2018-04-08 09:51:32 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SHOW LOCATION OF EXISTING FPL METER ON PLAN. |
| GENERALLY SPEAKING, CONDUCTORS ARE NOT PERMITTED TO |
| EXTEND INTO THE DWELLING WITHOUT OVERCURRENT |
| PROTECTION, UNLESS IT IS A BACK TO BACK SITUATION OR |
| THE CONDUCTOR LENGTH IS MINIMAL. PROVIDE CLARIFICATION |
| AND/OR CORRECTION TO INCLUDE A MAIN DISCONNECT ON THE |
| EXTERIOR OF THE DWELLING IF NEEDED. NEC 230.70; FBC RE |
| E3601.6; FBC 107.2.1 |
| 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9 |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. THE LOAD CALCULATION PROVIDED SHOWS THE FIRST |
| 10,000 VA AS A LOAD OF ONLY 3846.4, INSTEAD OF THE FULL |
| 10,000 THAT IT IS SUPPOSED TO BE. PROVIDE CORRECTION. |
| NEC 220; FBC RE E3602.2 |
| 6. BREAKER FOR POOL PUMP REQUIRED TO BE GFCI PROTECTED. |
| PROVIDE CORRECTION. NEC 680.21(C); FBC RE E4203.1.3 |
| 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 8. THE AFCI NOTE PROVIDED DOES NOT INCLUDE ALL AREAS |
| REQUIRED BY CODE TO HAVE THIS PROTECTION. PER CODE: |
| ?ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED.? |
| PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16 |
| 9. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN |
| PENINSULA. NEC 210.8, 210.52(C)(3); FBC RE E3901.4.3 |
| 10. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| FBC RE E3903.3 |
| 11. MASTER CLOSET APPEARS TO HAVE A STANDARD RECESS |
| LIGHT. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY |
| ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE |
| CORRECTION. NEC 410.16; FBC RE E4003.12 |
| 12. PROVIDE A LUMINAIRE CONTROLLED BY A SWITCH LOCATED |
| AT THE REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE |
| OUTLET INSTALLED AT OR NEAR THE APPLIANCE LOCATION FOR |
| THE AHU IN ATTIC. FBC RE M1305.1.3.1 |
| 13. PANEL SCHEDULE SHOWS # 6 WIRE TO BOTH AHU?S ON A 60 |
| AMP BREAKER. #6 ROMEX WIRE, WHICH IS TYPICAL IN |
| RESIDENTIAL WIRING, IS NOT RATED FOR 60 AMPS. PROVIDE |
| CORRECTION. NEC 334.80; FBC RE E3705.4.4 |
| 14. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| 15. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |