Plan Review Details - Permit 18040013
Plan Review Stops For Permit 18040013
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-05 Cont ID  
Sent By shill Date 2018-05-05 Time 15:44 Rev Time 0.00
Received By shill Date 2018-05-05 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-07 Cont ID  
Sent By cthroop Date 2018-04-07 Time 10:50 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 15:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-03 Cont ID  
Sent By jpearson Date 2018-05-03 Time 15:48 Rev Time 0.00
Received By jpearson Date 2018-05-03 Time 13:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-08 Cont ID  
Sent By jpearson Date 2018-04-08 Time 09:51 Rev Time 0.00
Received By jpearson Date 2018-04-08 Time 09:51 Sent To  
Notes
2018-04-08 09:51:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW LOCATION OF EXISTING FPL METER ON PLAN.
 GENERALLY SPEAKING, CONDUCTORS ARE NOT PERMITTED TO
 EXTEND INTO THE DWELLING WITHOUT OVERCURRENT
 PROTECTION, UNLESS IT IS A BACK TO BACK SITUATION OR
 THE CONDUCTOR LENGTH IS MINIMAL. PROVIDE CLARIFICATION
 AND/OR CORRECTION TO INCLUDE A MAIN DISCONNECT ON THE
 EXTERIOR OF THE DWELLING IF NEEDED. NEC 230.70; FBC RE
 E3601.6; FBC 107.2.1
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE LOAD CALCULATION PROVIDED SHOWS THE FIRST
 10,000 VA AS A LOAD OF ONLY 3846.4, INSTEAD OF THE FULL
 10,000 THAT IT IS SUPPOSED TO BE. PROVIDE CORRECTION.
 NEC 220; FBC RE E3602.2
 6. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED.
 PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 8. THE AFCI NOTE PROVIDED DOES NOT INCLUDE ALL AREAS
 REQUIRED BY CODE TO HAVE THIS PROTECTION. PER CODE:
 ?ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED.?
 PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16
 9. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN
 PENINSULA. NEC 210.8, 210.52(C)(3); FBC RE E3901.4.3
 10. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
 11. MASTER CLOSET APPEARS TO HAVE A STANDARD RECESS
 LIGHT. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 12. PROVIDE A LUMINAIRE CONTROLLED BY A SWITCH LOCATED
 AT THE REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE
 OUTLET INSTALLED AT OR NEAR THE APPLIANCE LOCATION FOR
 THE AHU IN ATTIC. FBC RE M1305.1.3.1
 13. PANEL SCHEDULE SHOWS # 6 WIRE TO BOTH AHU?S ON A 60
 AMP BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN
 RESIDENTIAL WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE
 CORRECTION. NEC 334.80; FBC RE E3705.4.4
 14. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 15. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-05-07 Cont ID  
Sent By thunt Date 2018-05-07 Time 15:25 Rev Time 0.00
Received By thunt Date 2018-05-07 Time 15:25 Sent To  
Notes
2018-05-07 15:25:31ALL GAS IS EXISTING AND NO GAS WORK IS TO BE DONE UNDER
 THIS PERMIT

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-04-04 Cont ID  
Sent By thunt Date 2018-04-04 Time 14:17 Rev Time 0.00
Received By thunt Date 2018-04-04 Time 14:17 Sent To  
Notes
2018-04-04 14:23:2104/04/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
  
 1) SHOW PIPE SIZE ON OUTLET OF GAS METER. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2
  
 2) CITY RECORDS SHOW EXISTING GAS SYSTEM ( POOL HEATER)
 LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21). THE PLANS INDICATE
 AN EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE STOVE TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS
 CODE SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC.
 G2404.3. GAS APPLIANCES SHALL BE LISTED AND LABELED.
 THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION.
 FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 4) ) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED
 GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-05-03 Cont ID  
Sent By fmittner Date 2018-05-03 Time 11:44 Rev Time 0.00
Received By fmittner Date 2018-05-03 Time 11:44 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By fmittner Date 2018-04-06 Time 14:57 Rev Time 0.00
Received By fmittner Date 2018-04-06 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-07 Cont ID  
Sent By thunt Date 2018-05-07 Time 15:25 Rev Time 0.00
Received By thunt Date 2018-04-24 Time 15:11 Sent To  
Notes
2018-04-27 15:11:28R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-16 Cont ID  
Sent By hmoser Date 2018-04-16 Time 13:47 Rev Time 0.00
Received By hmoser Date 2018-04-02 Time 11:02 Sent To  
Notes
2018-04-03 11:02:11R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-30 Cont ID  
Sent By cmontell Date 2018-04-30 Time 14:12 Rev Time 0.00
Received By cmontell Date 2018-04-30 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-16 Cont ID  
Sent By hmoser Date 2018-04-16 Time 13:47 Rev Time 0.00
Received By hmoser Date 2018-04-16 Time 11:29 Sent To I
Notes
2018-04-16 13:47:03PLAN DENIED
 REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE
 SIZING. 2017 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-07 Cont ID  
Sent By thunt Date 2018-05-07 Time 15:25 Rev Time 0.00
Received By thunt Date 2018-05-07 Time 15:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-04 Cont ID  
Sent By thunt Date 2018-04-04 Time 14:25 Rev Time 0.00
Received By thunt Date 2018-04-04 Time 14:25 Sent To  
Notes
2018-04-04 14:29:0404/04/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) WASHING MACHING TRAP IS NOT VENTED. PER FBC R
 P3102.2.1 EACH TRAP & TRAPPED FIXTURE IS REQUIRED TO BE
 VENTED
  
 2) PLUMBING NOTES LIST ALL HOT WATER PIPING TO BE
 INSULATED. PLEASE CALL OUT WALL THICKNESS OR MIN
 R-VALUE FBC 107.2.1
  
 3) PLEASE SHOW PLANS AS TO COMPLY WITH THE FBC 2017 6TH
 ED. FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER