Plan Review Details - Permit 18040104
Plan Review Stops For Permit 18040104
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 15:47 Rev Time 0.00
Received By shill Date 2019-03-26 Time 15:47 Sent To  
Notes
2019-03-26 15:47:13AIPP SATISFIED PER EMAIL FROM S.WELTER DATED 2/11/19
 ROUTED EMAIL TO FILENET
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-31 Cont ID  
Sent By shill Date 2018-10-31 Time 16:22 Rev Time 0.00
Received By shill Date 2018-10-31 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 19:03 Rev Time 0.00
Received By shill Date 2018-10-19 Time 06:50 Sent To  
Notes
2018-10-23 19:03:39****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
  
 SEVERAL COMMENTS WERE NOT ADDRESSED. PRIOR TO CO OR
 TCO, SUBMIT A REVISION ADDRESSING THE FOLLOWING:
  
 1. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF
 COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS,
 IBC2000 OR IBC2003).
  
 2. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER
 TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING
 SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN
 IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS
 OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4),
 SO THIS EXCEPTION CANNOT BE UTILIZED.
  
 RESPONSE LETTER STATES TO SEE ATTACHED LETTER. THIS WAS
 AGREED TO BY BUILDING OFFICIAL WITH RATIONALE TO BE
 PRESENTED IN A SIGNED AND SEALED LETTER, PLEASE
 PROVIDE.
  
 3. ALS.1.1, REGARDING THE EXISTING STAIR: FBC EB 805.2
 EXCEPTION 2, THIS WAS COMPLIANT UNDER THE CODE UNDER
 WHICH IT WAS CONSTRUCTED. INSPECTOR WILL VERIFY THAT
 DEVIATION BETWEEN STAIR TREADS WILL ADJUSTED IF UNSAFE.
 PER ARCHITECT, THE GUARDRAIL AND HANDRAIL WILL BE
 CONSTRUCTED TO COMPLY WITH FBC B 2014.
  
 4. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE I
 OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED, SEE
 FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON
 COMBUSTIBLE BUILDING.
  
 RESPONSE LETTER STATES THAT SPEC SHEETS SHOWING
 COMPLIANCE ARE ATTACHED; UNABLE TO LOCATE.
  
 5. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO
 PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP.
  
 6. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE
 ACCORDINGLY:
 A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING
 COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT
 DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE
 EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING.
 B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA
 FOR THE OTHERS?
 C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR
 THE OTHERS?
 D. NO DOORS SHOWN.
 E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES
 OF ROOFS ON THIS BUILDING?
 F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS.
  
 7. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE
 SUBMITTED (LIST MAY NOT BE COMPREHENSIVE):
 NANAWALL
 STOREFRONT
 GLAZED DOORS
 OPAQUE DOORS
 OVERHEAD DOORS
  
 WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION
 PLAN.
  
 8. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
 ***************************
 INTERNAL USE ONLY:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 36706
  
 CONSTRUCTION TYPE: IIA
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 36706
 SQ FT FOOTPRINT: 36706
 SQ FT ROOF: 36706
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 18:23 Rev Time 0.00
Received By shill Date 2018-08-21 Time 18:25 Sent To  
Notes
2018-08-24 06:47:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-3. OK
  
 4. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF
 COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS,
 IBC2000 OR IBC2003).
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS ON
 ALS.1.4, UNABLE TO LOCATE SELECTION. IT APPEARS THAT
 PLAN WAS REVISED TO COMPLY, BUT PLEASE INDICATE
 SELECTION. REVIEW OF ACCESSIBLE MEANS OF EGRESS WILL BE
 DONE AFTER METHOD (IBC2000 OR IBC2003) IS INDICATED.
  
 5. OK
  
 6-7. ALS.0.1, BUILDING TYPE IIA WITH A NOTE THAT PER
 TABLE 601 FOOTNOTE D, 1 HR FIRE RESISTANCE RATING
 SUBSTITUTED BY FIRE SPRINKLER. THIS CAN ONLY BE TAKEN
 IF THE SPRINKLERS ARE NOT REQUIRED BY OTHER PROVISIONS
 OF THE CODE. A STORY INCREASE WAS TAKEN (FROM 3 TO 4),
 SO THIS EXCEPTION CANNOT BE UTILIZED.
  
 8. OK
  
 9. FBC 107.3.5.1.1(5), FBC EB 904, PROVIDE FIRE
 PROTECTION PLANS TO SHOW COMPLIANCE WITH STANDPIPES FBC
 B 905.3.1(1) AND NFPA13 SPRINKLERS FBC B 903.2.11.3.
  
 10. FBC 107.3.5.1.1(6), FBC EB 904, PROVIDE FIRE ALARM
 PLANS TO SHOW COMPLIANCE WITH FBC B 907.2.2.
  
 11. ALS.1.1, FBC 107, NOTE STATES THAT "2014 FBC
 SECTION 1004.4 FIXED SEATING" (CONFERENCE ROOM), IS
 THIS CORRECT? IF THIS IS NOT FIXED SEATING, REVISE NOTE
 AND REVISE OCCUPANT LOAD ACCORDINGLY.
  
 2ND REVIEW, THIS LANGUAGE IS STILL ON THIS PAGE. THIS
 WILL BE REDLINED IF NOT REMOVED. RESPONSE LETTER REFERS
 TO "REVISED ALS1.1" BUT A NEW SHEET WAS NOT PROVIDED.
  
 12. ALS.1.1, PLAN INDICATES SIGNAGE AT STAIR INDICATING
 NO ACCESS. IT DOES NOT APPEAR THAT A SIGN WILL BE
 ADEQUATE TO PREVENT USE OF THE STAIR. ADDITIONAL MEANS
 MAY BE REQUIRED. PRIOR TO C.O. ADDITIONAL INFORMATION
 WILL BE REQUIRED REGARDING HOW OCCUPANTS WILL BE
 PREVENTED FROM ACCESSING THE STAIR. UNLESS YOU WISH TO
 REVISE THE PLAN OR PROPOSE SOMETHING AT THIS TIME, THIS
 WILL BE A PROVISO ITEM.
  
 OR, SEE FBC EB 805.2 EXCEPTION 2.
  
 13. OK
  
 14. ALS.1.2, FBC A 202.4, IT APPEARS THAT A PORTION OF
 THE 2ND FLOOR LACKS VERTICAL ACCESSIBILITY. PROVIDE
 RATIONALE. PLEASE PROVIDE VIA EMAIL PRIOR TO
 RESUBMITTAL.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS WAS
 REVISED, BUT SHEET ALS1.2 WAS NOT REVISED (NOR WAS
 A1.2.1, ALSO OTHER 2ND FLOOR PAGES).
  
 15-16. OK
  
 17. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE
 I OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED,
 SEE FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON
 COMBUSTIBLE BUILDING.
  
 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED.
  
 18-21. OK
  
 22. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO
 PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP.
  
 23-24. OK
  
 25. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE
 ACCORDINGLY:
 A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING
 COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT
 DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE
 EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING.
 B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA
 FOR THE OTHERS?
 C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR
 THE OTHERS?
 D. NO DOORS SHOWN.
 E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES
 OF ROOFS ON THIS BUILDING?
 F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS.
  
 2ND REVIEW, NEW ENERGY CALCS WERE NOT PROVIDED.
  
 NEW COMMENT:
  
 26. ALS0.1, OCCUPANCY CALCULATIONS, CLOUD OBSTRUCTS THE
 OCCUPANT LOAD.
  
  
 27. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE
 SUBMITTED (LIST MAY NOT BE COMPREHENSIVE):
 NANAWALL
 STOREFRONT
 GLAZED DOORS
 OPAQUE DOORS
 OVERHEAD DOORS
  
 WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION
 PLAN.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
 ***************************
 INTERNAL USE ONLY:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 36706
  
 CONSTRUCTION TYPE: ???
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 36706
 SQ FT FOOTPRINT: 36706
 SQ FT ROOF: 36706
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 15:48 Rev Time 0.00
Received By shill Date 2018-06-09 Time 09:34 Sent To  
Notes
2018-06-09 15:51:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SP1.0.1 AREA FOR THE ROOF TERRACE OPEN TO AIR (4685
 SF) IS NOT CONSISTENT WITH THE ROOF PLAN WHICH SHOWS
 1845 SF, REVISE OR CLARIFY, FBC B 1004.
  
 2. SP1.0.1 PARKING IS SHOWN AS 48 SPACES AND 1 HANDICAP
 SPACE. FBC A TABLE 208.2, TWO ACCESSIBLE SPACES ARE
 REQUIRED.
  
 3. SP1.0.1 FBC B TABLE 705.8, REVISE PLAN TO SHOW
 COMPLIANCE. DISTANCE TO CENTER OF ROAD IS NOT CLEAR
 (ALLEY).
  
 4. FBC A 207, REVISE PLAN TO INDICATE WHICH METHOD OF
 COMPLIANCE IS ELECTED (ACCESSIBLE MEANS OF EGRESS,
 IBC2000 OR IBC2003).
  
 5. ALS.0.1, CHANGE OF OCCUPANCY IS NOTED FOR THE 4TH
 FLOOR. THE AREAS WHICH WERE ENCLOSED BUT NOT
 CONDITIONED ARE ALSO CHANGE OF OCCUPANCY. THE
 CONVERSION OF EXTERIOR SPACE UNDER ROOF TO INTERIOR
 SPACE IS AN ADDITION. REVISE CODE SUMMARY TO CLARIFY
 SCOPE OF WORK.
  
 6. ALS.0.1, COMPLIANCE WITH FBC B TABLE 503 NOT CLEAR.
 SHEET ALS 0.1 STATES THAT THIS IS NON SEPARATED MIXED
 USE "BUSINESS: 9000 SF/STORY X 3 = 27,000 SF/FLOOR".
  
 SEE FBC B 508.3.2, COMPLIANCE WITH THE MOST STRINGENT
 OCCUPANCY IS TO BE SHOWN; IN THIS CASE ASSEMBLY. 9000
 SF IS THE LIMITATION FOR BUSINESS, TYPE V CONSTRUCTION
 WHICH WITH SPRINKLER INCREASE IS LIMITED TO 3 STORIES.
 REVISE PLAN TO INCLUDE BUILDING TYPE AND SHOW
 COMPLIANCE WITH FBC B TABLE 503.
  
 7. ALS.0.1, FBC 107, REVISE PLAN TO INCLUDE BUILDING
 TYPE, OR ADVISE WHERE THIS INFORMATION CAN BE FOUND.
  
 8. ALS.0.1, "SMOKE EVACUATION REQUIREMENT", NFPA101 IS
 REFERENCED. REVISE TO INCLUDE FBC. PROVIDE A SECTION SO
 EXCEPTION TO SMOKE CONTROL IS CLEAR, FBC B 404.5.
  
 9. FBC 107.3.5.1.1(5), FBC EB 904, PROVIDE FIRE
 PROTECTION PLANS TO SHOW COMPLIANCE WITH STANDPIPES FBC
 B 905.3.1(1) AND NFPA13 SPRINKLERS FBC B 903.2.11.3.
  
 10. FBC 107.3.5.1.1(6), FBC EB 904, PROVIDE FIRE ALARM
 PLANS TO SHOW COMPLIANCE WITH FBC B 907.2.2.
  
 11. ALS.1.1, FBC 107, NOTE STATES THAT "2014 FBC
 SECTION 1004.4 FIXED SEATING" (CONFERENCE ROOM), IS
 THIS CORRECT? IF THIS IS NOT FIXED SEATING, REVISE NOTE
 AND REVISE OCCUPANT LOAD ACCORDINGLY.
  
 12. ALS.1.1, PLAN INDICATES SIGNAGE AT STAIR INDICATING
 NO ACCESS. IT DOES NOT APPEAR THAT A SIGN WILL BE
 ADEQUATE TO PREVENT USE OF THE STAIR. ADDITIONAL MEANS
 MAY BE REQUIRED. PRIOR TO C.O. ADDITIONAL INFORMATION
 WILL BE REQUIRED REGARDING HOW OCCUPANTS WILL BE
 PREVENTED FROM ACCESSING THE STAIR. UNLESS YOU WISH TO
 REVISE THE PLAN OR PROPOSE SOMETHING AT THIS TIME, THIS
 WILL BE A PROVISO ITEM.
  
 OR, SEE FBC EB 805.2 EXCEPTION 2.
  
 13. COVER SHEET, FBC B 501.2, ADDRESS IDENTIFICATION,
 IS THE ADDRESS SHOWN CONCEPTUAL, OR INTENDED TO COMPLY
 WITH THIS SECTION?
  
 14. ALS.1.2, FBC A 202.4, IT APPEARS THAT A PORTION OF
 THE 2ND FLOOR LACKS VERTICAL ACCESSIBILITY. PROVIDE
 RATIONALE. PLEASE PROVIDE VIA EMAIL PRIOR TO
 RESUBMITTAL.
  
 15. AD.1.2.3, FBC 107, CLARIFY EXISTING OCCUPANCY OF
 THE ROOFTOP ROOM.
  
 16. ALS1.4, FBC B 1021.1, IT APPEARS THAT THE ROOF
 TERRACE IS REQUIRED TO HAVE TWO MEANS OF EGRESS. IS THE
 DOTTED LINE A DOOR IN THE NANAWALL? DOES IT HAVE
 HARDWARE? NOTE STATES "HOLD OPEN ON STATIONARY DOOR".
 IT'S NOT CLEAR HOW THIS COMPLIES WITH FBC B 1008.1.10,
 PANIC BARS.
  
 17. A0.0.2, A WOOD CEILING IS SHOWN. IF THIS IS A TYPE
 I OR TYPE II BUILDING, THIS APPEARS TO BE PROHIBITED,
 SEE FBC B 603 FOR COMBUSTIBLES PERMITTED IN A NON
 COMBUSTIBLE BUILDING.
  
 18. PLUMBING ACCESSIBILITY COMMENTS ARE APPLICABLE FOR
 BUILDING REVIEW.
  
 19. SEE THRESHOLD REVIEW. ALL STRUCTURAL SHEETS ARE TO
 INCLUDE THE STATEMENT REQUIRED BY FLORIDA STATUTE 553.
 A THRESHOLD INSPECTION PLAN IS REQUIRED AND THE PLAN IS
 TO BE NOTED AS SUCH. PLANS FOR THE STRUCTURE PERMIT AND
 FOR THIS INTERIOR PERMIT ARE TO BE REVISED.
  
 20. A.8.0.1, FBC B TABLE 716.5, THE DOORS IN THE TWO
 HOUR STAIR EXIT ENCLOSURES ARE REQUIRED TO BE 90
 MINUTE. FOR EXAMPLE, DOOR 210 SHOWS NO RATING, 216
 PROPOSES 45 MINUTE; REVISE AND CHECK ALL.
  
 21. A.8.0.1, NO PANIC HARDWARE PROPOSED ON ROOF
 TERRACE; ALL DOORS SERVING ASSEMBLY OCCUPANCY AND AN
 OCCUPANT LOAD 50 AND OVER ARE TO HAVE PANIC BARS FBC B
 1008.1.10.
  
 22. SEOR TO REVIEW SOILS; INCORPORATE REFERENCE INTO
 PLAN OR PROVIDE A SHOP DRAWING REVIEW STAMP.
  
 23. THE STRUCTURE PERMIT WAS ISSUED TO QUEST
 CONTRACTING. THIS APPLICATION WAS SUBMITTED BY DPR
 CONSTRUCTION. WILL THE CONTRACTOR BE CHANGED TO QUEST?
 IF NOT, PRIOR TO ISSUANCE OF THIS PERMIT A LETTER
 SIGNED BY THE QUALIFIERS OF THE TWO COMPANIES STATING
 THAT THEY WILL WORK TOGETHER TO OBTAIN CODE COMPLIANCE,
 FBC 107. THIS IS REQUIRED WHEN THERE IS MORE THAN ONE
 CONTRACTOR ON A PROJECT AND RESPONSIBILITIES MAY
 OVERLAP.
  
 24. FBC B 3306, IT APPEARS THAT A BARRIER AND OVERHEAD
 PROTECTION ARE REQUIRED. ACQUIRE PERMITS. IT APPEARS
 THAT WORK HAS ALREADY BEEN DONE WITHOUT THIS PROTECTION
 IN PLACE.
  
 25. ENERGY CALCS, CLARIFY THE FOLLOWING OR REVISE
 ACCORDINGLY:
 A. EXTERNAL LIGHTING IS NONE; HOW WILL THIS BUILDING
 COMPLY WITH MEANS OF EGRESS ILLUMINATION IN THE EXIT
 DISCHARGE? SIGNAGE FOR THE BUILDING? LIGHTS ON THE
 EXTERIOR? SP1.0.1 SHOWS EXTERIOR LIGHTING.
 B. WALLS SHOWN FOR 2ND FLOOR ONLY, WHERE IS THE DATA
 FOR THE OTHERS?
 C. WINDOWS SHOWN ON 2ND FLOOR ONLY, WHERE IS DATA FOR
 THE OTHERS?
 D. NO DOORS SHOWN.
 E. NO DATA FOR ROOF; AREN'T THERE TWO DIFFERENT TYPES
 OF ROOFS ON THIS BUILDING?
 F. FLOORS APPEAR TO SHOW SLAB ON GRADE FOR ALL LEVELS.
  
 26. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S0.0.5
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES. PRODUCTS TO BE
 SUBMITTED (LIST MAY NOT BE COMPREHENSIVE):
 NANAWALL
 STOREFRONT
 GLAZED DOORS
 OPAQUE DOORS
 OVERHEAD DOORS
  
 WHEN SUBMITTING PRODUCT APPROVALS, PROVIDE A LOCATION
 PLAN.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
 ***************************
 INTERNAL USE ONLY:
  
 USC-404 TYPE 437 - ALT: NON-RES, NON-HSKPG
 SQUARE FEET - 36706
  
 CONSTRUCTION TYPE: ???
 UNITS:
 FLOORS: 4
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 36706
 SQ FT FOOTPRINT: 36706
 SQ FT ROOF: 36706
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: OFFICE
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED B
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-02 Cont ID  
Sent By jpearson Date 2018-11-02 Time 08:10 Rev Time 0.00
Received By jpearson Date 2018-11-02 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-16 Cont ID  
Sent By jpearson Date 2018-10-16 Time 10:39 Rev Time 0.00
Received By jpearson Date 2018-10-16 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-08-16 Time   Rev Time 0.00
Received By jpearson Date 2018-08-16 Time 15:57 Sent To  
Notes
2018-08-16 15:45:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY
 SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS
 THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC
 107.2.1 (NOT PROVIDED. REQUIRED INFORMATION FOR RISER
 DIAGRAM. NEC 215.5)
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED, DEFERRED SUBMITTAL
 ACCEPTABLE.)
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
  
 NEW COMMENT:
  
 11. DOOR TO ELECTRICAL ROOM SHALL OPEN IN THE DIRECTION
 OF EGRESS AND BE EQUIPPED WITH LISTED PANIC HARDWARE.
 PROVIDE CORRECTION. NEC 110.26(C)(3)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By jpearson Date 2018-05-21 Time 09:43 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 14:13 Sent To  
Notes
2018-05-21 09:43:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE
 TENANTS. THIS WIREWAY SHOULD BE TIED INTO THE GROUNDING
 ELECTRODE SYSTEM. PROVIDE CORRECTION. NEC 250.50,
 250.58
 2. ELECTRICAL RISER NOTE 7 SHOWS A WIREWAY FOR FUTURE
 TENANTS. THE WIREWAY IS SHOWN AS BEING INSTALLED, WHILE
 THE METERS AND DISCONNECTS ARE SHOWN AS FUTURE. THIS
 WIREWAY CANNOT BE INSTALLED WITH ENERGIZED CONDUCTORS
 AND NO OVERCURRENT PROTECTION. PROVIDE CORRECTION. NEC
 230.70
 3. PROVIDE LABELING OF MAINS PER NEC 230.2(E)
 4. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET
 ALS.0.1 AND E0.1 IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 5. SHEET ALS.0.1 INDICATES THAT THE BUILDING IS FULLY
 SPRINKLERED. IS THERE A FIRE PUMP AND CONTROLLER, OR IS
 THIS FED FROM CITY WATER? PLEASE CLARIFY. WPB FBC
 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. RESTROOMS ON 3RD FLOOR DO NOT SHOW THE AUTOMATIC
 LIGHTING CONTROL REQUIRED. PROVIDE CORRECTION. FBC EC
 C405.2
 9. SHEET E2.5, THE UNISEX RESTROOM DOES NOT SHOW THE
 AUTOMATIC LIGHTING CONTROL REQUIRED. PROVIDE
 CORRECTION. FBC EC C405.2
 10. PROVIDE NOTE REQUIRING GFCI DEVICE FOR WATER
 COOLERS TO BE READILY ACCESSIBLE. NEC 422.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-11-01 Cont ID  
Sent By scaldero Date 2018-11-01 Time 10:11 Rev Time 0.00
Received By scaldero Date 2018-11-01 Time 10:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-27 Cont ID  
Sent By scaldero Date 2018-09-27 Time 10:15 Rev Time 0.00
Received By scaldero Date 2018-09-26 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-07-24 Cont ID  
Sent By scaldero Date 2018-07-24 Time 14:01 Rev Time 0.00
Received By scaldero Date 2018-07-24 Time 12:47 Sent To  
Notes
2018-07-24 14:01:30PERMIT # 18040104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW COMMENTS:
  
 1) BECAUSE THIS BUILDING DOES NOT HAVE AN EXISTING FIRE
 SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM: ENGINEERED
 FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION DOCUMENTS
 ARE REQUIRED FOR A GENERAL/MASTERL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 2) PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By scaldero Date 2018-05-02 Time 11:46 Rev Time 0.00
Received By scaldero Date 2018-05-02 Time 10:07 Sent To  
Notes
2018-05-02 11:46:48PERMIT # 18040104
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET ALS 1.0: THE TRAVEL DISTANCE TO THE STAIRS BY
 THE PRODUCTION ROOM (003) INDICATES 270 FEET. PER NFPA
 101, CHAPTER 39, TRAVEL DISTANCE MAY NOT EXCEED 200
 FEET IF THE BUILDING IS NOT PROTECTED BY A FIRE
 SPRINKLER SYSTEM. PLEASE PROVIDE FOR CODE COMPLIANCE OR
 JUSTIFICATION.
  
 39.2.6.2
 TRAVEL DISTANCE TO AN EXIT SHALL NOT EXCEED 200 FT (61
 M) FROM ANY POINT IN A BUILDING, UNLESS OTHERWISE
 PERMITTED BY 39.2.6.3.
  
 39.2.6.3
 TRAVEL DISTANCE SHALL NOT EXCEED 300 FT (91 M) IN
 BUSINESS OCCUPANCIES PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
  
 2) SHEET ALS 1.1: INDICATES AN EGRESS TRAVEL DISTANCE
 OF 202 FEET. PLEASE PROVIDE FOR COMPLIANCE OF CODE, AS
 NOTED ABOVE, OR JUSTIFICATION.
  
 3) SHEET ALS 1.4: PLEASE PROVIDE JUSTIFICATION THAT
 SHOWS COMPLIANCE WITH ALL APPLICABLE ASPECTS OF NFPA
 101: 7.2.12 - AREA OF REFUGE; INCLUDING ALL DIMENSIONS
 APPLICABLE TO THE STAIRWELL (MIN CLEAR WIDTH OF 48
 INCHES IS REQUIRED - - STAIR A HAS A CLEAR WIDTH OF
 ONLY 44 INCHES), LOCATION OF REQUIRED SIGNAGE, TWO-WAY
 COMMUNICATION (IF REQUIRED), ETC.
  
 4) PER NFPA 101: 39.3.4 - A FIRE ALARM SYSTEM IS
 REQUIRED FOR THIS OCCUPANCY.
  
 5) DOES THIS BUILDING HAVE A FULL OR PARTIAL FIRE
 SPRINKLER SYSTEM? OR IS A FIRE SPINKLER SYSTEM GOING TO
 BE INSTALLED?
  
 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 7) COULD NOT FIND DETAILS FOR STAIR A. NOT INCLUDED IN
 SHEETS A6-0-1 THROUGH A6-0-5.
  
 8) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 DURING PLAN RESUBMISSION.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-11-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-31 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 19:05 Rev Time 0.00
Received By shill Date 2018-09-25 Time 13:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 18:23 Rev Time 0.00
Received By shill Date 2018-07-19 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 15:51 Rev Time 0.00
Received By shill Date 2018-04-17 Time 15:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By shill Date 2018-08-28 Time 12:43 Rev Time 0.00
Received By shill Date 2018-08-28 Time 12:43 Sent To  
Notes
2018-08-28 12:43:37REVIEWED UNDER STRUCTURE PERMIT 17120610
  
 PALM BEACH COUNTY REVIEWED FOR IMPACT FEES.
 NO FEES DUE.
 4/5/18 18 11477

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 19:33 Rev Time 0.00
Received By shill Date 2018-05-27 Time 19:33 Sent To  
Notes
2018-05-27 19:35:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 PROVIDE PRINTED FLOOR PLANS INCLUDING SQUARE FOOT
 AREAS. THE PLANS ARE TO BE STAMPED AND THE RECEIPT
 SHOWING THAT FEES DUE WERE PAID IS TO BE PROVIDED.
 561-233-5025 FOR MORE INFORMATION
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-11-01 Cont ID  
Sent By ccole Date 2018-11-01 Time 09:07 Rev Time 0.00
Received By ccole Date 2018-11-01 Time 07:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-10-23 Cont ID  
Sent By ccole Date 2018-10-23 Time 09:33 Rev Time 0.00
Received By ccole Date 2018-10-23 Time 09:33 Sent To  
Notes
2018-10-23 09:56:203RD REVIEW- FBC-2017 MECHANICAL
 PERMIT #18040104
 10/23/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: AS PREVIOUSLY NOTED THERE APPEARS TO BE
 AN INADEQUATE AMOUNT OF O/A PROVIDED TO THE BASEMENT
 ROOMS AND SPACES FOR OCCUPANTS, AND FOR MAKEUP AIR FOR
 THE BATHROOM EXHAUST. THE CURRENT PLAN SHOWS ONLY 135
 CFMS PROVIDED TO LOUNGE 003 FROM THE OARTU WHICH IS NOT
 IN COMPLIANCE WITH TABLE 403.3.1.1 AND SECTION 501.4.
 IN ADDITION PLEASE NOTE THE
  
 FOLLOWING: A) THE OARTU SCHEDULE ON SHEET M7.1 HAS A
 CAPACITY OF 2730 CFMS, AND THE AIR BALANCE SCHEDULE ON
 M7.2 INDICATES 400 CFMS TO BE PROVIDED TO THE BASEMENT
 AND 855 CFMS TO THE FIRST FLOOR. THIS DATA APPEARS TO
 INDICATE A MISTAKE IN SYSTEM SELECTION. B) THE RTU #2
 SCHEDULE ON M7.1 INDICATES THE UNIT HAS AN O/A CAPACITY
 OF 1387 CFMS, HOWEVER THE AIR BALANCE
  
 SCHEDULE INDICATES A REQUIREMENT OF 2705 CFMS. AGAIN AN
 APPARENT MISTAKE IN SYSTEM SELECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By ccole Date 2018-08-21 Time 07:42 Rev Time 0.00
Received By ccole Date 2018-08-15 Time 07:42 Sent To  
Notes
2018-08-15 07:50:592ND REVIEW- PART 2, FBC-2017 MECHANICAL
 PERMIT #18040104
 8/21/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE FOLLOWING COMMENTS ARE BASED ON THE 1ST REVIEW
 COMMENTS WHICH STILL EXIST EITHER PARTIALLY OR
 COMPLETELY .
  
 1) THE REQUESTED ELECTRONICALLY SIGNED AND SEALED
 ENERGY AND AC CALCULATIONS WERE NOT PROVIDED.
  
 2) THE ENERGY COMPLIANCE FORM IS INDICATING THE VRF
 UNITS ARE "WATER SOURCE" BUT THAT DOES NOT MATCH WITH
 THE EQUIPMENT SCHEDULES PROVIDED ON THE PLANS WHICH
 INDICATE AIR SOURCE UNITS- SEE TABLE C403.2.3(11) FBC
 EC.
  
 3) THE ENERGY COMPLIANCE FORM DOES NOT LIST ANY DATA
 FOR RTU-2 (528.2 MBH) AND THE OARTU (107.1 MBH) -
 PLEASE PROVIDE THE DATA.
  
 4) M7.1 & M7.2: THE ENERGY COMPLIANCE FORM LISTS RTU-1
 AS A 93.3 MBH UNIT, HOWEVER THERE IS NO RTU-1 IN THE
 SCHEDULES OR WITH THAT COOLING CAPACITY.
  
 5) AS PREVIOUSLY NOTED IN THE FIRST REVIEW, THERE IS NO
 COMPLIANCE DATA LISTED IN THE ENERGY COMPLIANCE FORM
 FOR AHU'S 5, 6, 7, & 8.
  
 6) REFER TO SHEETS M2.5, M6.1 AND M7.1: PLEASE CORRECT
 THE LABELING OF THE LARGE 528.2 MBH RTU WHICH IS
 INDICATED AS RTU-2 ON THE PLANS, AND RTU-1 IN THE
 SCHEDULE.
  
 7) SHEETS ALS.01 AND M0.1 HAVE NOT BEEN UPDATED TO LIST
 THE CORRECT CODE EDITIONS AND THE CORRECT NOA # FOR THE
 ROOF STAND.
  
 8) SHEET M6.1: PLEASE PROVIDE EXHAUST VENTILATION
 CALCULATIONS AND AIR BALANCE CALCULATIONS ON THE PLAN.
  
 9) SHEET M2.1: PLEASE CLARIFY HOW O/A IS BEING PROVIDED
 TO THE LOUNGE ROOM THAT IS CLOSE TO THE STAIRCASE, AND
 HOW MAKEUP AIR IS BEING PROVIDED FOR THE TOILET ROOM
 EXHAUST SYSTEM.
  
 10) SHEET M2.2: REFER TO SECTION 502.13 FBC M AND
 CLARIFY HOW THE EXHAUST VENTILATION SYSTEM IN THE
 GARAGE WILL OPERATE- CONTINOUSLY OR IN ACCORDANCE WITH
 SECTION 404. PLEASE PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE GARAGE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
 2ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18040104
 8/15/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR ELECTRONICALLY SIGNED AND SEALED
 ENERGY AND AC CALCULATIONS- SEE COMMENT #1 FROM THE 1ST
 REVIEW.
  
 2) ACCORDING TO THE RESPONSE NARRATIVE TO THE 1ST
 REVIEW COMMENTS, SHEETS M0.1, M2.1, M2.5, M6.1, AND
 M7.1 HAVE BEEN REVISED, HOWEVER THOSE SHEETS HAVE NOT
 BEEN UPDATED, AND M6.1 HAS BEEN REPLACED WITH E.01. THE
 REVIEW IS STOPPED AT THIS POINT UNITL REVISED SHEETS
 ARE UPLOADED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By ccole Date 2018-05-22 Time 11:21 Rev Time 0.00
Received By ccole Date 2018-05-22 Time 07:26 Sent To  
Notes
2018-05-22 12:04:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040104
 5/22/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC AND ENERGY CALCULATIONS ARE NOT
 ELECTRONICALLY SIGNED AND SEALED. PLEASE REFER TO RULE
 61G15-23.005: ENGINEERING PLANS, SPECIFICATIONS.
 REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED
 AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025 FS, AND RULE 61G15-23.001 FAC MAY BE SIGNED
 ELECTRONICALLY AS PROVIDED HEREIN BY THE PROFESSIONAL
 ENGINEER IN RESPONSUIBLE CHARGE.
  
 2) ENERGYGAUGE FORM: A) COMPLIANCE DATA FOR AHU'S 5, 6,
 7, & 8 HAS NOT BEEN PROVIDED. B) RTU-1 LISTED AT 93,300
 BTUH IN THE ENERGY COMPLIANCE DATA IS NOT SHOWN IN THE
 AC EQUIPMENT SCHEDULES. C) THE 52820 BTUH COOLING
 CAPACITY FOR VAV-3 SHOWN IN THE CALCS DOES NOT MATCH
 THE CAPACITY SHOWN IN THE EQUIPMENT SPECIFICATIONS ON
 SHEET M7.1.
  
 3) SHEETS ALS.01 & M0.1: THE PLANS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODES SIXTH
 EDITION 2017. PLEASE UPDATE THE CODE DATA, AND THE NOA
 FOR THE ROOF STAND. NOA #13-1017.09 HAS BEEN SUPERSEDED
 BY NOA #15-0902.05.
  
 4) M2.5 & M7.1: RTU-1 IS MISLABLED AS RTU-2 ON THE ROOF
 PLAN. SHOW THE LOCATION OF THE 7.5 TON RTU FOR THE
 BUSINESS LOUNGE.
  
 5) PROVIDE COMPLETE VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES IN ACCORDANCE WITH TABLE 403.3.1.1 FBC
 MC. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR, AND EXHAUST AIR WHERE
 REQUIRED.
  
 6) M0.1 & M2.1: DUCT SMOKE DETECTORS ARE REQUIRED FOR
 THE MMU SUPPLY SYSTEMS PER SECTION 606.2.2 FBC MC.
 PLEASE SEE EXCEPTION 2 WHICH ALLOWS SMOKE DETECTORS TO
 BE PLACED IN THE RETURN AIR PLENUMS.
  
 7) M2.1: THE PLAN APPEARS TO SHOW ONLY 135 CFMS OF
 OUTSIDE AIR FOR ALL THE OCCUPIED SPACES ON THE FLOOR.
 SEE COMMENT #4 ABOVE AND PROVIDE CALCULATIONS.
  
 8) M2.1: PROVIDE A MEANS OF RETURN AIR FOR THE SYSTEM.
  
 9) M2.1:USING THE CORRIDOR FOR MAKEUP AIR FOR THE
 TOILET ROOM EXHAUST SYSTEMS REQUIRES THE CORRIDOR TO BE
 DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE GREATER
 THAN THE RATE OF MAKEUP AIR TAKEN FROM THE CORRIDOR-
 SECTION 601.2 (1) FBC MC.
  
 10) M2.2: SHOW HOW IS AIR BEING RETURNED FOM THE
 CONFERENCE AND OFFICE ROOMS- SECTION 601.6 FBC MC.
  
 11) M2.5: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 DUCT OF RTU-1 (RTU-2 ON THE PLAN- SEE COMMENT #4).
  
 12) P2.5: PROVIDE A DETAIL SHOWING HOW THE CONDENSATE
 PIPING WILL BE SUPPORTED ON THE ROOF- TYPE AND SPACING
 OF SUPPORTS
  
 13) PROVIDE TWO COPIES OF NOA #15-0902.05. ACKNOWLEDGED
 THAT COMPLETE STRUCTURAL ENGINEERING FOR INSTALLATION
 OF THE RTU'S WILL BE A DEFERRED SUBMITTAL PER NOTE ON
 M6.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-22 Cont ID  
Sent By gjohnson Date 2018-08-22 Time 07:25 Rev Time 0.00
Received By gjohnson Date 2018-08-21 Time 15:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-01 Cont ID  
Sent By gjohnson Date 2018-06-01 Time 07:42 Rev Time 0.00
Received By gjohnson Date 2018-05-24 Time 17:48 Sent To  
Notes
2018-05-31 17:44:011ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. ALS-1-2 THE PLUMBING FIXTURE COUNT STATES A
 OCCUPANT LOAD OF 90 THE 2ND FLOOR OCCUPANT LOAD IS
 LISTED AT 119 PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. A9-5-1 THE SHOWER IN THE WOMENS APPEARS TO BE A
 ALTERNATE ROLL-IN THE DEPTH OF THE SHOWER IS SHOWN AS
 371/4" THE CODE CALLS OUT FOR A HARD DIMENSION OF 36"
 SHALL COMPLY WITH FBC PL 608.2.3
  
 3. SHT. A9-5-1 PLEASE SHOW DIMENSIONS OF THE SHOWER IN
 THE MENS BATHROOM. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT A9-5-2 SHT. A9-5-2 THE TOILET IN THE BATHROOMS #
 203,205,208 SHALL COMPLY WITH FBC PL 604.2
  
 5. SHT. A9-5-9 THE GRAB BARS FOR THE TOILET IN
 BATHROOMS # 203,205, 208 SHALL COMPLY WITH FBC PL
 604.5.1 AND 604.5.2 , 609.4
  
 6. SHT. A9-5-9 THE SHOWERS IN BATHROOMS # 203,205,208
 SHALL COMPLY WITH FBC PL 608 PLEASE INDICATE ON THE
 PLAN WHICH TYPE OF SHOWER COMPARTMENT THEY ARE DESIGNED
 TO TO MEET AND SHOW ALL DIMENSIONS. PER WPB AMEND TO
 FBC 107.2.1
  
 7. SHT A9-5-9 SHOW COMPLIANCE WITH FBC PL 608.3 THE
 GRAB BARS IN-THE SOWERS FOR BATHROOMS # 203,205,208
  
 8. SHT. P5.1 THE SHOWER IN BATHROOM 203, 208 MEN'S
 BATHROOM IN BASEMENT ARE SHOWING A HORIZONTAL DRY VENT
 AND ARE NOT CODE COMPLIANT ALL DRY VENTS SHALL COMPLY
 WITH FBC PL 905.3, 905.4
  
 9. SHT. P5.1 THE TOILET 203 IS NOT VENTED PROPERLY IT
 SHALL BE VENTED BEFORE CONNECTING TO THE BUILDING
 DRAIN. PER FBC PL 901.2.1
  
 10. SHT. P5.1 WHAT VENTING SYSTEM FROM FBC PL CH. 9 ARE
 THE TOILETS IN THE BASEMENT BATHROOMS DESIGNED TO MEET
 IF IT IS A CIRCUIT VENT IT SHALL HAVE A VENT BETWEEN
 THE TWO MOST UP STREAM FIXTURES AND THE VENT HAS TO BE
 DRY . PER FBC PL 914.2
  
 11. PROVIDE A SITE PLAN THAT SHOWS THE CONNECTION OF
 THE SANITARY AND WATER TO THE CITY SYSTEMS. PER WPB
 AMEND TO FBC 107.2.1
  
 12. THE NEW SANITARY FROM THE UPPER FLOORS CAN NOT
 DISCHARGE TO THE SUMP PIT IN THE BASEMENT IT SHALL
 CONNECT TO THE GRAVITY SYSTEM CONNECTED TO THE CITY
 TAP. PER FBC PL 712.1
  
 13. I UNDERSTAND THAT THE SUMP PUMP WILL BE DONE BY
 OTHER BUT PLEASE PROVIDE THE CAPACITY OF THE SUMP PIT
 AND PUMP AND A BASIC PIPING DETAIL.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 14:19 Rev Time 0.00
Received By shill Date 2018-06-09 Time 14:19 Sent To  
Notes
2018-06-09 14:20:39GAF EVERGUARD TPO (AND LWIC @ 4TH FL MIN R10) ROOF
 PRODUCT APPROVAL IS TO BE SUBMITTED, ALONG WITH RAS117
 CALCS IF REQUIRED, TO THE BUILDING DIVISION, REVIEWED
 AND ISSUED PRIOR TO INSTALLATION. CONFIRM COMPLIANCE
 WITH PRESSURES SHOWN ON SHEET S0.0.5 PRIOR TO
 SUBMITTAL. THE ASSEMBLY PROPOSED IS TO BE INDICATED.
  
 THE PRODUCT APPROVAL SHOULD BE SUBMITTED WITH THE ROOF
 SUB PERMIT APPLICATION.
  
 SHEET A1.5.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-11-02 Cont ID  
Sent By jpearson Date 2018-11-02 Time 08:10 Rev Time 0.00
Received By jpearson Date 2018-11-02 Time 08:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 19:06 Rev Time 0.00
Received By shill Date 2018-10-23 Time 19:06 Sent To  
Notes
2018-10-23 19:06:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ALL SIGNATURES ARE OK, ALL TRADES WITH THE FOLLOWING
 EXCEPTION:
 E2.4
 E2.5
  
 NEW SHEETS SUBMITTED NEXT REVIEW CYCLE NEED
 VERIFICATION
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 18:19 Rev Time 0.00
Received By shill Date 2018-08-22 Time 06:51 Sent To  
Notes
2018-08-22 06:51:41PLAN REVIEW IN PROGRESS
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ELECTRICAL "SIGNATURE DOCUMENTS" WERE PROVIDED -
 SINCE THERE ARE ELECTRICAL COMMENTS, IT APPEARS THAT
 ELECTRICAL SHEETS NEED TO BE REPLACED. PLEASE ENSURE
 THAT ALL DOCUMENTS UPLOADED ARE DIGITALLY SIGNED AND
 SEALED.
  
 2. THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING
 PAGES UPLOADED ON 7/19/18 ARE NOT DIGITALLY SIGNED AND
 SEALED.
  
  
  
2018-08-16 15:00:348/16/18 E PAGES ARE DIGITALLY SIGNED AND SEALED IN FILE
 UNDER "SIGNATURES" FOLDER. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By shill Date 2018-05-21 Time 14:18 Rev Time 0.00
Received By shill Date 2018-05-21 Time 14:18 Sent To  
Notes
2018-05-21 14:35:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ALL SIGNATURES ARE OK, ALL TRADES
 NEW SHEETS SUBMITTED 2ND REVIEW CYCLE NEED VERIFICATION
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-08-22 Cont ID  
Sent By shill Date 2018-08-22 Time 18:19 Rev Time 0.00
Received By shill Date 2018-08-22 Time 18:19 Sent To  
Notes
2018-08-22 18:20:23SI AGREEMENT 18060833
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By shill Date 2018-06-05 Time 07:33 Rev Time 0.00
Received By shill Date 2018-06-05 Time 07:33 Sent To  
Notes
2018-06-05 07:37:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 553.79(5) 2016, THIS IS A THRESHOLD BUILDING (FOUR
 STORIES).
 ***NO WORK TO RESUME ON THE STRUCTURE PERMIT UNTIL THE
 FOLLOWING ITEMS ARE ADDRESSED***
 FAILURE TO IMMEDIATELY RESOLVE THESE ISSUES WILL RESULT
 IN REVOCATION OF THE STRUCTURE PERMIT 17120610 AS THIS
 PERMIT WAS ISSUED IN ERROR.
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. THRESHOLD STATEMENT REQUIRED BY FS553.79(7)(D) -
 ENGINEER, REVISE THE STATEMENT SO IT IS CLEAR THAT IT
 IS FOR COMPLIANCE WITH THE STATUTORY REQUIREMENT.
 SUGGESTED:
  
 "PER FS553.79, TO THE BEST OF THE ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRESAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS CHAPTER AND CHAPTER 633."
  
 PER BUILDING OFFICIAL - ALL STRUCTURAL PAGES FOR THE
 STRUCTURE PERMIT 17120610 ARE TO BE REVISED TO INCLUDE
 THE STATUTORY STATEMENT.
  
 4. THRESHOLD INSPECTION PLAN REQUIRED BY FS553.79(5)A);
 S0.03, PLEASE REVISE TITLE OF THIS PAGE SO IT IS CLEAR
 THAT THIS SERVES AS A THRESHOLD INSPECTION PLAN.
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-17 Cont ID  
Sent By elevesqu Date 2018-10-17 Time 15:26 Rev Time 0.00
Received By elevesqu Date 2018-10-17 Time 15:26 Sent To  
Notes
2018-10-17 15:27:09PROVISO:
 1. THE REQUIRED DISTANCE BETWEEN A BICYCLE HITCH AND A
 WALL IS 24'. IT DOES NOT APPEAR THAT THE PROPOSED
 BICYCLE HITCH INTERIOR TO THE GATES WILL MEET THE RACK
 DIMENSION REQUIREMENTS. THE APPLICANT CAN PROPOSE NEW
 LOCATION (WILL HAVE TO BE MOVED, SEE PROVISO NO. 3).
 ADDITIONALLY, ONE HITCH CAN BE REMOVED IF NECESSARY, AS
 THE REQUIRED NUMBER OF INTERNAL BICYCLE RACKS IS SIX.
  
 2. PLEASE MOVE THE BICYCLE RACK ON DATURA STREET TO THE
 BULBOUT TO PROVIDE ENOUGH ROOM ON THE SIDEWALK.
  
 3. PROPOSED FENCES ALONG DATURA STREET SHALL BE LOCATED
 OUTSIDE THE 16' SETBACK LINE, SHALL BE A MAXIMUM HEIGHT
 OF 4', AND SHALL BE LOCATED BEHIND 5' LANDSCAPE BUFFER.
 PLEASE ADJUST LOCATION OF PEDESTRIAN FENCE AND GATE.
  
 4. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS THE
 DRIVEWAY.
  
 5. WITHIN 60 DAYS OF PERMIT ISSUANCE, THE APPLICANT
 SHALL RESUBMIT THE FOLLOWING INFORMATION/PLANS:
 A. THE UPDATED PLANNING PLAN TO MATCH THE SITE PLAN.
 B. AN UPDATED CIVIL PLAN REFLECTING THE SITE PLAN AND
 THAT SHOWS THE MAINTAINED SIDEWALK ELEVATION ALONG
 DRIVEWAY CURB CUTS.
 C. AN UPDATED SITE PLAN DETAIL SHEET SP 1.0.2. SHOWING
 THE CORRECT SIZED ROLLING GATE AND PEDESTRIAN GATE
 DETAIL.
 D. UPDATE THE BICYCLE HITCH LOCATIONS ON SITE PLAN SP
 1.0.1.
 E. LABEL THE TYPICAL PARKING STALL DIMENSIONS ON SHEET
 SP 1.0.1. ALONG ALL ROWS OF PARKING, AS THEY HAVE
 DIFFERENT LENGTHS DEPENDING ON THE ROW.
 F. PLEASE SUBMIT A PHOTOMETRIC PLAN AND DETAIL PLAN
 THAT SHOWS PHOTOMETRICS OF THE PUBLIC SIDEWALKS,
 INTERNAL SIDEWALKS, BUILDING ENTRANCES, DUMPSTER AREA,
 ETC AND LIGHT FIXTURE DETAIL. PER SECTION 94-113 (B),
 BUILDINGS SHALL PROVIDE LIGHTING AT A MINIMUM OF 0.6
 FOOTCANDLE AND MAXIMUM OF 1.0 FOOTCANDLE AS MEASURED AT
 THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK. LIGHT FIXTURES AND POLES SHALL MEET THE CITY
 APPROVED STANDARD.
 G. RELOCATE THE PEDESTRIAN GATE BEHIND THE REQUIRED 16
 FOOT SETBACK AND BEHIND THE LANDSCAPE BUFFER/HEDGE ON
 SHEET SP 1.0.1.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-08-20 Cont ID  
Sent By elevesqu Date 2018-08-20 Time 15:34 Rev Time 0.00
Received By elevesqu Date   Time   Sent To  
Notes
2018-08-20 15:34:51PLANTING PLAN IS NOT UPDATED VERSION - NEEDS TO MATCH
 LATEST FROM SITE PLAN REVIEW.
  
 ADDITIONAL ADA SPACE ON PERMIT PLANS DOES NOT MATCH
 LATEST FROM SITE PLAN. PLEASE CALL TO DISCUSS
 MODIFICATION.
  
 GATE SHOWN ON SHEET SP1.0.2 DOES NOT MATCH GATE ON
 LATEST SUBMITTED SHEET 1.0.2.
  
 CONTACT LIZ LEVESQUE, URBAN DESIGN PLANNER OR
 [email protected] WITH ANY QUESTIONS

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By AA Date 2018-06-07 Time 16:44 Rev Time 0.00
Received By elevesqu Date 2018-06-07 Time 16:44 Sent To  
Notes
2018-06-07 16:44:53PENDING SITE PLAN APPROVAL. APPLICANT NEEDS TO RESUBMIT
 PLANS THAT MATCH SITE PLAN APPROVAL PLANS - SUBMITTED
 PLANS ARE OLD VERSIONS.
  
 CALL LIZ LEVESQUE WITH ANY QUESTIONS
 561-822-1426
  
  