATING | | NO ACCESS. IT DOES NOT APPEAR THAT A SIGN WILL BE | | ADEQUATE TO PREVENT USE OF THE STAIR. ADDITIONAL MEANS | | MAY BE REQUIRED. PRIOR TO C.O. ADDITIONAL INFORMATION | | WILL BE REQUIRED REGARDING HOW OCCUPANTS WILL BE | | PREVENTED FROM ACCESSING THE STAIR. UNLESS YOU WISH TO | | REVISE THE PLAN OR PROPOSE SOMETHING AT THIS TIME, THIS | | WILL BE A PROVISO ITEM. | | | | OR, SEE FBC EB 805.2 EXCEPTION 2. | | | | 13. COVER SHEET, FBC B 501.2, ADDRESS IDENTIFICATION, | | IS THE ADDRESS SHOWN CONCEPTUAL, OR INTENDED TO COMPLY | | WITH THIS SECTION? | | | | 14. ALS.1.2, FBC A 202.4, IT APPEARS THAT A PORTION OF | | THE 2ND FLOOR LACKS VERTICAL ACCESSIBILITY. PROVIDE | | RATIONALE. PLEASE PROVIDE VIA EMAIL PRIOR TO | | RESUBMITTAL. | | | | 15. AD.1.2.3, FBC 107, CLARIFY EXISTING OCCUPANCY OF | | THE ROOFTOP ROOM. | | | | 16. ALS1.4, FBC B 1021.1, IT APPEARS THAT THE ROOF | | TERRACE IS REQUIRED TO HAVE TWO MEANS OF EGRESS. IS THE | | DOTTED LINE A DOOR IN THE NANAWALL? DOES IT HAVE | | HARDWARE? NOTE STATES "HOLD OPEN ON STATIONARY DOOR". | | IT'S NOT CLEAR HOW THIS COMPLIES WITH FBC B 1008.1.10, | | PANIC BARS. | | | | 17. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE | | I OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED, | | SEE FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON | | COMBUSTIBLE BUILDING. | | | | 18. PLUMBING ACCESSIBILITY COMMENTS ARE APPLICABLE FOR | | BUILDING REVIEW. | | | | 19. SEE THRESHOLD REVIEW. ALL STRUCTURAL SHEETS ARE TO | | INCLUDE THE STATEMENT REQUIRED BY FLORIDA STATUTE 553. | | A THRESHOLD INSPECTION PLAN IS REQUIRED AND THE PLAN IS | | TO BE NOTED AS SUCH. PLANS FOR THE STRUCTURE PERMIT AND | | FOR THIS INTERIOR PERMIT ARE TO BE REVISED. | | | | 20. A.8.0.1, FBC B TABLE 716.5, THE DOORS IN THE TWO | | HOUR STAIR EXIT ENCLOSURES ARE REQUIRED TO BE 90 | | MINUTE. FOR EXAMPLE, DOOR 210 SHOWS NO RATING, 216 | | PROPOSES 45 MINUTE; REVISE AND CHECK ALL. | | | | 21. A.8.0.1, NO PANIC HARDWARE PROPOSED ON ROOF | | TERRACE; ALL DOORS SERVING ASSEMBLY OCCUPANCY AND AN | | OCCUPANT LOAD 50 AND OVER ARE TO HAVE PANIC BARS FBC B | | 1008.1.10. | | | | 22. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO | | PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP. | | | | 23. THE STRUCTURE PERMIT WAS ISSUED TO QUEST | | CONTRACTING. THIS APPLICATION WAS SUBMITTED BY DPR | | CONSTRUCTION. WILL THE CONTRACTOR BE CHANGED TO QUEST? | | IF NOT, PRIOR TO ISSUANCE OF THIS PERMIT A LETTER | | SIGNED BY THE QUALIFIERS OF THE TWO COMPANIES STATING | | THAT THEY WILL WORK TOGETHER TO OBTAIN CODE COMPLIANCE, | | FBC 107. THIS IS REQUIRED WHEN THERE IS MORE THAN ONE | | CONTRACTOR ON A PROJECT AND RESPONSIBILITIES MAY | | OVERLAP. | | | | 24. FBC B 3306, IT APPEARS THAT A BARRIER AND OVERHEAD | | PROTECTION ARE REQUIRED. ACQUIRE PERMITS. IT APPEARS | | THAT WORK HAS ALREADY BEEN DONE WITHOUT THIS PROTECTION | | IN PLACE. | | | | 25. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE | | ACCORDINGLY: | | A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING | | COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT | | DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE | | EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING. | | B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA | | FOR THE OTHERS? | | C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR | | THE OTHERS? | | D. NO DOORS SHOWN. | | E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES | | OF ROOFS ON THIS BUILDING? | | F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS. | | | | 26. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING | | PROVISOS: | | | | A. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY | | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING | | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. | | CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5 | | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, | | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS | | COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE | | SUBMITTED (LIST MAY NOT BE COMPREHENSIVE): | | NANAWALL | | STOREFRONT | | GLAZED DOORS | | OPAQUE DOORS | | OVERHEAD DOORS | | | | WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION | | PLAN. | | | | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | REQUIRED FOR: | | LIGHT POLES/SITE LIGHTING | | FIRE ALARM | | FIRE SPRINKLER | | LOW VOLTAGE | | ACCESS | | LANDSCAPING | | IRRIGATION | | ALL OTHER ITEMS OTHER THAN BMEP | | | | | | *************************** | | INTERNAL USE ONLY: | | | | USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG | | SQUARE FEET - 36706 | | | | CONSTRUCTION TYPE: ??? | | UNITS: | | FLOORS: 4 | | BEDROOMS: | | ROOMS: | | SQ FT LIVABLE: 36706 | | SQ FT FOOTPRINT: 36706 | | SQ FT ROOF: 36706 | | | | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF | | KNOWN): | | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): | | XX.XX | | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: | | XX.XX | | OCC LOAD: | | PROP USE: OFFICE | | SPRINKLER SYS? Y | | SPRK REQ'D? Y | | BATHRMS: | | | | BLDG CODE: FL 2014 | | OCC CLASS: 5TH ED B | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2018-11-02 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-11-02 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-11-02 |
Time |
08:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-10-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-16 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-16 |
Time |
10:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-08-16 |
Time |
|
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-08-16 |
Time |
15:57 |
Sent To |
|
|
Notes |
2018-08-16 15:45:13 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY | | SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS | | THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC | | 107.2.1 (NOT PROVIDED. REQUIRED INFORMATION FOR RISER | | DIAGRAM. NEC 215.5) | | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 (NOT PROVIDED, DEFERRED SUBMITTAL | | ACCEPTABLE.) | | 7. CORRECTED. | | 8. CORRECTED. | | 9. CORRECTED. | | 10. CORRECTED. | | | | NEW COMMENT: | | | | 11. DOOR TO ELECTRICAL ROOM SHALL OPEN IN THE DIRECTION | | OF EGRESS AND BE EQUIPPED WITH LISTED PANIC HARDWARE. | | PROVIDE CORRECTION. NEC 110.26(C)(3) | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-05-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-21 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-20 |
Time |
14:13 |
Sent To |
|
|
Notes |
2018-05-21 09:43:02 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE | | TENANTS. THIS WIREWAY SHOULD BE TIED INTO THE GROUNDING | | ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC 250.50, | | 250.58 | | 2. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE | | TENANTS. THE WIREWAY IS SHOWN AS BEING INSTALLED, WHILE | | THE METERS AND DISCONNECTS ARE SHOWN AS FUTURE. THIS | | WIREWAY CANNOT BE INSTALLED WITH ENERGIZED CONDUCTORS | | AND NO OVERCURRENT PROTECTION. PROVIDE CORRECTION. NEC | | 230.70 | | 3. PROVIDE LABELING OF MAINS PER NEC 230.2(E) | | 4. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET | | ALS.0.1 AND E0.1 IS NOT THE CURRENT CODE. PROVIDE | | CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) | | 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY | | SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS | | THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC | | 107.2.1 | | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | 8. RESTROOMS ON 3RD FLOOR DO NOT SHOW THE AUTOMATIC | | LIGHTING CONTROL REQUIRED. PROVIDE CORRECTION. FBC EC | | C405.2 | | 9. SHEET E2.5, THE UNISEX RESTROOM DOES NOT SHOW THE | | AUTOMATIC LIGHTING CONTROL REQUIRED. PROVIDE | | CORRECTION. FBC EC C405.2 | | 10. PROVIDE NOTE REQUIRING GFCI DEVICE FOR WATER | | COOLERS TO BE READILY ACCESSIBLE. NEC 422.5 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2018-11-01 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-11-01 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-11-01 |
Time |
10:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2018-09-27 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-09-27 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-09-26 |
Time |
11:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2018-07-24 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-07-24 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-07-24 |
Time |
12:47 |
Sent To |
|
|
Notes |
2018-07-24 14:01:30 | PERMIT # 18040104 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 2ND REVIEW COMMENTS: | | | | 1) BECAUSE THIS BUILDING DOES NOT HAVE AN EXISTING FIRE | | SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM: ENGINEERED | | FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS | | ARE REQUIRED FOR A GENERAL/MASTERL BUILDING PERMIT. | | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE | | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS | | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) | | FOR A SUB-PERMIT. | | | | 2) PER FLORIDA ADMINISTRATIVE CODE SECTION | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-05-02 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-05-02 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-05-02 |
Time |
10:07 |
Sent To |
|
|
Notes |
2018-05-02 11:46:48 | PERMIT # 18040104 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED COMMENTS: | | | | 1) SHEET ALS 1.0: THE TRAVEL DISTANCE TO THE STAIRS BY | | THE PRODUCTION ROOM (003) INDICATES 270 FEET. PER NFPA | | 101, CHAPTER 39, TRAVEL DISTANCE MAY NOT EXCEED 200 | | FEET IF THE BUILDING IS NOT PROTECTED BY A FIRE | | SPRINKLER SYSTEM. PLEASE PROVIDE FOR CODE COMPLIANCE OR | | JUSTIFICATION. | | | | 39.2.6.2 | | TRAVEL DISTANCE TO AN EXIT SHALL NOT EXCEED 200 FT (61 | | M) FROM ANY POINT IN A BUILDING, UNLESS OTHERWISE | | PERMITTED BY 39.2.6.3. | | | | 39.2.6.3 | | TRAVEL DISTANCE SHALL NOT EXCEED 300 FT (91 M) IN | | BUSINESS OCCUPANCIES PROTECTED THROUGHOUT BY AN | | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN | | ACCORDANCE WITH SECTION 9.7. | | | | 2) SHEET ALS 1.1: INDICATES AN EGRESS TRAVEL DISTANCE | | OF 202 FEET. PLEASE PROVIDE FOR COMPLIANCE OF CODE, AS | | NOTED ABOVE, OR JUSTIFICATION. | | | | 3) SHEET ALS 1.4: PLEASE PROVIDE JUSTIFICATION THAT | | SHOWS COMPLIANCE WITH ALL APPLICABLE ASPECTS OF NFPA | | 101: 7.2.12 - AREA OF REFUGE; INCLUDING ALL DIMENSIONS | | APPLICABLE TO THE STAIRWELL (MIN CLEAR WIDTH OF 48 | | INCHES IS REQUIRED - - STAIR A HAS A CLEAR WIDTH OF | | ONLY 44 INCHES), LOCATION OF REQUIRED SIGNAGE, TWO-WAY | | COMMUNICATION (IF REQUIRED), ETC. | | | | 4) PER NFPA 101: 39.3.4 - A FIRE ALARM SYSTEM IS | | REQUIRED FOR THIS OCCUPANCY. | | | | 5) DOES THIS BUILDING HAVE A FULL OR PARTIAL FIRE | | SPRINKLER SYSTEM? OR IS A FIRE SPINKLER SYSTEM GOING TO | | BE INSTALLED? | | | | 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | 7) COULD NOT FIND DETAILS FOR STAIR A. NOT INCLUDED IN | | SHEETS A6-0-1 THROUGH A6-0-5. | | | | 8) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | DURING PLAN RESUBMISSION. | | | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-11-02 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-10-31 |
Time |
14:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-10-23 |
Time |
19:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-09-25 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-08-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-22 |
Time |
18:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-19 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-09 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-04-17 |
Time |
15:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2018-08-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-28 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-28 |
Time |
12:43 |
Sent To |
|
|
Notes |
2018-08-28 12:43:37 | REVIEWED UNDER STRUCTURE PERMIT 17120610 | | | | PALM BEACH COUNTY REVIEWED FOR IMPACT FEES. | | NO FEES DUE. | | 4/5/18 18 11477 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-27 |
Time |
19:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-27 |
Time |
19:33 |
Sent To |
|
|
Notes |
2018-05-27 19:35:14 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. | | PROVIDE PRINTED FLOOR PLANS INCLUDING SQUARE FOOT | | AREAS. THE PLANS ARE TO BE STAMPED AND THE RECEIPT | | SHOWING THAT FEES DUE WERE PAID IS TO BE PROVIDED. | | 561-233-5025 FOR MORE INFORMATION | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2018-11-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-11-01 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-11-01 |
Time |
07:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-23 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-23 |
Time |
09:33 |
Sent To |
|
|
Notes |
2018-10-23 09:56:20 | 3RD REVIEW- FBC-2017 MECHANICAL | | PERMIT #18040104 | | 10/23/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.1: AS PREVIOUSLY NOTED THERE APPEARS TO BE | | AN INADEQUATE AMOUNT OF O/A PROVIDED TO THE BASEMENT | | ROOMS AND SPACES FOR OCCUPANTS, AND FOR MAKEUP AIR FOR | | THE BATHROOM EXHAUST. THE CURRENT PLAN SHOWS ONLY 135 | | CFMS PROVIDED TO LOUNGE 003 FROM THE OARTU WHICH IS NOT | | IN COMPLIANCE WITH TABLE 403.3.1.1 AND SECTION 501.4. | | IN ADDITION PLEASE NOTE THE | | | | FOLLOWING: A) THE OARTU SCHEDULE ON SHEET M7.1 HAS A | | CAPACITY OF 2730 CFMS, AND THE AIR BALANCE SCHEDULE ON | | M7.2 INDICATES 400 CFMS TO BE PROVIDED TO THE BASEMENT | | AND 855 CFMS TO THE FIRST FLOOR. THIS DATA APPEARS TO | | INDICATE A MISTAKE IN SYSTEM SELECTION. B) THE RTU #2 | | SCHEDULE ON M7.1 INDICATES THE UNIT HAS AN O/A CAPACITY | | OF 1387 CFMS, HOWEVER THE AIR BALANCE | | | | SCHEDULE INDICATES A REQUIREMENT OF 2705 CFMS. AGAIN AN | | APPARENT MISTAKE IN SYSTEM SELECTION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-08-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-08-21 |
Time |
07:42 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-08-15 |
Time |
07:42 |
Sent To |
|
|
Notes |
2018-08-15 07:50:59 | 2ND REVIEW- PART 2, FBC-2017 MECHANICAL | | PERMIT #18040104 | | 8/21/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | THE FOLLOWING COMMENTS ARE BASED ON THE 1ST REVIEW | | COMMENTS WHICH STILL EXIST EITHER PARTIALLY OR | | COMPLETELY . | | | | 1) THE REQUESTED ELECTRONICALLY SIGNED AND SEALED | | ENERGY AND AC CALCULATIONS WERE NOT PROVIDED. | | | | 2) THE ENERGY COMPLIANCE FORM IS INDICATING THE VRF | | UNITS ARE "WATER SOURCE" BUT THAT DOES NOT MATCH WITH | | THE EQUIPMENT SCHEDULES PROVIDED ON THE PLANS WHICH | | INDICATE AIR SOURCE UNITS- SEE TABLE C403.2.3(11) FBC | | EC. | | | | 3) THE ENERGY COMPLIANCE FORM DOES NOT LIST ANY DATA | | FOR RTU-2 (528.2 MBH) AND THE OARTU (107.1 MBH) - | | PLEASE PROVIDE THE DATA. | | | | 4) M7.1 & M7.2: THE ENERGY COMPLIANCE FORM LISTS RTU-1 | | AS A 93.3 MBH UNIT, HOWEVER THERE IS NO RTU-1 IN THE | | SCHEDULES OR WITH THAT COOLING CAPACITY. | | | | 5) AS PREVIOUSLY NOTED IN THE FIRST REVIEW, THERE IS NO | | COMPLIANCE DATA LISTED IN THE ENERGY COMPLIANCE FORM | | FOR AHU'S 5, 6, 7, & 8. | | | | 6) REFER TO SHEETS M2.5, M6.1 AND M7.1: PLEASE CORRECT | | THE LABELING OF THE LARGE 528.2 MBH RTU WHICH IS | | INDICATED AS RTU-2 ON THE PLANS, AND RTU-1 IN THE | | SCHEDULE. | | | | 7) SHEETS ALS.01 AND M0.1 HAVE NOT BEEN UPDATED TO LIST | | THE CORRECT CODE EDITIONS AND THE CORRECT NOA # FOR THE | | ROOF STAND. | | | | 8) SHEET M6.1: PLEASE PROVIDE EXHAUST VENTILATION | | CALCULATIONS AND AIR BALANCE CALCULATIONS ON THE PLAN. | | | | 9) SHEET M2.1: PLEASE CLARIFY HOW O/A IS BEING PROVIDED | | TO THE LOUNGE ROOM THAT IS CLOSE TO THE STAIRCASE, AND | | HOW MAKEUP AIR IS BEING PROVIDED FOR THE TOILET ROOM | | EXHAUST SYSTEM. | | | | 10) SHEET M2.2: REFER TO SECTION 502.13 FBC M AND | | CLARIFY HOW THE EXHAUST VENTILATION SYSTEM IN THE | | GARAGE WILL OPERATE- CONTINOUSLY OR IN ACCORDANCE WITH | | SECTION 404. PLEASE PROVIDE EXHAUST VENTILATION | | CALCULATIONS FOR THE GARAGE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #18040104 | | 8/15/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) 2ND REQUEST FOR ELECTRONICALLY SIGNED AND SEALED | | ENERGY AND AC CALCULATIONS- SEE COMMENT #1 FROM THE 1ST | | REVIEW. | | | | 2) ACCORDING TO THE RESPONSE NARRATIVE TO THE 1ST | | REVIEW COMMENTS, SHEETS M0.1, M2.1, M2.5, M6.1, AND | | M7.1 HAVE BEEN REVISED, HOWEVER THOSE SHEETS HAVE NOT | | BEEN UPDATED, AND M6.1 HAS BEEN REPLACED WITH E.01. THE | | REVIEW IS STOPPED AT THIS POINT UNITL REVISED SHEETS | | ARE UPLOADED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-22 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-22 |
Time |
07:26 |
Sent To |
|
|
Notes |
2018-05-22 12:04:49 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18040104 | | 5/22/18 | | | | CODES IN EFFECT: | | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE AC AND ENERGY CALCULATIONS ARE NOT | | ELECTRONICALLY SIGNED AND SEALED. PLEASE REFER TO RULE | | 61G15-23.005: ENGINEERING PLANS, SPECIFICATIONS. | | REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED | | AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION | | 471.025 FS, AND RULE 61G15-23.001 FAC MAY BE SIGNED | | ELECTRONICALLY AS PROVIDED HEREIN BY THE PROFESSIONAL | | ENGINEER IN RESPONSUIBLE CHARGE. | | | | 2) ENERGYGAUGE FORM: A) COMPLIANCE DATA FOR AHU'S 5, 6, | | 7, & 8 HAS NOT BEEN PROVIDED. B) RTU-1 LISTED AT 93,300 | | BTUH IN THE ENERGY COMPLIANCE DATA IS NOT SHOWN IN THE | | AC EQUIPMENT SCHEDULES. C) THE 52820 BTUH COOLING | | CAPACITY FOR VAV-3 SHOWN IN THE CALCS DOES NOT MATCH | | THE CAPACITY SHOWN IN THE EQUIPMENT SPECIFICATIONS ON | | SHEET M7.1. | | | | 3) SHEETS ALS.01 & M0.1: THE PLANS SHALL BE DESIGNED IN | | ACCORDANCE WITH THE FLORIDA BUILDING CODES SIXTH | | EDITION 2017. PLEASE UPDATE THE CODE DATA, AND THE NOA | | FOR THE ROOF STAND. NOA #13-1017.09 HAS BEEN SUPERSEDED | | BY NOA #15-0902.05. | | | | 4) M2.5 & M7.1: RTU-1 IS MISLABLED AS RTU-2 ON THE ROOF | | PLAN. SHOW THE LOCATION OF THE 7.5 TON RTU FOR THE | | BUSINESS LOUNGE. | | | | 5) PROVIDE COMPLETE VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES IN ACCORDANCE WITH TABLE 403.3.1.1 FBC | | MC. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR, AND EXHAUST AIR WHERE | | REQUIRED. | | | | 6) M0.1 & M2.1: DUCT SMOKE DETECTORS ARE REQUIRED FOR | | THE MMU SUPPLY SYSTEMS PER SECTION 606.2.2 FBC MC. | | PLEASE SEE EXCEPTION 2 WHICH ALLOWS SMOKE DETECTORS TO | | BE PLACED IN THE RETURN AIR PLENUMS. | | | | 7) M2.1: THE PLAN APPEARS TO SHOW ONLY 135 CFMS OF | | OUTSIDE AIR FOR ALL THE OCCUPIED SPACES ON THE FLOOR. | | SEE COMMENT #4 ABOVE AND PROVIDE CALCULATIONS. | | | | 8) M2.1: PROVIDE A MEANS OF RETURN AIR FOR THE SYSTEM. | | | | 9) M2.1:USING THE CORRIDOR FOR MAKEUP AIR FOR THE | | TOILET ROOM EXHAUST SYSTEMS REQUIRES THE CORRIDOR TO BE | | DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER | | THAN THE RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR- | | SECTION 601.2 (1) FBC MC. | | | | 10) M2.2: SHOW HOW IS AIR BEING RETURNED FOM THE | | CONFERENCE AND OFFICE ROOMS- SECTION 601.6 FBC MC. | | | | 11) M2.5: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY | | DUCT OF RTU-1 (RTU-2 ON THE PLAN- SEE COMMENT #4). | | | | 12) P2.5: PROVIDE A DETAIL SHOWING HOW THE CONDENSATE | | PIPING WILL BE SUPPORTED ON THE ROOF- TYPE AND SPACING | | OF SUPPORTS | | | | 13) PROVIDE TWO COPIES OF NOA #15-0902.05. ACKNOWLEDGED | | THAT COMPLETE STRUCTURAL ENGINEERING FOR INSTALLATION | | OF THE RTU'S WILL BE A DEFERRED SUBMITTAL PER NOTE ON | | M6.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-08-22 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-22 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-21 |
Time |
15:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-06-01 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-01 |
Time |
07:42 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-05-24 |
Time |
17:48 |
Sent To |
|
|
Notes |
2018-05-31 17:44:01 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. ALS-1-2 THE PLUMBING FIXTURE COUNT STATES A | | OCCUPANT LOAD OF 90 THE 2ND FLOOR OCCUPANT LOAD IS | | LISTED AT 119 PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 2. SHT. A9-5-1 THE SHOWER IN THE WOMENS APPEARS TO BE A | | ALTERNATE ROLL-IN THE DEPTH OF THE SHOWER IS SHOWN AS | | 371/4" THE CODE CALLS OUT FOR A HARD DIMENSION OF 36" | | SHALL COMPLY WITH FBC PL 608.2.3 | | | | 3. SHT. A9-5-1 PLEASE SHOW DIMENSIONS OF THE SHOWER IN | | THE MENS BATHROOM. PER WPB AMEND TO FBC 107.2.1 | | | | 4. SHT A9-5-2 SHT. A9-5-2 THE TOILET IN THE BATHROOMS # | | 203,205,208 SHALL COMPLY WITH FBC PL 604.2 | | | | 5. SHT. A9-5-9 THE GRAB BARS FOR THE TOILET IN | | BATHROOMS # 203,205, 208 SHALL COMPLY WITH FBC PL | | 604.5.1 AND 604.5.2 , 609.4 | | | | 6. SHT. A9-5-9 THE SHOWERS IN BATHROOMS # 203,205,208 | | SHALL COMPLY WITH FBC PL 608 PLEASE INDICATE ON THE | | PLAN WHICH TYPE OF SHOWER COMPARTMENT THEY ARE DESIGNED | | TO TO MEET AND SHOW ALL DIMENSIONS. PER WPB AMEND TO | | FBC 107.2.1 | | | | 7. SHT A9-5-9 SHOW COMPLIANCE WITH FBC PL 608.3 THE | | GRAB BARS IN-THE SOWERS FOR BATHROOMS # 203,205,208 | | | | 8. SHT. P5.1 THE SHOWER IN BATHROOM 203, 208 MEN'S | | BATHROOM IN BASEMENT ARE SHOWING A HORIZONTAL DRY VENT | | AND ARE NOT CODE COMPLIANT ALL DRY VENTS SHALL COMPLY | | WITH FBC PL 905.3, 905.4 | | | | 9. SHT. P5.1 THE TOILET 203 IS NOT VENTED PROPERLY IT | | SHALL BE VENTED BEFORE CONNECTING TO THE BUILDING | | DRAIN. PER FBC PL 901.2.1 | | | | 10. SHT. P5.1 WHAT VENTING SYSTEM FROM FBC PL CH. 9 ARE | | THE TOILETS IN THE BASEMENT BATHROOMS DESIGNED TO MEET | | IF IT IS A CIRCUIT VENT IT SHALL HAVE A VENT BETWEEN | | THE TWO MOST UP STREAM FIXTURES AND THE VENT HAS TO BE | | DRY . PER FBC PL 914.2 | | | | 11. PROVIDE A SITE PLAN THAT SHOWS THE CONNECTION OF | | THE SANITARY AND WATER TO THE CITY SYSTEMS. PER WPB | | AMEND TO FBC 107.2.1 | | | | 12. THE NEW SANITARY FROM THE UPPER FLOORS CAN NOT | | DISCHARGE TO THE SUMP PIT IN THE BASEMENT IT SHALL | | CONNECT TO THE GRAVITY SYSTEM CONNECTED TO THE CITY | | TAP. PER FBC PL 712.1 | | | | 13. I UNDERSTAND THAT THE SUMP PUMP WILL BE DONE BY | | OTHER BUT PLEASE PROVIDE THE CAPACITY OF THE SUMP PIT | | AND PUMP AND A BASIC PIPING DETAIL. | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2018-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-09 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-09 |
Time |
14:19 |
Sent To |
|
|
Notes |
2018-06-09 14:20:39 | GAF EVERGUARD TPO (AND LWIC @ 4TH FL MIN R10) ROOF | | PRODUCT APPROVAL IS TO BE SUBMITTED, ALONG WITH RAS117 | | CALCS IF REQUIRED, TO THE BUILDING DIVISION, REVIEWED | | AND ISSUED PRIOR TO INSTALLATION. CONFIRM COMPLIANCE | | WITH PRESSURES SHOWN ON SHEET S0.0.5 PRIOR TO | | SUBMITTAL. THE ASSEMBLY PROPOSED IS TO BE INDICATED. | | | | THE PRODUCT APPROVAL SHOULD BE SUBMITTED WITH THE ROOF | | SUB PERMIT APPLICATION. | | | | SHEET A1.5.1 |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2018-11-02 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-11-02 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-11-02 |
Time |
08:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-10-23 |
Time |
19:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-10-23 |
Time |
19:06 |
Sent To |
|
|
Notes |
2018-10-23 19:06:15 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | ALL SIGNATURES ARE OK, ALL TRADES WITH THE FOLLOWING | | EXCEPTION: | | E2.4 | | E2.5 | | | | NEW SHEETS SUBMITTED NEXT REVIEW CYCLE NEED | | VERIFICATION | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2018-08-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-22 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-22 |
Time |
06:51 |
Sent To |
|
|
Notes |
2018-08-22 06:51:41 | PLAN REVIEW IN PROGRESS | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. ELECTRICAL "SIGNATURE DOCUMENTS" WERE PROVIDED - | | SINCE THERE ARE ELECTRICAL COMMENTS, IT APPEARS THAT | | ELECTRICAL SHEETS NEED TO BE REPLACED. PLEASE ENSURE | | THAT ALL DOCUMENTS UPLOADED ARE DIGITALLY SIGNED AND | | SEALED. | | | | 2. THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING | | PAGES UPLOADED ON 7/19/18 ARE NOT DIGITALLY SIGNED AND | | SEALED. | | | | | | | 2018-08-16 15:00:34 | 8/16/18 E PAGES ARE DIGITALLY SIGNED AND SEALED IN FILE | | UNDER "SIGNATURES" FOLDER. LEM |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-05-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-21 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-21 |
Time |
14:18 |
Sent To |
|
|
Notes |
2018-05-21 14:35:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | ALL SIGNATURES ARE OK, ALL TRADES | | NEW SHEETS SUBMITTED 2ND REVIEW CYCLE NEED VERIFICATION | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
P |
Date |
2018-08-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-22 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-22 |
Time |
18:19 |
Sent To |
|
|
Notes |
2018-08-22 18:20:23 | SI AGREEMENT 18060833 | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-05 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-05 |
Time |
07:33 |
Sent To |
|
|
Notes |
2018-06-05 07:37:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 553.79(5) 2016, THIS IS A THRESHOLD BUILDING (FOUR | | STORIES). | | ***NO WORK TO RESUME ON THE STRUCTURE PERMIT UNTIL THE | | FOLLOWING ITEMS ARE ADDRESSED*** | | FAILURE TO IMMEDIATELY RESOLVE THESE ISSUES WILL RESULT | | IN REVOCATION OF THE STRUCTURE PERMIT 17120610 AS THIS | | PERMIT WAS ISSUED IN ERROR. | | | | 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT | | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO | | CONTRACTOR. | | | | 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL | | PROPOSED INSPECTORS. | | | | 3. THRESHOLD STATEMENT REQUIRED BY FS553.79(7)(D) - | | ENGINEER, REVISE THE STATEMENT SO IT IS CLEAR THAT IT | | IS FOR COMPLIANCE WITH THE STATUTORY REQUIREMENT. | | SUGGESTED: | | | | "PER FS553.79, TO THE BEST OF THE ENGINEER'S KNOWLEDGE, | | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY | | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN | | ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633." | | | | PER BUILDING OFFICIAL - ALL STRUCTURAL PAGES FOR THE | | STRUCTURE PERMIT 17120610 ARE TO BE REVISED TO INCLUDE | | THE STATUTORY STATEMENT. | | | | 4. THRESHOLD INSPECTION PLAN REQUIRED BY FS553.79(5)A); | | S0.03, PLEASE REVISE TITLE OF THIS PAGE SO IT IS CLEAR | | THAT THIS SERVES AS A THRESHOLD INSPECTION PLAN. | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-10-17 |
|
|
Cont ID |
|
Sent By |
elevesqu |
Date |
2018-10-17 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
elevesqu |
Date |
2018-10-17 |
Time |
15:26 |
Sent To |
|
|
Notes |
2018-10-17 15:27:09 | PROVISO: | | 1. THE REQUIRED DISTANCE BETWEEN A BICYCLE HITCH AND A | | WALL IS 24'. IT DOES NOT APPEAR THAT THE PROPOSED | | BICYCLE HITCH INTERIOR TO THE GATES WILL MEET THE RACK | | DIMENSION REQUIREMENTS. THE APPLICANT CAN PROPOSE NEW | | LOCATION (WILL HAVE TO BE MOVED, SEE PROVISO NO. 3). | | ADDITIONALLY, ONE HITCH CAN BE REMOVED IF NECESSARY, AS | | THE REQUIRED NUMBER OF INTERNAL BICYCLE RACKS IS SIX. | | | | 2. PLEASE MOVE THE BICYCLE RACK ON DATURA STREET TO THE | | BULBOUT TO PROVIDE ENOUGH ROOM ON THE SIDEWALK. | | | | 3. PROPOSED FENCES ALONG DATURA STREET SHALL BE LOCATED | | OUTSIDE THE 16' SETBACK LINE, SHALL BE A MAXIMUM HEIGHT | | OF 4', AND SHALL BE LOCATED BEHIND 5' LANDSCAPE BUFFER. | | PLEASE ADJUST LOCATION OF PEDESTRIAN FENCE AND GATE. | | | | 4. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS THE | | DRIVEWAY. | | | | 5. WITHIN 60 DAYS OF PERMIT ISSUANCE, THE APPLICANT | | SHALL RESUBMIT THE FOLLOWING INFORMATION/PLANS: | | A. THE UPDATED PLANNING PLAN TO MATCH THE SITE PLAN. | | B. AN UPDATED CIVIL PLAN REFLECTING THE SITE PLAN AND | | THAT SHOWS THE MAINTAINED SIDEWALK ELEVATION ALONG | | DRIVEWAY CURB CUTS. | | C. AN UPDATED SITE PLAN DETAIL SHEET SP 1.0.2. SHOWING | | THE CORRECT SIZED ROLLING GATE AND PEDESTRIAN GATE | | DETAIL. | | D. UPDATE THE BICYCLE HITCH LOCATIONS ON SITE PLAN SP | | 1.0.1. | | E. LABEL THE TYPICAL PARKING STALL DIMENSIONS ON SHEET | | SP 1.0.1. ALONG ALL ROWS OF PARKING, AS THEY HAVE | | DIFFERENT LENGTHS DEPENDING ON THE ROW. | | F. PLEASE SUBMIT A PHOTOMETRIC PLAN AND DETAIL PLAN | | THAT SHOWS PHOTOMETRICS OF THE PUBLIC SIDEWALKS, | | INTERNAL SIDEWALKS, BUILDING ENTRANCES, DUMPSTER AREA, | | ETC AND LIGHT FIXTURE DETAIL. PER SECTION 94-113 (B), | | BUILDINGS SHALL PROVIDE LIGHTING AT A MINIMUM OF 0.6 | | FOOTCANDLE AND MAXIMUM OF 1.0 FOOTCANDLE AS MEASURED AT | | THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE | | SIDEWALK. LIGHT FIXTURES AND POLES SHALL MEET THE CITY | | APPROVED STANDARD. | | G. RELOCATE THE PEDESTRIAN GATE BEHIND THE REQUIRED 16 | | FOOT SETBACK AND BEHIND THE LANDSCAPE BUFFER/HEDGE ON | | SHEET SP 1.0.1. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-08-20 |
|
|
Cont ID |
|
Sent By |
elevesqu |
Date |
2018-08-20 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
elevesqu |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2018-08-20 15:34:51 | PLANTING PLAN IS NOT UPDATED VERSION - NEEDS TO MATCH | | LATEST FROM SITE PLAN REVIEW. | | | | ADDITIONAL ADA SPACE ON PERMIT PLANS DOES NOT MATCH | | LATEST FROM SITE PLAN. PLEASE CALL TO DISCUSS | | MODIFICATION. | | | | GATE SHOWN ON SHEET SP1.0.2 DOES NOT MATCH GATE ON | | LATEST SUBMITTED SHEET 1.0.2. | | | | CONTACT LIZ LEVESQUE, URBAN DESIGN PLANNER OR | | [email protected] WITH ANY QUESTIONS |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
AA |
Date |
2018-06-07 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
elevesqu |
Date |
2018-06-07 |
Time |
16:44 |
Sent To |
|
|
Notes |
2018-06-07 16:44:53 | PENDING SITE PLAN APPROVAL. APPLICANT NEEDS TO RESUBMIT | | PLANS THAT MATCH SITE PLAN APPROVAL PLANS - SUBMITTED | | PLANS ARE OLD VERSIONS. | | | | CALL LIZ LEVESQUE WITH ANY QUESTIONS | | 561-822-1426 | | | | |
|
|
|