Plan Review Details - Permit 18040097
Plan Review Stops For Permit 18040097
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-05-10 Cont ID  
Sent By jgomez Date 2019-05-10 Time 18:58 Rev Time 0.00
Received By jgomez Date 2019-05-10 Time 16:54 Sent To I
Notes
2019-05-10 18:59:32BUILDING REVIEW APPROVED WITH PROVISO:
 1-ARCHITECT TO SPECIFY MATERIALS TO BE USED IN FIRE
 RATED CEILINGS & TENANT SEPARATION WALLS PRIOR TO
 INSPECTIONS. SEC. 702.6 FBC-EXISTING BUILDING.
  
 2- SIZE OF BEDROOM WINDOWS ON UNITS #5 AND #12 WERE
 REDUCED. THERE ARE NO PERMITS TO CHANGE THE SIZE OF THE
 WINDOWS. REVISE WINDOW SIZE TO ORIGINAL SIZE.
  
 3- SEC. 702.4 FBC-EXISTING BUILDING: WINDOW OPENING
 CONTROL DEVICES COMPLYING WITH ASTM F2090 MAY BE
 REQUIRED IF IN GROUP R-2 IF ALL OF THE FOLLOWING APPLY
 TO THE REPLACEMENT WINDOW: (1)THE WINDOW IS OPERABLE;
 (2)THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME; (3)IN GROUP R-2 THE TOP OF THE SILL
 OF THE WINDOW OPENING IS AT A HEIGHT LESS THAN 36
 INCHES (915 MM) ABOVE THE FINISHED FLOOR; (4)THE WINDOW
 WILL PERMIT OPENINGS THAT WILL ALLOW PASSAGE OF A
 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE WINDOW IS IN
 ITS LARGEST OPENED POSITION; AND (5)THE VERTICAL
 DISTANCE FROM THE TOP OF THE SILL OF THE WINDOW OPENING
 TO THE FINISHED GRADE OR OTHER SURFACE BELOW, ON THE
 EXTERIOR OF THE BUILDING, IS GREATER THAN 72 INCHES
 (1829 MM). THE WINDOW OPENING CONTROL DEVICE, AFTER
 OPERATION TO RELEASE THE CONTROL DEVICE ALLOWING THE
 WINDOW TO FULLY OPEN, SHALL NOT REDUCE THE MINIMUM NET
 CLEAR OPENING AREA OF THE WINDOW UNIT TO LESS THAN THE
 AREA REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING.
  
 4- IF CHANGING FLOORING, THEN PROVIDE THE FOLLOWING:
 FLOORING SOUND INSULATION MATERIAL: A) COPY OF THE
 FLAME SPREAD INDEX & SMOKE DEVELOPED INDEX TEST (ASTM E
 84 OR UL 723) SEC. 720.1 OF FBC. B) COPY OF THE SOUND
 TRANSMISSION CLASS (STC) TEST ( ASTM E 90) SEC. 1207.2
 OF FBC. AND C) COPY OF THE IMPACT INSULATION CLASS
 (IIC) TEST (ASTM E 492) SEC. 1207.3 OF FBC 6TH EDITION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-12-12 Cont ID  
Sent By jgomez Date 2018-12-12 Time 11:56 Rev Time 0.00
Received By jgomez Date 2018-12-12 Time 12:56 Sent To  
Notes
2018-12-10 11:57:19RESIDENTIAL (R2) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- PLANS TO HAVE COMPLETE DETAILS AND SPECIFICATIONS
 CLEARLY SPECIFYING ALL SCOPE OF WORK, INCLUDING BUT NOT
 LIMITED TO WORK ON TENANT FIRE RATED WALLS, FLOOR
 CEILING FIRE RATED ASSEMBLY, FIRE RATING OF TENANT
 ENTRY DOORS, DESIGN PRESSURES FOR EXTERIOR DOORS AND
 WINDOWS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: ACCORDING TO CITY RECORDS PERMIT #98100735 AND
 PROPERTY APPRAISER THERE ARE 12 UNITS TOTAL NOT 13.
 PLANS TO SHOW THAT EXISTING OFFICE IS CHANGED TO
 APARTMENT/STUDIO. NEED TO TAKE PLANS TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT.
  
 RESPONSE:
 REPEAT COMMENT. SCOPE OF WORK SHOWN ON THE FIRST FLOOR
 PLAN SHEET OF DRAWINGS SUBMITTED IS TOO GENERAL.
 ARCHITECT TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR WORK IN FIRE RATED WALLS, FLOOR
 CEILING ASSEMBLIES, ETC. AND, CLEARLY IDENTIFY ALL
 AREAS OF WORK. ALSO, COORDINATE WITH SCOPE OF WORK
 SHOWN CONTRACTOR'S PROPOSAL TO AVOID CONFLICTS/DELAYS.
  
 2- IMPACT FEES
 UPON APPROVAL OF PLANS ONE SET OF PLANS SHALL BE SIGNED
 OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN IMPACT
 FEE REVIEW BASED ON THE NUMBER OF UNITS. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH CAN BE
 ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY IMPACT
 FEES AT (561) 233-5025.
  
 ORIGINAL COMMENT:
 3- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. PLANS SUBMITTED DON'T SPECIFY EXISTING
 SIZE AND TYPE OF WINDOWS AND PROPOSED SIZE AND TYPE.
 PROVIDE REQUIRED INFORMATION. NEED TO VERIFY
 MANUFACTURER'S LARGEST STANDARD SIZE WINDOW. SEE COPY
 BELOW OF THE REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING CODE WHEN REPLACING WINDOWS. ALSO, NEED TO
 VERIFY WINDOW OPENING CONTROL DEVICES. SEE SEC. 702.4
 FBC-EXISTING BUILDING BELOW.
 NOTE: CLARIFY WHY ONLY THE BEDROOM WINDOWS FOR UNIT #5
 ON FIRST FLOOR AND UNIT #12 ON SECOND FLOOR HAVE A
 DIFFERENT WINDOW HEIGHT AS THE REST OF THE BEDROOM
 WINDOWS. ALSO, THEY DON'T SEEM TO BE THE SAME AS ONES
 SHOWN ON APPROVED PERMIT #98100735. (COORDINATE WITH
 ITEM #8 BELOW).
  
 702.5 EMERGENCY ESCAPE AND RESCUE OPENINGS.
  
 WHERE WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN GROUP R-2 AND R-3 OCCUPANCIES
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 REPLACEMENT WINDOWS SHALL BE EXEMPT FROM THE
 REQUIREMENTS OF SECTIONS 1030.2, 1030.3 AND 1030.5 OF
 THE FLORIDA BUILDING CODE, BUILDING AND SECTIONS
 R310.21 AND R310.2.3 OF THE FLORIDA BUILDING CODE,
 RESIDENTIAL ACCORDINGLY, PROVIDED THE REPLACEMENT
 WINDOW IS THE MANUFACTURER?S LARGEST STANDARD SIZE
 WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING. THE REPLACEMENT WINDOW SHALL BE
 PERMITTED TO BE OF THE SAME OPERATING STYLE AS THE
 EXISTING WINDOW OR A STYLE THAT PROVIDES FOR AN EQUAL
 OR GREATER WINDOW OPENING AREA THAN THE EXISTING
 WINDOW.
  
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE PERMITTED FOR USE ON WINDOWS REQUIRED TO
 PROVIDE EMERGENCY ESCAPE AND RESCUE OPENINGS.
  
 NOTE: WINDOW REPLACEMENT ALSO MAY NEED TO COMPLY WITH
 THE WINDOW OPENING CONTROL DEVICES SEC. 702.4
 FBC-EXISTING BUILDING. CLEARLY IDENTIFY ON PLANS
 WINDOWS THAT WILL REQUIRE WINDOW OPENING CONTROL
 DEVICES. SEE COPY OF SEC. 702.4 BELOW.
  
 702.4 WINDOW OPENING CONTROL DEVICES.
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
  
 1.THE WINDOW IS OPERABLE;
  
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
  
 3.ONE OF THE FOLLOWING APPLIES:
  
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
  
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
  
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
  
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
  
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTIONS:
  
 1.OPERABLE WINDOWS WHERE THE TOP OF THE SILL OF THE
 WINDOW OPENING IS LOCATED MORE THAN 75 FEET (22 860 MM)
 ABOVE THE FINISHED GRADE OR OTHER SURFACE BELOW, ON THE
 EXTERIOR OF THE ROOM, SPACE OR BUILDING, AND THAT ARE
 PROVIDED WITH WINDOW FALL PREVENTION DEVICES THAT
 COMPLY WITH ASTM F2006.
  
 2.OPERABLE WINDOWS WITH OPENINGS THAT ARE PROVIDED WITH
 WINDOW FALL PREVENTION DEVICES THAT COMPLY WITH ASTM
 F2090.
  
  
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR (NOTE: THIS MAY BE SUBMITTED LATER
 AS A DEFERRED SUBMITTAL BUT BEFORE INSTALLATION TO
 AVOID CONFLICTS/DELAYS):
  
 A) EXTERIOR DOORS IF REPLACED. PLANS ARE NOT CLEAR IF
 DOORS ARE GOING TO BE REPLACED. NOTE: COORDINATE WITH
 ITEM #8 BELOW.
  
 ORIGINAL COMMENT:
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS, ROOFING, ETC) AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. REVISE AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 RESPONSE:
 CONTRACTOR'S PROPOSAL LETTER SUBMITTED INCLUDES
 EXTERIOR WORK THAT NEEDS TO BE DONE UNDER SEPARATE
 PERMITS (ROOFING, EXTERIOR LIGHTING, LANDSCAPING AND
 DRIVEWAY). PROVIDE ONLY THE VALUATION FOR WORK WITHIN
 THE BUILDING. APPLY FOR THE OTHER PERMITS SEPARATELY.
 ALSO, PROPOSAL LETTER SPECIFIES 25 UNITS. CLARIFY # OF
 UNITS. NOTE: CONTRACTOR AND ARCHITECT TO COORDINATE
 SCOPE OF WORK TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 7- CONTRACTOR'S PROPOSAL LETTER INCLUDES NEW FLOORING.
 PROVIDE THE FOLLOWING FLOORING INFORMATION AS REQUIRED
 BY SEC. 602.2 FBC-EXISTING BUILDING CODE FOR NEW AND
 REPLACEMENT MATERIALS. SEE COPY OF THIS SECTION BELOW.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL BUT BEFORE INSTALLATION TO AVOID
 CONFLICTS/DELAYS):
  
 FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH.
  
 RESPONSE:
 NOT ADDRESSED. COORDINATE WITH ITEM #1 ABOVE.
  
 NEW COMMENTS BASED ON SIGNED AND SEALED PLANS
 SUBMITTED:
 (PLANS WERE NOT REVIEWED EARLIER BECAUSE THEY WERE NOT
 PREPARED BY A LICENSED ARCHITECT AS REQUIRED BY SEC.
 481.229 F.S. AND REQUESTED ON FIST REVIEW)
  
 8- PLANS SUBMITTED DON'T MATCH LAST APPROVED PLANS ON
 CITY RECORDS PERMIT #98100735 (WHICH HAPPENS TO BE
 PERFORMED BY SAME ARCHITECT SUBMITTING PLANS NOW).
 THERE ARE NO CITY RECORDS FOR PERMITS TO DO ALTERATIONS
 TO THE APPROVED PLANS. THERE ARE SIGNIFICANT CHANGES ON
 THE FIRST AND SECOND FLOOR PLANS. FLOOR LAYOUT WAS
 CHANGED ON SOME UNITS. ARCHITECT TO PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR WORK ON AREAS THAT WERE
 CHANGED FROM APPROVED PLANS ON PERMIT #98100735.
 INCLUDING BUT NOT LIMITED TO UNIT #6 NEW EXTERIOR DOOR
 ON WEST SIDE, MAIN SINGLE ENTRY DOOR ON EAST SIDE AND
 ALL UNITS FLOOR LAYOUTS THAT WERE CHANGED. SEC. 107.2.1
 AND SEC. 105.1 CITY AMENDMENTS.
  
 9- FIRST FLOOR PLAN SUBMITTED SHOWS A DOOR AT THE ENTRY
 OF STAIRWAY TO SECOND FLOOR. THIS DOOR LOOKS LIKE IS
 BLOCKING THE EGRESS FROM RESIDENTS ON SECOND FLOOR. IN
 ADDITION NEED TO SHOW COMPLIANCE WITH SEC. 1010.1.9.11
 FBC (DOORS) AND SEC. 1011.6 FBC (LANDINGS). REVISE AS
 REQUIRED.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-18 Cont ID  
Sent By jgomez Date 2018-09-14 Time 18:04 Rev Time 0.00
Received By jgomez Date 2018-09-14 Time 18:04 Sent To  
Notes
2018-09-13 17:55:01RESIDENTIAL (R2) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- PROVIDE COMPLETE PLANS SIGNED AND SEALED BY LICENSED
 ARCHITECT AS REQUIRED BY SEC. 481.229 FLORIDA STATUTE.
  
 NOTE:
 THIS ITEM WAS DISCUSSED BETWEEN STEVE KENNEDY
 (ASSISTANT BUILDING OFFICIAL) AND KEN BEST (ONE OF THE
 OWNERS). OWNER AGREED HE WAS GOING TO TALK TO HIS
 ARCHITECT. ALSO, I DISCUSSED THIS WITH ROBERT BROWN
 (BUILDING OFFICIAL). HE ALSO AGREES ARCHITECT IS
 REQUIRED. CONTRACTOR AND OWNER ARE WELCOME TO REQUEST A
 MEETING WITH ROBERT BROWN, SAMANTHA HILL (CHIEF PLANS
 EXAMINER)AND ME IF ADDITIONAL CLARIFICATION IS
 REQUIRED.
  
 RESPONSE:
 PLANS SUBMITTED ARE NOT PREPARED BY A LICENSED
 ARCHITECT. BASED ON ALL THE SCOPE OF WORK AND VALUE THE
 PLANS ARE REQUIRED TO BE PERFORMED BY A LICENSED
 ARCHITECT. SEE COPY OF FLORIDA STATUTES 481.229
 EXCEPTIONS: EXEMPTIONS FROM LICENSURE BELOW:
  
  
 TITLE XXXII
 REGULATION OF PROFESSIONS AND OCCUPATIONS
  
 CHAPTER 481
 ARCHITECTURE, INTERIOR DESIGN, AND LANDSCAPE
 ARCHITECTURE
  
 SECTION 229
 EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
  
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE.?
 (1)NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
 (A)ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
  
 (B)ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING,
 TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY
 ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST;
 OR
  
 (C)ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF
 A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR
 SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
  
  
 ORIGINAL COMMENT:
 2- PLANS TO HAVE COMPLETE DETAILS AND SPECIFICATIONS
 CLEARLY SPECIFYING ALL SCOPE OF WORK, INCLUDING BUT NOT
 LIMITED TO WORK ON TENANT FIRE RATED WALLS, FLOOR
 CEILING FIRE RATED ASSEMBLY, FIRE RATING OF TENANT
 ENTRY DOORS, DESIGN PRESSURES FOR EXTERIOR DOORS AND
 WINDOWS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: ACCORDING TO CITY RECORDS PERMIT #98100735 AND
 PROPERTY APPRAISER THERE ARE 12 UNITS TOTAL NOT 13.
 PLANS TO SHOW THAT EXISTING OFFICE IS CHANGED TO
 APARTMENT/STUDIO. NEED TO TAKE PLANS TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT.
  
 RESPONSE:
 SCOPE OF WORK SHOWN ON THE FIRST FLOOR PLAN SHEET OF
 DRAWINGS SUBMITTED IS TOO GENERAL. ARCHITECT TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS. AND, CLEARLY
 IDENTIFY ALL AREAS OF WORK.
  
 3- 1- IMPACT FEES
 COUNTY. UPON APPROVAL, ONE SET OF PLANS SHALL BE SIGNED
 OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN IMPACT
 FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP AND A
 COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE CITY
 BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 ORIGINAL COMMENT:
 4- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 RESPONSE:
 PLANS SUBMITTED DON'T SPECIFY EXISTING SIZE AND TYPE OF
 WINDOWS AND PROPOSED SIZE AND TYPE. PROVIDE REQUIRED
 INFORMATION. NEED TO VERIFY MANUFACTURER'S LARGEST
 STANDARD SIZE WINDOW. SEE COPY BELOW OF THE
 REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING CODE
 WHEN REPLACING WINDOWS. ALSO, NEED TO VERIFY WINDOW
 OPENING CONTROL DEVICES. SEE SEC. 702.4 FBC-EXISTING
 BUILDING BELOW.
  
 702.5 EMERGENCY ESCAPE AND RESCUE OPENINGS.
  
 WHERE WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE
 AND RESCUE OPENINGS IN GROUP R-2 AND R-3 OCCUPANCIES
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 REPLACEMENT WINDOWS SHALL BE EXEMPT FROM THE
 REQUIREMENTS OF SECTIONS 1030.2, 1030.3 AND 1030.5 OF
 THE FLORIDA BUILDING CODE, BUILDING AND SECTIONS
 R310.21 AND R310.2.3 OF THE FLORIDA BUILDING CODE,
 RESIDENTIAL ACCORDINGLY, PROVIDED THE REPLACEMENT
 WINDOW IS THE MANUFACTURER?S LARGEST STANDARD SIZE
 WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING. THE REPLACEMENT WINDOW SHALL BE
 PERMITTED TO BE OF THE SAME OPERATING STYLE AS THE
 EXISTING WINDOW OR A STYLE THAT PROVIDES FOR AN EQUAL
 OR GREATER WINDOW OPENING AREA THAN THE EXISTING
 WINDOW.
  
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE PERMITTED FOR USE ON WINDOWS REQUIRED TO
 PROVIDE EMERGENCY ESCAPE AND RESCUE OPENINGS.
  
 NOTE: WINDOW REPLACEMENT ALSO MAY NEED TO COMPLY WITH
 THE WINDOW OPENING CONTROL DEVICES SEC. 702.4
 FBC-EXISTING BUILDING. THIS WILL BE VERIFIED IN THE
 FIELD BY THE INSPECTOR.
  
 702.4 WINDOW OPENING CONTROL DEVICES.
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
  
 1.THE WINDOW IS OPERABLE;
  
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
  
 3.ONE OF THE FOLLOWING APPLIES:
  
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
  
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
  
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
  
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
  
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTIONS:
  
 1.OPERABLE WINDOWS WHERE THE TOP OF THE SILL OF THE
 WINDOW OPENING IS LOCATED MORE THAN 75 FEET (22 860 MM)
 ABOVE THE FINISHED GRADE OR OTHER SURFACE BELOW, ON THE
 EXTERIOR OF THE ROOM, SPACE OR BUILDING, AND THAT ARE
 PROVIDED WITH WINDOW FALL PREVENTION DEVICES THAT
 COMPLY WITH ASTM F2006.
  
 2.OPERABLE WINDOWS WITH OPENINGS THAT ARE PROVIDED WITH
 WINDOW FALL PREVENTION DEVICES THAT COMPLY WITH ASTM
 F2090.
  
  
  
 ORIGINAL COMMENT:
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR (NOTE: THIS MAY BE SUBMITTED LATER
 AS A DEFERRED SUBMITTAL BUT BEFORE INSTALLATION TO
 AVOID CONFLICTS/DELAYS):
  
 A) EXTERIOR DOORS IF REPLACED. PLANS ARE NOT CLEAR IF
 DOORS ARE GOING TO BE REPLACED.
  
 ORIGINAL COMMENT:
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS,
 WINDOWS) AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 7-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. REVISE AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 RESPONSE:
 CONTRACTOR'S PROPOSAL LETTER SUBMITTED INCLUDES
 EXTERIOR WORK THAT NEEDS TO BE DONE UNDER SEPARATE
 PERMITS (ROOFING, EXTERIOR LIGHTING, LANDSCAPING AND
 DRIVEWAY). PROVIDE ONLY THE VALUATION FOR WORK WITHIN
 THE BUILDING. APPLY FOR THE OTHER PERMITS SEPARATELY.
 ALSO, PROPOSAL LETTER SPECIFIES 25 UNITS. CLARIFY # OF
 UNITS.
  
 NEW COMMENT:
 8- CONTRACTOR'S PROPOSAL LETTER INCLUDES NEW FLOORING.
 PROVIDE THE FOLLOWING FLOORING INFORMATION AS REQUIRED
 BY SEC. 602.2 FBC-EXISTING BUILDING CODE FOR NEW AND
 REPLACEMENT MATERIALS. SEE COPY OF THIS SECTIION BELOW.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL BUT BEFORE INSTALLATION TO AVOID
 CONFLICTS/DELAYS):
  
 FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH.
  
 602.2 NEW AND REPLACEMENT MATERIALS.
  
 EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY THIS CODE,
 MATERIALS PERMITTED BY THE APPLICABLE CODE FOR NEW
 CONSTRUCTION SHALL BE USED. LIKE MATERIALS SHALL BE
 PERMITTED FOR REPAIRS AND ALTERATIONS, PROVIDED NO
 DANGEROUS OR UNSAFE CONDITION, AS DEFINED IN CHAPTER 2,
 IS CREATED. HAZARDOUS MATERIALS, SUCH AS ASBESTOS AND
 LEAD-BASED PAINT, SHALL NOT BE USED WHERE THE CODE FOR
 NEW CONSTRUCTION WOULD NOT PERMIT THEIR USE IN
 BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND LOCATION.
  
 EXCEPTION: REPAIRS TO A HISTORIC BUILDING SHALL BE
 PERMITTED USING ORIGINAL OR LIKE MATERIALS. MATERIALS
 SHALL COMPLY WITH SECTIONS 602.2, 602.3 AND 602.4.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By jgomez Date 2018-05-16 Time 18:51 Rev Time 0.00
Received By jgomez Date 2018-05-16 Time 16:13 Sent To  
Notes
2018-05-17 10:19:16RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE COMPLETE PLANS SIGNED AND SEALED BY LICENSED
 ARCHITECT AS REQUIRED BY SEC. 481.229 FLORIDA STATUTE.
  
 2- PLANS TO HAVE COMPLETE DETAILS AND SPECIFICATIONS
 CLEARLY SPECIFYING ALL SCOPE OF WORK, INCLUDING BUT NOT
 LIMITED TO WORK ON TENANT FIRE RATED WALLS, FLOOR
 CEILING FIRE RATED ASSEMBLY, FIRE RATING OF TENANT
 ENTRY DOORS, DESIGN PRESSURES FOR EXTERIOR DOORS AND
 WINDOWS, ETC. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: ACCORDING TO CITY RECORDS PERMIT #98100735 AND
 PROPERTY APPRAISER THERE ARE 12 UNITS TOTAL NOT 13.
 PLANS TO SHOW THAT EXISTING OFFICE IS CHANGED TO
 APARTMENT/STUDIO. NEED TO TAKE PLANS TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT.
  
 3- 1- IMPACT FEES
 COUNTY. UPON APPROVAL, ONE SET OF PLANS SHALL BE SIGNED
 OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN IMPACT
 FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP AND A
 COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE CITY
 BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  
 4- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5
 FBC-EXISTING BUILDING.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR DOORS IF REPLACED.
  
 B) WINDOW MULLIONS AND CLEARLY MARK MULLION SIZE TO
 VERIFY COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 7-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. REVISE AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2019-11-12 Cont ID  
Sent By jpearson Date 2019-11-12 Time 12:24 Rev Time 0.00
Received By jpearson Date 2019-11-12 Time 10:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2019-09-17 Cont ID  
Sent By jpearson Date 2019-09-17 Time 09:06 Rev Time 0.00
Received By jpearson Date 2019-09-17 Time 09:06 Sent To  
Notes
2019-09-17 09:05:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED, BECAUSE A NEW ELECTRICAL PLAN WAS SUBMITTED
 BY AN ENGINEER, THIS REVIEW IS NEW AND PREVIOUS
 COMMENTS ARE DISCARDED.
  
 1. PER THE WPB AMENDMENTS TO THE FBC: SUBMITTAL
 DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS,
 STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH PERMIT APPLICATION. NOTICE THE WORD "SETS".
 THE SUBMISSION PROVIDED IS VERY DISORGANIZED AND NOT IN
 TWO COMPLETE SETS. PROVIDE CORRECTION. WPB FBC 107.1
 2. A BLOCK NOTE ON SHEET E-1 STATES THAT OTHER SHEETS
 WERE PROVIDED AND PREVIOUSLY APPROVED FOR THE
 ELECTRICAL IN THE ROOMS. THIS IS NOT CORRECT. THE
 ENGINEER OF RECORD SHOULD SUPPLY PLANS FOR ALL THE WORK
 TO BE COMPLETED DESCRIBED IN THE SCOPE OF WORK. TO
 DATE, THERE ARE NO APPROVED PLANS FOR ANY PORTION OF
 THE ELECTRICAL WORK. PER THE WPB AMENDMENTS TO THE FBC:
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. PROVIDE CORRECTIONS. WPB FBC
 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION FOR THE SERVICE.
 THE ENGINEER HAS USED THE DEMAND LOAD FROM EACH PANEL,
 AND THEN FURTHER APPLIED A DEMAND FACTOR TO THIS NUMBER
 BASED ON THE TABLE IN NEC 220.84. THIS VIOLATES HOW
 THIS CODE ARTICLE SHOUOLD BE APPLIED. PROVIDE
 CORRECTION. NEC 220.84(C)
 4. IN REFERENCE TO LAD CALCULATION, THE RISER DIAGRAM
 SHOW 13 METERS, AND 13 RUNS TO UNITS, BUT THE LOAD
 CALCULATION ONLY INCLUDES 12 UNITS. STUDIO IS NOT SHOWN
 ON PLANS. CORRECT DISCREPANCIES, PROVIDE CORRECTION.
 NEC 215.2, 220; WPB FBC 107.2.1
 5. IN REFERENCE TO LAD CALCULATION, PANEL SCHEDULE
 SHOWS ONLY ONE SMALL APPLIANCE CIRCUIT. A MINIMUM OF
 TWO 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY KITCHEN COUNTERTOP RECEPTACLE OUTLET(S). PROVIDE
 CORRECTION. NEC 210.11(C)(1)
 6. RISER DIAGRAM SHOWS THREE RUNS OF 500 KCMIL WIRE FOR
 THE SERVICE DROP. PER NEC 240.4(C), THE AMPACITY OF THE
 CONDUCTORS FEEDING THIS OVERCURRENT DEVICE SHALL BE
 RATED EQUAL TO OR GREATER THAN THE OVERCURRENT DEVICE.
 PROVIDE CORRECTION. NEC 240.4(C)
 7. AFCI PROTECTION SHOWN IN NOTE 2 OF PANEL HAS NOT
 BEEN APPLIED PROPERLY TO THE CIRCUITS THAT REQUIRE AFCI
 PROTECTION. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 8. AS THE PLAN PROVIDED IS MISSING A SUBSTANTIAL AMOUNT
 OF INFORMATION, A FULL REVIEW IS NOT POSSIBLE AT THIS
 TIME. FURTHER REVIEW COMMENTS MAY BE POSSIBLE WHEN
 CORRECTIONS ARE SUBMITTED. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2019-05-31 Cont ID  
Sent By jpearson Date 2019-05-31 Time 15:38 Rev Time 0.00
Received By jpearson Date 2019-05-31 Time 15:38 Sent To M
Notes
2019-05-31 15:38:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NOTICE COMMENT 16 BELOW. THIS PLAN IS NOT ACCEPTABLE AS
 IS. THE CAPACITY OF THE SERVICE EXCEEDS THE AMOUNT
 PERMITTED TO BE DESIGNED BY AN ELECTRICAL CONTRACTOR.
 ADDITIONALLY, FURTHER INFORMATION SUBMITTED WAS
 SUBMITTED ON 8.5 X 11 PAPER. THE WEST PALM BEACH
 AMMENDMENTS TO THE FBC REQUIRE A MINIMUM OF 1/8 SCALE
 PLAN. A LICENSED DESIGN PROFESSIONAL SHOULD PROVIDE
 CORRECTIONS AS NOTED BELOW. WPB FBC 107.2.1.3
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. RISER DIAGRAM PROVIDED SHOWS WHAT APPEARS TO BE A
 1200 AMP METER BANK. WILL THIS HAVE A 1200 AMP BREAKER
 AS A MAIN DISCONNECT SO AS NOT TO EXCEED THE MAXIMUM
 NUMBER OF MAINS PERMITTED? THIS IS NOT EXPLAINED ON
 RISER DIAGRAM. IF SO, PROVIDE ARC ENERGY REDUCTION PER
 NEC 240.87. PROVIDE DETAILS. WPB FBC 107.2.1; NEC
 230.71
 8. RISER SHOWS PARALLEL 600 KCMIL COPPER AS SERVICE
 CONDUCTORS. THE AMPACITY OF TWO RUNS OF 600 KCMIL
 COPPER IS 840 AMPS. PER CODE, THE AMPACITY OF THESE
 CONDUCTORS SHALL BE EQUAL TO OR GREATER THAN THE
 OVERCURRENT DEVICE. PROVIDE CORRECTION. NEC 240.4(C)
 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 10. PANEL SCHEDULE PROVIDED SOES NOT SHOW THE GFCI
 PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT THAT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 11. PROVIDE LOAD CALCULATION FOR EACH PANEL AND FOR
 SERVICE TO CONFIRM THAT THE SERVICE IS ADEQUATELY
 SIZED. NEC 220; WPB FBC 107.2.1
 12. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 13. RISER SHOWS A 1/0 COPPER GROUNDING ELECTRODE
 CONDUCTOR. THE GROUNDING ELECTRODE CONDUCTOR SHOULD BE
 SIZED FOR THE TOTAL AREA OF THE SERVICE CONDUCTORS.
 SHOW ALL AVAILABLE GROUNDING ELECTRODES. PROVIDE
 CORRECTION. NEC 250.50, 250.66
 14. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 15. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 16. DESIGN OF ELECTRICAL SYSTEM IS SHOWN AS 1200 AMP.
 THIS IS NOT PERMITTED TO BE DESIGNED BY THE ELECTRICAL
 CONTRACTOR PER FLORIDA STATUTES. PROVIDE PLAN BY A
 DESIGN PROFESSIONAL. FS 471.003(2)(H); WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-04-22 Cont ID  
Sent By jpearson Date 2019-04-22 Time 15:45 Rev Time 0.00
Received By jpearson Date 2019-04-22 Time 13:24 Sent To  
Notes
2019-04-22 15:44:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 NOTICE COMMENT 16 BELOW. THIS PLAN IS NOT ACCEPTABLE AS
 IS. THE CAPACITY OF THE SERVICE EXCEEDS THE AMOUNT
 PERMITTED TO BE DESIGNED BY AN ELECTRICAL CONTRACTOR.
 ADDITIONALLY, FURTHER INFORMATION SUBMITTED WAS
 SUBMITTED ON 8.5 X 11 PAPER. THE WEST PALM BEACH
 AMMENDMENTS TO THE FBC REQUIRE A MINIMUM OF 1/8 SCALE
 PLAN. A LICENSED DESIGN PROFESSIONAL SHOULD PROVIDE
 CORRECTIONS AS NOTED BELOW. WPB FBC 107.2.1.3
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. DUE TO ADJUSTMENT OF VALUE, ADDITIONAL FEES FOR PLAN
 REVIEW ARE DUE PRIOR TO THE NEXT PLAN REVIEW CYCLE. WPB
 FBC 105.1 (ADDITIONAL FEES NOT PAID, A HOLD WILL BE
 PLACED ON PERMIT UNTIL FEES ARE PAID.)
  
 NEW COMMENTS:
  
 7. RISER DIAGRAM PROVIDED SHOWS WHAT APPEARS TO BE A
 1200 AMP METER BANK. WILL THIS HAVE A 1200 AMP BREAKER
 AS A MAIN DISCONNECT SO AS NOT TO EXCEED THE MAXIMUM
 NUMBER OF MAINS PERMITTED? THIS IS NOT EXPLAINED ON
 RISER DIAGRAM. IF SO, PROVIDE ARC ENERGY REDUCTION PER
 NEC 240.87. PROVIDE DETAILS. WPB FBC 107.2.1; NEC
 230.71
 8. RISER SHOWS PARALLEL 600 KCMIL COPPER AS SERVICE
 CONDUCTORS. THE AMPACITY OF TWO RUNS OF 600 KCMIL
 COPPER IS 840 AMPS. PER CODE, THE AMPACITY OF THESE
 CONDUCTORS SHALL BE EQUAL TO OR GREATER THAN THE
 OVERCURRENT DEVICE. PROVIDE CORRECTION. NEC 240.4(C)
 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 10. PANEL SCHEDULE PROVIDED SOES NOT SHOW THE GFCI
 PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT THAT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 11. PROVIDE LOAD CALCULATION FOR EACH PANEL AND FOR
 SERVICE TO CONFIRM THAT THE SERVICE IS ADEQUATELY
 SIZED. NEC 220; WPB FBC 107.2.1
 12. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 13. RISER SHOWS A 1/0 COPPER GROUNDING ELECTRODE
 CONDUCTOR. THE GROUNDING ELECTRODE CONDUCTOR SHOULD BE
 SIZED FOR THE TOTAL AREA OF THE SERVICE CONDUCTORS.
 SHOW ALL AVAILABLE GROUNDING ELECTRODES. PROVIDE
 CORRECTION. NEC 250.50, 250.66
 14. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 15. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 16. DESIGN OF ELECTRICAL SYSTEM IS SHOWN AS 1200 AMP.
 THIS IS NOT PERMITTED TO BE DESIGNED BY THE ELECTRICAL
 CONTRACTOR PER FLORIDA STATUTES. PROVIDE PLAN BY A
 DESIGN PROFESSIONAL. FS 471.003(2)(H); WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-11-05 Cont ID  
Sent By jpearson Date 2018-11-05 Time 18:48 Rev Time 0.00
Received By jpearson Date 2018-11-05 Time 17:58 Sent To  
Notes
2018-11-05 18:48:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. DUE TO ADJUSTMENT OF VALUE, ADDITIONAL FEES FOR PLAN
 REVIEW ARE DUE PRIOR TO THE NEXT PLAN REVIEW CYCLE. WPB
 FBC 105.1 (ADDITIONAL FEES NOT PAID, A HOLD WILL BE
 PLACED ON PERMIT UNTIL FEES ARE PAID.)
  
 NEW COMMENTS:
  
 7. RISER DIAGRAM PROVIDED SHOWS WHAT APPEARS TO BE A
 1200 AMP METER BANK. WILL THIS HAVE A 1200 AMP BREAKER
 AS A MAIN DISCONNECT SO AS NOT TO EXCEED THE MAXIMUM
 NUMBER OF MAINS PERMITTED? THIS IS NOT EXPLAINED ON
 RISER DIAGRAM. IF SO, PROVIDE ARC ENERGY REDUCTION PER
 NEC 240.87. PROVIDE DETAILS. WPB FBC 107.2.1; NEC
 230.71
 8. RISER SHOWS PARALLEL 600 KCMIL COPPER AS SERVICE
 CONDUCTORS. THE AMPACITY OF TWO RUNS OF 600 KCMIL
 COPPER IS 840 AMPS. PER CODE, THE AMPACITY OF THESE
 CONDUCTORS SHALL BE EQUAL TO OR GREATER THAN THE
 OVERCURRENT DEVICE. PROVIDE CORRECTION. NEC 240.4(C)
 9. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9,
 110.10
 10. PANEL SCHEDULE PROVIDED SOES NOT SHOW THE GFCI
 PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT THAT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 11. PROVIDE LOAD CALCULATION FOR EACH PANEL AND FOR
 SERVICE TO CONFIRM THAT THE SERVICE IS ADEQUATELY
 SIZED. NEC 220; WPB FBC 107.2.1
 12. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 13. RISER SHOWS A 1/0 COPPER GROUNDING ELECTRODE
 CONDUCTOR. THE GROUNDING ELECTRODE CONDUCTOR SHOULD BE
 SIZED FOR THE TOTAL AREA OF THE SERVICE CONDUCTORS.
 SHOW ALL AVAILABLE GROUNDING ELECTRODES. PROVIDE
 CORRECTION. NEC 250.50, 250.66
 14. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 15. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 16. DESIGN OF ELECTRICAL SYSTEM IS SHOWN AS 1200 AMP.
 THIS IS NOT PERMITTED TO BE DESIGNED BY THE ELECTRICAL
 CONTRACTOR PER FLORIDA STATUTES. PROVIDE PLAN BY A
 DESIGN PROFESSIONAL. FS 471.003(2)(H); WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-31 Cont ID  
Sent By jpearson Date 2018-08-31 Time 13:54 Rev Time 0.00
Received By jpearson Date 2018-08-31 Time 13:54 Sent To  
Notes
2018-08-31 13:53:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PER WPB FBC 107.2.1.3,
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. PROVIDE CORRECTION. FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5 (NOT PROVIDED)
 2. CORRECTED.
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.)
 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; WPB FBC 107.3.5 (NOT PROVIDED.)
 5. WORK DESCRIPTION STATES THAT ALL ELECTRICAL OUTLETS
 AND SWITCHES WILL BE REPLACED. PROVIDE AFCI AND/OR GFCI
 PROTECTION TO MEET CODE. NEC 406.4(D)(3 AND 4) (NOT
 PROVIDED.)
  
 NEW COMMENT:
  
 6. DUE TO ADJUSTMENT OF VALUE, ADDITIONAL FEES FOR PLAN
 REVIEW ARE DUE PRIOR TO THE NEXT PLAN REVIEW CYCLE. WPB
 FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-06 Cont ID  
Sent By jpearson Date 2018-05-06 Time 13:54 Rev Time 0.00
Received By jpearson Date 2018-05-06 Time 13:54 Sent To  
Notes
2018-05-06 13:54:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PER WPB FBC 107.2.1.3,
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. PROVIDE CORRECTION. FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; WPB FBC 107.3.5
 5. WORK DESCRIPTION STATES THAT ALL ELECTRICAL OUTLETS
 AND SWITCHES WILL BE REPLACED. PROVIDE AFCI AND/OR GFCI
 PROTECTION WHERE NEEDED TO MEET CODE. NEC 406.4(D)(3
 AND 4)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-04-09 Cont ID  
Sent By scaldero Date 2019-04-09 Time 11:31 Rev Time 0.00
Received By scaldero Date 2019-04-09 Time 11:30 Sent To  
Notes
2019-04-09 11:31:00PERMIT # 18040097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) ALL WORK AND REQUIREMENTS SHALL COMPLY WITH THE 6TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-11-05 Cont ID  
Sent By scaldero Date 2018-11-05 Time 11:13 Rev Time 0.00
Received By scaldero Date 2018-11-05 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-24 Cont ID  
Sent By scaldero Date 2018-08-24 Time 09:34 Rev Time 0.00
Received By scaldero Date 2018-08-24 Time 09:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By scaldero Date 2018-04-06 Time 12:19 Rev Time 0.00
Received By scaldero Date 2018-04-06 Time 12:12 Sent To  
Notes
2018-04-06 12:19:02PERMIT # 18040097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) ALL WORK AND REQUIREMENTS SHALL COMPLY WITH THE 6TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2019-04-12 Cont ID  
Sent By aborngra Date 2019-04-12 Time 10:09 Rev Time 0.00
Received By aborngra Date 2019-04-12 Time 10:08 Sent To  
Notes
2019-04-12 10:09:09THE PERMIT HAS APPROVED THE PERMIT WITH THE FOLLOWING
 CONDITIONS:
  
 1. ALL REPLACEMENT WINDOWS SHALL HAVE CLEAR GLASS OR
 LOW-E GLASS.
 2. ALL REPLACEMENT WINDOWS SHALL MATCH THE EXISTING
 WINDOW CONFIGURATION.
 3. ALL REPLACEMENT WINDOWS SHALL FIT THE ORIGINAL
 WINDOW FRAME.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 10:58 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 10:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By fmittner Date 2018-10-26 Time 08:12 Rev Time 0.00
Received By fmittner Date 2018-10-26 Time 08:12 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-04-18 Cont ID  
Sent By fmittner Date 2018-04-18 Time 14:54 Rev Time 0.00
Received By fmittner Date 2018-04-18 Time 14:54 Sent To  
Notes
2018-04-18 14:57:25WINDOWS APPROVED TO MATCH EXISITNG 1/1 SINGLE HUNG
 WHITE OR BROZE FRAMES.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2019-11-12 Time   Rev Time 0.00
Received By cpuell Date 2019-11-07 Time 10:18 Sent To  
Notes
2019-11-09 10:19:47JPEARSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2019-09-17 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-13 Time 14:35 Sent To  
Notes
2019-09-16 14:36:09RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-06-04 Cont ID  
Sent By hmoser Date 2019-06-04 Time 13:59 Rev Time 0.00
Received By hmoser Date 2019-05-30 Time 13:49 Sent To  
Notes
2019-05-31 13:50:01RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-10 Cont ID  
Sent By jgomez Date 2019-05-10 Time 18:59 Rev Time 0.00
Received By jgomez Date 2019-04-03 Time 16:18 Sent To I
Notes
2019-04-03 16:18:12C25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-18 Cont ID  
Sent By cpuell Date 2018-12-18 Time 11:29 Rev Time 0.00
Received By cpuell Date 2018-10-30 Time 11:04 Sent To  
Notes
2018-11-01 11:04:22C04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 07:03 Rev Time 0.00
Received By shill Date 2018-08-17 Time 15:07 Sent To  
Notes
2018-09-11 15:00:24C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-05 Cont ID  
Sent By jgomez Date 2018-06-05 Time 10:23 Rev Time 0.00
Received By jgomez Date 2018-04-03 Time 10:53 Sent To  
Notes
2018-06-08 10:24:23LAST REVIEW DONE ON 06/05/18. HISTORIC.
2018-04-05 10:54:06C12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2019-11-21 Cont ID  
Sent By jgomez Date 2019-11-21 Time 09:01 Rev Time 0.00
Received By jgomez Date 2019-11-21 Time 08:56 Sent To  
Notes
2019-11-21 09:02:11NO FEES DUE.COUNTY STAMPED PLANS ON 11/19/19. NO
 MU-NUMBER. SEE CITY COPY. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-12-10 Cont ID  
Sent By jgomez Date 2018-12-10 Time 11:57 Rev Time 0.00
Received By jgomez Date 2018-12-10 Time 11:57 Sent To  
Notes
2018-12-10 11:57:501- IMPACT FEES
 UPON APPROVAL OF PLANS ONE SET OF PLANS SHALL BE SIGNED
 OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN IMPACT
 FEE REVIEW BASED ON THE NUMBER OF UNITS. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH CAN BE
 ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY IMPACT
 FEES AT (561) 233-5025.
  
 NOTE: ACCORDING TO CITY RECORDS PERMIT #98100735 AND
 PROPERTY APPRAISER THERE ARE 12 UNITS TOTAL NOT 13.
 PLANS TO SHOW THAT EXISTING OFFICE IS CHANGED TO
 APARTMENT/STUDIO. NEED TO TAKE PLANS TO PALM BEACH
 COUNTY FOR IMPACT FEES ASSESSMENT.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-09-18 Cont ID  
Sent By jgomez Date 2018-09-18 Time 17:17 Rev Time 0.00
Received By jgomez Date 2018-09-18 Time 17:17 Sent To  
Notes
2018-09-18 17:17:211- IMPACT FEES
 COUNTY. UPON APPROVAL, ONE SET OF PLANS SHALL BE SIGNED
 OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN IMPACT
 FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP AND A
 COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE CITY
 BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By jgomez Date 2018-05-17 Time 10:31 Rev Time 0.00
Received By jgomez Date 2018-05-17 Time 07:34 Sent To  
Notes
2018-05-17 10:31:541- IMPACT FEES
 COUNTY. UPON APPROVAL, ONE SET OF PLANS SHALL BE SIGNED
 OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN IMPACT
 FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP AND A
 COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE CITY
 BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT BEFORE A
 PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-06-04 Cont ID  
Sent By hmoser Date 2019-06-04 Time 13:59 Rev Time 0.00
Received By hmoser Date 2019-06-04 Time 13:09 Sent To I
Notes
2019-06-04 13:47:52PASS PROVISO
 REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 INCLUDING DOORS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-04-30 Cont ID  
Sent By hmoser Date 2019-04-30 Time 14:11 Rev Time 0.00
Received By hmoser Date 2019-04-30 Time 13:55 Sent To I
Notes
2019-04-30 14:11:03PLAN DENIED
 MECHANICAL PLANS NOT LEGIBLE
 REFER TO SECTION 107.2.1 CONSTRUCTION DOCUMENTS SHALL
 BE
 OF SUFFICIENT CLARITY. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-12-06 Cont ID  
Sent By hmoser Date 2018-12-06 Time 14:10 Rev Time 0.00
Received By hmoser Date 2018-12-06 Time 11:07 Sent To  
Notes
2018-12-06 14:10:25PLAN DENIED
 1) 1ST FLOOR HALL AND LAUNDRY ROOM MISSING FIRE DAMPERS
 PER SECTION 602.2.1 FBC (M) 2017 FIRE PARTITIONS
 2) 2ND FLOOR HALL AND STORAGE ROOM MISSING FIRE DAMPERS
 PER SECTION 602.2.1 FIRE PARTITIONS FBC (M) 2017
 3) SHOW LOCATION OF DRYER EXHAUST TERMINATION. SECTION
 507 CLOTHES DRYER EXHAUST. FBC (M) 2017
 4) JUST A REMINDER NO COMBUSTIBLES IN RETURN AIR PLENUM
 INCLUDING DOORS. SECTION 602.2.1 MATERIALS IN PLENUM'S.
 FBC (M) 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-12 Cont ID  
Sent By hmoser Date 2018-10-12 Time 13:07 Rev Time 0.00
Received By hmoser Date 2018-10-12 Time 11:12 Sent To  
Notes
2018-10-12 13:07:43PLAN DENIED
 PLAN MUST BE SIGNED AND SEALED BY ARCHITECT OR
 ENGINEER. PER SECTION 407.003 FLORIDA STATUTES.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By hmoser Date 2018-05-09 Time 10:13 Rev Time 0.00
Received By hmoser Date 2018-05-08 Time 14:36 Sent To  
Notes
2018-05-09 10:13:28PLAN DENIED
 1) PROVIDE DUCT SIZE, CFM AND GRILL SIZE ON PLANS.
 2017 FBC (M)
 2) REFER TO SECTION 601.6 BALANCED RETURN AIR
 2017 FBC (M)
 3) REFER TO SECTION 602.2.1 MATERIALS WITH IN
 PLENUM'S. ( NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM'S INCLUDING DOORS 2017 FBC (M)
 4) PROVIDE EQUIPMENT SCHEDULE ON PLANS
 107.3.5.1.4 MINIMUM PLAN REVIEW ( MECHANICAL )
 5) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 6) PROVIDE ENERGY CALCULATIONS WITH THE PLAN
 SECTION 603.2 DUCT SIZING 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-04-15 Cont ID  
Sent By tklarge Date 2019-04-15 Time 14:42 Rev Time 0.00
Received By tklarge Date 2019-04-15 Time 10:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-12-17 Cont ID  
Sent By gjohnson Date 2018-12-17 Time 17:20 Rev Time 0.00
Received By gjohnson Date 2018-12-17 Time 17:20 Sent To  
Notes
2018-12-17 17:43:551ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING SHEET WITH DETAILED SCOPE OF WORK
 ESTIMATE FROM M COSTA PLUMBING STATES THE REPLACEMENT
 OF SANITARY STACKS AND REPIPING WATER LINE PROVIDE
 ISOMETRIC DRAWINGS FOR ALL PLUMBING BEING REPLACED. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. PROVIDE UPDATED SPEC FOR THE WATER HEATERS THE ONES
 THAT WERE PROVIDED WERE FROM 2012 AND DON'T MEET THE
 CURRENT ENERGY CODE SHALL COMPLY WITH FBC ENERGY TABLE
 C404.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-12 Cont ID  
Sent By gjohnson Date 2018-09-12 Time 16:16 Rev Time 0.00
Received By gjohnson Date 2018-09-12 Time 07:01 Sent To  
Notes
2018-09-12 16:32:592ND REVIEW: FBC 2017 6TH EDITION
  
 PRIOR TO RESUBMITTING IT WOULD BE WISE TO SET UP A
 MEETING WITH THE PLAN REVIEWERS
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. COMPLY WITH BUILDINGS COMMENTS.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 HEATERS. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE BREAKER SIZE FOR WATER HEATER SHALL COMPLY
 WITH MANUFACTURE INSTALLATION GUIDE. PER WPB AMEND TO
 FBC 107.2.1
  
 NEW COMMENTS :
  
 1. NO RESPONSE LETTER WAS PROVIDED FOR REREVIEW
 ALTHOUGH THIS IS NOT REQUIRED IT WILL HELP EXPEDITE THE
 REVIEW PROCESS YOUR SUBMITTAL PACKAGE IS CONFUSING
 PLEASE MARK VOID OR REMOVE ALL OLD OR PREVIOUSLY
 REVIEWED DENIED PLANS. PER WPB AMEND TO FBC 107.2.1
  
 2. THE PLUMBING APPLICATION STATES THAT AN EXISTING
 ROUGH WILL BE FINISHED THE PLAN ONLY INDICATES THE
 REPLACEMENT OF EXISTING FIXTURES PLEASE PROVIDE A
 DETAILED SCOPE OF PLUMBING WORK TO BE DONE ADDRESSING
 EACH TYPE OF FIXTURE SUCH AS, BATHROOM, KITCHEN, WATER
 HEATER AND LAUNDRY. IF ANY NEW PIPING IS BEING DONE
 PROVIDE A SANITARY AND WATER ISOMETRIC DRAWING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By gjohnson Date 2018-05-17 Time 12:58 Rev Time 0.00
Received By gjohnson Date 2018-05-17 Time 11:41 Sent To  
Notes
2018-05-17 13:18:271ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. COMPLY WITH BUILDINGS COMMENTS.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 HEATERS. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE BREAKER SIZE FOR WATER HEATER SHALL COMPLY
 WITH MANUFACTURE INSTALLATION GUIDE. PER WPB AMEND TO
 FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2019-05-10 Cont ID  
Sent By jgomez Date 2019-05-10 Time 19:03 Rev Time 0.00
Received By jgomez Date 2019-05-10 Time 19:03 Sent To  
Notes
2019-05-10 19:04:21NO ROOFING WORK SHOWN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-12-10 Cont ID  
Sent By jgomez Date 2018-12-10 Time 12:00 Rev Time 0.00
Received By jgomez Date 2018-12-10 Time 11:59 Sent To  
Notes
2018-12-10 12:00:16CONTRACTOR TO ADVICE IF DOING ROOFING WORK UNDER THIS
 SUBMITTAL OR IF ROOFING CONTRACTOR IS APPLYING FOR
 SEPARATE PERMIT.
  
 NO ROOFING INFORMATION WAS SUBMITTED. CONTRACTOR MAY
 PROVIDE COMPLETE INFORMATION OR PROVIDE COMPLETE
 INFORMATION UNDER AS SEPARATE PERMIT.
  
 NOTE: ROOF WORK IS ALWAYS DONE UNDER A ROOFING
 SUB-PERMIT OR SEPARATE ROOFING PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By jgomez Date 2018-09-18 Time 17:17 Rev Time 0.00
Received By jgomez Date 2018-09-18 Time 17:17 Sent To  
Notes
2018-09-18 17:20:16NO ROOFING INFORMATION WAS SUBMITTED. CONTRACTOR MAY
 PROVIDE COMPLETE INFORMATION OR PROVIDE COMPLETE
 INFORMATION UNDER AS SEPARATE PERMIT.
 NOTE: ROOF WORK IS ALWAYS DONE UNDER A ROOFING
 SUB-PERMIT OR SEPARATE ROOFING PERMIT.

Review Stop Z ZONING
Rev No 4 Status P Date 2019-04-12 Cont ID  
Sent By aborngra Date 2019-04-12 Time 10:08 Rev Time 0.00
Received By aborngra Date 2019-04-12 Time 10:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 10:57 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 10:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By fmittner Date 2018-10-26 Time 08:12 Rev Time 0.00
Received By fmittner Date 2018-10-26 Time 08:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By fmittner Date 2018-06-05 Time 10:35 Rev Time 0.00
Received By fmittner Date 2018-06-05 Time 10:35 Sent To  
Notes
2018-06-05 10:36:19GREEN CARD ONLY SHOWS 10 UNITS.
2018-05-17 10:30:50NOTE: ACCORDING TO CITY RECORDS PERMIT #98100735 AND
 PROPERTY APPRAISER THERE ARE 12 UNITS TOTAL NOT 13. JG.


Account Summary | Usage Policy | Privacy Policy