Plan Review Details - Permit 18040023
Plan Review Stops For Permit 18040023
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By jwitmer Date 2018-04-06 Time 11:09 Rev Time 0.00
Received By jwitmer Date 2018-04-05 Time 15:42 Sent To  
Notes
2018-04-06 11:06:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18040023
 ADD: 1771 PALM BEACH LAKES BLVD. SUITE: W305
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-373-3902
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. APRIL 06/ 2018
 ACTION: BUILDING PROVISO
  
 1A) 2017 FBC-ACCESSIBILITY CODE SECTION 903.4 BACK
 SUPPORT. THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR
 SHALL BE AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A
 POINT 2 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE
 TO A POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 1B) 903.5 HEIGHT. THE TOP OF THE BENCH SEAT SURFACE
 SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES (485
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1C) 903.6 STRUCTURAL STRENGTH. ALLOWABLE STRESSES SHALL
 NOT BE EXCEEDED FOR MATERIALS USED WHEN A VERTICAL OR
 HORIZONTAL FORCE OF 250 POUNDS IS APPLIED AT ANY POINT
 ON THE SEAT, FASTENER, MOUNTING DEVICE, OR SUPPORTING
 STRUCTURE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-08 Cont ID  
Sent By jpearson Date 2018-04-08 Time 11:30 Rev Time 0.00
Received By jpearson Date 2018-04-08 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By scaldero Date 2018-04-06 Time 12:56 Rev Time 0.00
Received By scaldero Date 2018-04-06 Time 12:47 Sent To  
Notes
2018-04-06 12:56:54PERMIT # 18040023
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])AND APPROVED
 BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH
 DIXIE HIGHWAY.
  
 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 3) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 4) SEPERATES PERMITS REQUIRED FOR ALL WORK DONE RELATED
 TO THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 5) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-09 Cont ID  
Sent By eschneid Date 2018-04-09 Time 15:49 Rev Time 0.00
Received By eschneid Date 2018-04-02 Time 14:18 Sent To  
Notes
2018-04-03 14:18:21B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-04-06 Cont ID  
Sent By jwitmer Date 2018-04-06 Time 11:09 Rev Time 0.00
Received By jwitmer Date 2018-04-05 Time 15:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By hmoser Date 2018-04-09 Time 11:05 Rev Time 0.00
Received By hmoser Date 2018-04-09 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 11:30 Rev Time 0.00
Received By gjohnson Date 2018-04-09 Time 11:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By ES Date 2018-04-09 Time 15:49 Rev Time 0.25
Received By eschneid Date 2018-04-09 Time 15:27 Sent To PC
Notes
***NONE***