Plan Review Details - Permit 18031402
Plan Review Stops For Permit 18031402 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2019-03-06 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-03-06 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-03-06 |
Time |
09:02 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-01-28 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-01-28 |
Time |
10:54 |
Sent To |
Z |
|
Notes |
2019-01-28 11:14:44 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | JOSEAN A. DUPREY | | BUILDING PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6716 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. A DOOR PRODUCT SUBMITTAL WAS PROVIDED. HOWEVER THIS | | IS BASE ON THE 2014 FBC. PLEASE PROVIDE A NEW PRODUCT | | APPROVAL PER CURRENT BUILDING CODE, ALSO PROVIDE THE | | FRONT PAGE OF THE PRODUCT APPROVAL, WE WANT TO KNOW IF | | IS IMPACT RESISTANT AND WICH PRODUCT SPECIFIC IS | | SELECTED. FBC 107 | | | | 2. PROVIDE STRUCTURAL DETAILA FOR THE NEW SIDEWALK TO | | THE ENTRANCE. FBC 107 | | | | 3. THE NEW DOOR OPENING STRUCTURAL DETAIL DO NOT | | SPECIFY HOW THE ANGLE WILL BE INSTALLED (E.I. CLIPS, IN | | THE WALL?, AT THE BOTTOL OF THE HEADER?) ALSO NO REBAR | | WAS SPECIFIED FOR THIS DETAIL. FBC 107 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-11-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-11-07 |
Time |
12:23 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-11-07 |
Time |
10:00 |
Sent To |
HIST |
|
Notes |
2018-11-07 12:17:50 | 2017 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 18031402 | | ADD: 519 NORTHWOOD AVE. SUITE 525 | | CONT: CALIBER CONTRACTOR | | TEL: 561-222-1906 | | E-MAIL: [email protected] | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 2ND REVIEW | | DATE: WED. NOV. 07/2018 | | ACTION: DENIED | | NOTICE!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY. DO NOT TAKE THE OLD SHEETS AWAY, WE USE | | THEM TO REFER TO THE CHANGES MADE. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET | | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) | | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | | | 1) THE COVERSHEET A1: COMPLIED. BUSINESS OCCUPANCY | | DECLARED, NO OCCUPANCY SEPARATION REQUIRED BETWEEN | | BUSINESS AND F1 OCCUPANCY. Q THE COVERSHEET A1 UNDER | | THE HEADING PROJECT DESCRIPTION LIST THIS AS A LEVEL LL | | ALTERATION. PLEASE NOTE THE LAST KNOWN USE (BUSINESS | | TAX) WAS SMYRNA MARKET OR A RETAIL OCCUPANCY. THIS | | WOULD MAKE THE USE A CHANGE OF OCCUPANCY AND UNDER THE | | 2017 FBC-EXISTING BUILDING CODE CHAPTER 10 CHANGE OF | | OCCUPANCY. SEE SECTION 1001.2.2.1 OF THE EXISTING | | BUILDING CODE. PARTIAL CHANGE OF OCCUPANCY. WHERE THE | | OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN | | EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY. | | 2A) 2ND REQUEST. SHEET A-2 SHOWS A NEW DOOR OPENING TO | | THE EXTERIOR, A NEW 6068 DOUBLE DOORS. PLEASE PROVIDE A | | SITE PLAN FOR WHERE THE 6068 DOORS ARE LEADING TOO. IF | | THERE IS TO BE SEASONAL SEATING PLEASE PROVIDE ON THE | | SITE PLAN THE ADDITIONAL SEATING. 2017 FBC-B 302.1. A | | ROOM OR SPACE THAT IS INTENDED TO BE OCCUPIED AT | | DIFFERENT TIMES FOR DIFFERENT PURPOSES SHALL COMPLY | | WITH ALL OF THE REQUIREMENTS THAT ARE APPLICABLE TO | | EACH OF THE PURPOSES FOR WHICH THE ROOM OR SPACE WILL | | BE OCCUPIED. | | 2B) NEW COMMENT. SHEET A2 HAS A NEW MASONRY OPENING | | (WINDOW), PLEASE CORRECT FOR A NEW DOORWAY. 107.2.1.3 | | ADDITIONAL INFORMATION REQUIRED. | | | | 3) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH SECTION | | 202.4.1. OF THE 2017 FBC-ACCESSIBILITY CODE SECTION | | 202.4.1 DISPROPORTIONATE COST. PROVIDE AN ITEMIZED LIST | | WHERE 0.20 % OF THE PERMIT VALUE IS GOING TO ACCESSIBLE | | UPGRADES OR UP TO $5,000.00 IN VALUE MEETING THE EVENT | | OF DISPROPORTIONALITY UNDER 202.4.2. | | FBC-ACCESSIBILITY CODE SECTION 202.4.1 DISPROPORTIONATE | | COST. | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | 3A)2ND REQUEST. SHEETS A3 & A4 MISSING FROM THIS | | REVIEW. SHEET A3 & A4 IDENTIFY THE FRONT DOOR AS DOOR | | 101. PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE | | FRONT ENTRY. GOOGLE EARTH STREET VIEW SHOWS A COLUMN AT | | THE FRONT ENTRY AS WELL AS A HORIZONTAL BAR | | APPROXIMATELY 36 INCHES ABOVE GRADE. 107.2.1.3 | | ADDITIONAL INFORMATION IS REQUIRED. | | | | 2017 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY. | | EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR | | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE | | PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. | | | | ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. MINIMUM | | MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY | | WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE | | FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE | | OR HINGE SIDE CLEARANCE. THE FRONT DOOR APPEARS TO HAVE | | LESS THAN THE REQUIRED 18 INCHES FOR MANEUVERING | | CLEARANCES. | | | | 3B) 2ND REQUEST. THERE IS ALSO A RAMP; PLEASE PROVIDE | | THE SLOPE IN INCHES RISE PER FEET IN LENGTH. 2017 | | ACCESSIBILITY CODE. 405.2 SLOPE. RAMP RUNS SHALL HAVE A | | RUNNING SLOPE NOT STEEPER THAN 1:12. EXCEPTION: IN | | EXISTING SITES, BUILDINGS, AND FACILITIES, RAMPS SHALL | | BE PERMITTED TO HAVE RUNNING SLOPES STEEPER THAN 1:12 | | COMPLYING WITH TABLE 405.2 WHERE SUCH SLOPES ARE | | NECESSARY DUE TO SPACE LIMITATIONS. | | | | 3C) 2ND REQUEST. THE EXISTING RESTROOM DOES NOT ALSO | | MEET THE REQUIREMENTS FOR A SINGLE USER TOILET ROOM | | UNDER 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE | | TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL | | COMPLY WITH 603. EXCEPTIONS: | | 1.IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE TO | | COMPLY WITH 603, ALTERING EXISTING TOILET ROOMS SHALL | | NOT BE REQUIRED WHERE A SINGLE UNISEX TOILET ROOM | | COMPLYING WITH 213.2.1 IS PROVIDED AND LOCATED IN THE | | SAME AREA AND ON THE SAME FLOOR AS EXISTING IN | | ACCESSIBLE TOILET OR BATHING ROOMS. | | | | 4)2ND REQUEST. MISSING SHEETS A3 & A4. SHEET A3 & A4. | | NEW WORK NOT COVERED UNDER THE 20% DISPROPORTIONATE | | COST. PLEASE SHOW COMPLIANCE WITH: | | | | 4A) 2ND REQUEST. MISSING SHEETS A3 & A4. 226.1 WHERE | | DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF | | FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES | | AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY | | WITH 902. | | | | 4B) 2ND REQUEST. MISSING SHEETS A3 & A4. 226.2 | | DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED | | TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE | | SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK | | SURFACES. | | | | 4C) 2ND REQUEST. MISSING SHEETS A3 & A4. 206.2.5 | | 206.2.5 RESTAURANTS AND CAFETERIAS. IN RESTAURANTS AND | | CAFETERIAS, AN ACCESSIBLE ROUTE SHALL BE PROVIDED TO | | ALL DINING AREAS, INCLUDING RAISED OR SUNKEN DINING | | AREAS, AND OUTDOOR DINING AREAS (SEASONAL SEATING). | | | | 4D) 2ND REQUEST. 902.1 .DINING SURFACES SHALL COMPLY | | WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING | | SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES, | | LUNCH COUNTERS, AND BOOTHS. | | | | 4D)(1) 2ND REQUEST. MISSING SHEETS A3 & A4. 902.2 CLEAR | | FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING | | WITH 305 POSITIONED FOR A FORWARD APPROACH SHALL BE | | PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306 | | SHALL BE PROVIDED. | | | | 4D)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING | | SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM | | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | 5) 2ND REQUEST. SHEETS A3 & A4 ARE MISSING. SHEET A4 | | THERE IS A DISCREPANCY IN THE WIND SPEEDS; YES THE VULT | | WIND SPEED FOR THIS WIND ZONE FOR A BUILDING CATEGORY | | II STRUCTURE IS 170 VULT. THE PLANS GO ONTO INDICATE | | THE VASD IS 132 WHICH IS ALSO CORRECT. THERE IS ALSO A | | STATEMENT THE CURRENT NOA?S ARE TOO BE BASED ON 146 | | VASD. PLEASE NOTE THE 146 VASD WIND ZONES ARE FOR DADE | | AND BROWARD ONLY. IF THE DESIGNER WISHES TO DESIGN TO | | THE HIGHER WIND SPEED THEN ALSO UP THE VULT WIND SPEED | | TO CORRELATE WITH THE 146 VASD. UNTIL THIS IS KNOWN THE | | PRESSURES GIVEN CANNOT BE DETERMINED FOR CODE | | COMPLIANCE. PLEASE ALSO NOTE THE PRESSURES GIVEN NOTE | | MAX. PSF, THIS IS ASSUMED TO BE 10 SQUARE FEET. | | DISCREPANCY IN PLANS. 107.2.1.3. ALL PRESSURES NEED TO | | BE EXPRESSED IN VASD SINCE THE PRODUCT APPROVALS ARE IN | | VASD. | | | | 6A) 2ND REQUEST. 2017 FBC-B 1609.1.2 PROTECTION OF | | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA | | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE | | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY | | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE | | PRODUCT APPROVALS: | | (31)(A) EXTERIOR DOORS | | (G) PRE-ENGINEERED A/C STANDS | | | | 6B)2ND REQUEST. PLEASE IDENTIFY ON THE PRODUCT APPROVAL | | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE | | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS | | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & | | HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF | | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, | | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING | | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND | | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED | | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING | | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE | | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN | | THE TESTS. | | | | 6C)2ND REQUEST. W. P. B. 107.3.4.1 PRODUCT APPROVALS. | | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE | | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-04-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-04-05 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-04-04 |
Time |
16:46 |
Sent To |
|
|
Notes |
2018-04-05 10:03:08 | 2017 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 18031402 | | ADD: 519 NORTHWOOD AVE. SUITE 525 | | CONT: CALIBER CONTRACTOR | | TEL: 561-222-1906 | | E-MAIL: [email protected] | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: THUR. APRIL 05/2018 | | ACTION: DENIED | | | | 1) THE COVERSHEET A1: | | | | 1A) THE COVERSHEET A1 UNDER THE HEADING PROJECT | | DESCRIPTION LIST THIS AS A LEVEL LL ALTERATION. PLEASE | | NOTE THE LAST KNOWN USE (BUSINESS TAX) WAS SMYRNA | | MARKET OR A RETAIL OCCUPANCY. THIS WOULD MAKE THE USE A | | CHANGE OF OCCUPANCY AND UNDER THE 2017 FBC-EXISTING | | BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY. SEE | | SECTION 1001.2.2.1 OF THE EXISTING BUILDING CODE. | | PARTIAL CHANGE OF OCCUPANCY. WHERE THE OCCUPANCY | | CLASSIFICATION OR GROUP OF A PORTION OF AN EXISTING | | BUILDING IS CHANGED, SECTION 1012 SHALL APPLY. | | | | 1B) IT WOULD APPEAR THAT THE MAIN OCCUPANCY IS NOT A | | BUSINESS OCCUPANCY BUT A F-1 OCCUPANCY. PLEASE REFER TO | | THE 2017 FBC-B 508.2.3 OF THE EXISTING BUILDING CODE. | | YOU MUST TAKE THE BUILDING AREA PER FLOOR, NOT THE | | TENANT SPACE. | | 508.2.3 ALLOWABLE BUILDING AREA. THE ALLOWABLE AREA OF | | THE BUILDING SHALL BE BASED ON THE APPLICABLE | | PROVISIONS OF SECTION 506 FOR THE MAIN OCCUPANCY OF THE | | BUILDING. AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT | | OCCUPY MORE THAN 10 PERCENT OF THE FLOOR AREA OF THE | | STORY IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED | | THE TABULAR VALUES FOR NONSPRINKLERED BUILDINGS IN | | TABLE 506.2 FOR EACH SUCH ACCESSORY OCCUPANCY. | | | | 1C) SINCE THE BUSINESS PORTION OF THE TENANT SPACE IS | | ACCESSORY TO THE F-1 OCCUPANCY THERE IS NO NEED OF AN | | OCCUPANCY SEPARATION. 2017 FBC-B 508.2.4 SEPARATION OF | | OCCUPANCIES. NO SEPARATION IS REQUIRED BETWEEN | | ACCESSORY OCCUPANCIES AND THE MAIN OCCUPANCY. | | | | 1D) COMMON PATH OF TRAVEL FOR THE F-1 OCCUPANCY IS | | STILL 75 FEET, MUST CHANGE THE OCCUPANCY TYPE. 2017 | | FBC-B TABLE 1006.2.1. | | | | 1E) THE A-1 SHEET UNDER FIRE PROTECTION LIST THIS | | BUILDING AS NOT-SPRINKLERED, WHEREAS SHEET A5 TABLE | | 803.9 IS TAKING CREDIT FOR A FIRE SPRINKLERED BUILDING. | | DISCREPANCY IN PLANS, PLEASE CORRECT. 107.2.1.3. | | ADDITIONAL INFORMATION IS REQUIRED. | | | | 2) SHEET A-3 SHOWS A NEW DOOR OPENING TO THE EXTERIOR, | | A NEW 6068 DOUBLE DOORS. PLEASE PROVIDE A SITE PLAN FOR | | WHERE THE 6068 DOORS ARE LEADING TOO. IF THERE IS TO BE | | SEASONAL SEATING PLEASE PROVIDE ON THE SITE PLAN THE | | ADDITIONAL SEATING. 2017 FBC-B 302.1. A ROOM OR SPACE | | THAT IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR | | DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE | | REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE | | PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED. | | | | 3) PLEASE SHOW COMPLIANCE WITH SECTION 202.4.1. OF THE | | 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1 | | DISPROPORTIONATE COST. PROVIDE AN ITEMIZED LIST WHERE | | 0.20 % OF THE PERMIT VALUE IS GOING TO ACCESSIBLE | | UPGRADES OR UP TO $5,000.00 IN VALUE MEETING THE EVENT | | OF DISPROPORTIONALITY UNDER 202.4.2. | | FBC-ACCESSIBILITY CODE SECTION 202.4.1 DISPROPORTIONATE | | COST. | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | 3A) SHEET A3 & A4 IDENTIFY THE FRONT DOOR AS DOOR 101. | | PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE FRONT | | ENTRY. GOOGLE EARTH STREET VIEW SHOWS A COLUMN AT THE | | FRONT ENTRY AS WELL AS A HORIZONTAL BAR APPROXIMATELY | | 36 INCHES ABOVE GRADE. 107.2.1.3 ADDITIONAL INFORMATION | | IS REQUIRED. | | | | 2017 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY. | | EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR | | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE | | PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. | | | | ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. MINIMUM | | MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY | | WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE | | FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE | | OR HINGE SIDE CLEARANCE. THE FRONT DOOR APPEARS TO HAVE | | LESS THAN THE REQUIRED 18 INCHES FOR MANEUVERING | | CLEARANCES. | | | | 3B) THERE IS ALSO A RAMP; PLEASE PROVIDE THE SLOPE IN | | INCHES RISE PER FEET IN LENGTH. 2017 ACCESSIBILITY | | CODE. 405.2 SLOPE. RAMP RUNS SHALL HAVE A RUNNING SLOPE | | NOT STEEPER THAN 1:12. EXCEPTION: IN EXISTING SITES, | | BUILDINGS, AND FACILITIES, RAMPS SHALL BE PERMITTED TO | | HAVE RUNNING SLOPES STEEPER THAN 1:12 COMPLYING WITH | | TABLE 405.2 WHERE SUCH SLOPES ARE NECESSARY DUE TO | | SPACE LIMITATIONS. | | | | 3C) THE EXISTING RESTROOM DOES NOT ALSO MEET THE | | REQUIREMENTS FOR A SINGLE USER TOILET ROOM UNDER 213.2 | | TOILET ROOMS AND BATHING ROOMS. WHERE TOILET ROOMS ARE | | PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH 603. | | EXCEPTIONS: | | 1.IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE TO | | COMPLY WITH 603, ALTERING EXISTING TOILET ROOMS SHALL | | NOT BE REQUIRED WHERE A SINGLE UNISEX TOILET ROOM | | COMPLYING WITH 213.2.1 IS PROVIDED AND LOCATED IN THE | | SAME AREA AND ON THE SAME FLOOR AS EXISTING IN | | ACCESSIBLE TOILET OR BATHING ROOMS. | | | | 4) SHEET A3 & A4. NEW WORK NOT COVERED UNDER THE 20% | | DISPROPORTIONATE COST. PLEASE SHOW COMPLIANCE WITH: | | | | 4A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE | | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE | | SEATING SPACES AND STANDING SPACES AT THE DINING | | SURFACES SHALL COMPLY WITH 902. | | | | 4B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES | | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | SURFACES AND WORK SURFACES. | | | | 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN | | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL | | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR | | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS (SEASONAL | | SEATING). | | | | 4D) 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2 AND | | 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, | | BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, | | AND BOOTHS. | | | | 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | 5) SHEET A4 THERE IS A DISCREPANCY IN THE WIND SPEEDS; | | YES THE VULT WIND SPEED FOR THIS WIND ZONE FOR A | | BUILDING CATEGORY II STRUCTURE IS 170 VULT. THE PLANS | | GO ONTO INDICATE THE VASD IS 132 WHICH IS ALSO CORRECT. | | THERE IS ALSO A STATEMENT THE CURRENT NOA?S ARE TOO BE | | BASED ON 146 VASD. PLEASE NOTE THE 146 VASD WIND ZONES | | ARE FOR DADE AND BROWARD ONLY. IF THE DESIGNER WISHES | | TO DESIGN TO THE HIGHER WIND SPEED THEN ALSO UP THE | | VULT WIND SPEED TO CORRELATE WITH THE 146 VASD. UNTIL | | THIS IS KNOWN THE PRESSURES GIVEN CAN NOT BE DETERMINED | | FOR CODE COMPLIANCE. PLEASE ALSO NOTE THE PRESSURES | | GIVEN NOTE MAX. PSF, THIS IS ASSUMED TO BE 10 SQUARE | | FEET. DISCREPANCY IN PLANS. 107.2.1.3. ALL PRESSURES | | NEED TO BE EXPRESSED IN VASD SINCE THE PRODUCT | | APPROVALS ARE IN VASD. | | | | 6A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | APPROVALS: | | (31)(A) EXTERIOR DOORS | | (G) PRE-ENGINEERED A/C STANDS | | | | 6B) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE | | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION | | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH | | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, | | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED | | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND | | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B | | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE | | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S | | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE | | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED | | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. | | | | 6C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | SHOP DRAWINGS ETC.. | | | | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2019-03-13 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-03-13 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-03-13 |
Time |
13:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2019-03-04 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-03-04 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-03-04 |
Time |
12:23 |
Sent To |
|
|
Notes |
2019-03-04 14:50:25 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | 4TH ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS | | BELOW. BE ADVISED THAT A FOUR TIMES FEE FOR PLAN REVIEW | | HAS BEEN ADDED TO PERMIT. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES, NOTED FOR | | THIRD REVIEW. ANY NEW COMMENTS WILL BE LISTED AFTER | | PREVIOUS COMMENTS. | | | | 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY | | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR | | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, | | 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC | | 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 | | PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). | | INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 | | PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD | | BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS | | AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)(3RD | | REVIEW: PANEL SCHEDULES ARE STILL SHOWING THE WRONG | | VOLTAGE. PANEL A IS SHOWN BEING FED FROM B PHASE OF | | PANEL B, WHICH WOULD CREATE A HIGH LEG ON PANEL A AND | | PANEL A1, WHICH SHOW LOADS THAT SHOULD NOT BE CONNECTED | | TO A HIGH LEG.)(4TH REVIEW: AS EXPLAINED IN PREVIOUS | | REVIEWS, AND IN MEETING WITH ENGINEER, THE VOLTAGES | | SPECIFIED IN PANEL SCHEDULES AND USED IN CALCULATION | | SHOULD BE AS NOTED ABOVE,WHICH IS PER NEC 220.5. THIS | | IS IMPORTANT BECAUSE THE CALCULATED CURRENT DRAW WILL | | CHANGE BASED ON USING THE CORRECT NUMBERS. AS THIS IS A | | HIGH LEG SYSTEM, IT SHOULD BE IDENTIFIED AS 120/240 | | VOLT 3 PHASE AND 120/240 VOLT 1 PHASE, RESPECTIVELY. | | ADDITIONALLY, THE HIGH LEG IS STILL SHOWN AS FEEDING | | PANEL A. THE PANEL SCHEDULE FOR PANEL A1 HAS BEEN | | REMOVED FROM PLAN.) | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | 8. CORRECTED. | | 9. CORRECTED. | | 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)(3RD | | REVIEW: LOAD CALCULATION NOT CORRECT. AS EXPLAINED IN | | MEETING WITH EOR, A 50% DEMAND FACTOR FOR RECEPTACLE | | LOAD OVER 10,000 VA IS NOT PERMITTED AS SHOWN. ANY | | EQUIPMENT FED FROM AN OUTLET MUST BE CALCULATED AT 100% | | FOR NON-CONTINUOUS LOAD AND 125% FOR A CONTINUOUS LOAD. | | NEC 215.2, 220.14(A). ADDITIONALLY, THERE ARE LOADS | | SHOWN IN LOAD CALCULATION THAT ARE NOT SHOWN ANYWHERE | | ELSE ON PLAN. PROVIDE CORRECTIONS.)(4TH REVIEW: LOAD | | CALCULATION FOR SERVICE IS NOW CORRECT, BUT THE LOAD | | CALCULATION FOR PANEL A SHOWS THE DEMAND FACTORS FOR | | OUTLETS AT 50% FOR ANY LOAD OVER 10,000. AS STATED | | BEFORE, THIS DEMAND FACTOR CANNOT BE APPLIED TO | | EQUIPMENT, ONLY TO GENERAL RECEPTACLE LOADS. PROVIDE | | CORRECTION.) | | 11. CORRECTED. | | 12. CORRECTED. | | 13. CORRECTED. | | 14. PER COMMENT REFERENCING CORDS, INSPECTOR WILL NEED | | TO CONFIRM AT TIME OF INSPECTION THAT THE EQUIPMENT IS | | LISTED FOR THIS TYPE OF CONNECTION PER NEC 400.7(8). | | PROVISO WILL BE LISTED ON PLAN WHEN APPROVED. | | 15. CORRECTED. | | 16. CORRECTED. | | 17. CORRECTED. | | 18. CORRECTED. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2019-01-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-01-10 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-01-10 |
Time |
12:12 |
Sent To |
|
|
Notes |
2019-01-10 15:20:41 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES, NOTED FOR | | THIRD REVIEW. ANY NEW COMMENTS WILL BE LISTED AFTER | | PREVIOUS COMMENTS. | | | | THESE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THE | | SUBMITTED PLANS THAT IS NOT TO CODE. PLEASE BE ADVISED | | THAT SOME OF THESE COMMENTS HAVE NOT BEEN ADDRESSED FOR | | TWO REVIEWS. IF UPON THE NEXT REVIEW, IF IT IS | | NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN FOR THE | | SAME REASONS, AN ADDITIONAL PLAN REVIEW IS REQUIRED. | | FLORIDA STATUTES STATE: WITH RESPECT TO EVALUATION OF | | DESIGN PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT | | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH | | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | REVIEW. FS 553.80(2)(B) THE ADDITIONAL FEE FOR THIS | | PROJECT WOULD BE $550.00. THIS IS BASED ON CURRENT | | PERMIT VALUE SHOWN OF $25,000.00 | | | | 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY | | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR | | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, | | 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC | | 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 | | PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). | | INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 | | PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD | | BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS | | AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)(3RD | | REVIEW: PANEL SCHEDULES ARE STILL SHOWING THE WRONG | | VOLTAGE. PANEL A IS SHOWN BEING FED FROM B PHASE OF | | PANEL B, WHICH WOULD CREATE A HIGH LEG ON PANEL A AND | | PANEL A1, WHICH SHOW LOADS THAT SHOULD NOT BE CONNECTED | | TO A HIGH LEG.) | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | 8. CORRECTED. | | 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS | | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (3RD | | REVIEW, NOT PROVIDED. THIS IS A CHANGE OF OCCUPANCY, | | AUTOMATIC LIGHTING CONTROL IS REQUIRED.) | | 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)(3RD | | REVIEW: LOAD CALCULATION NOT CORRECT. AS EXPLAINED IN | | MEETING WITH EOR, A 50% DEMAND FACTOR FOR RECEPTACLE | | LOAD OVER 10,000 VA IS NOT PERMITTED AS SHOWN. ANY | | EQUIPMENT FED FROM AN OUTLET MUST BE CALCULATED AT 100% | | FOR NON-CONTINUOUS LOAD AND 125% FOR A CONTINUOUS LOAD. | | NEC 215.2, 220.14(A). ADDITIONALLY, THERE ARE LOADS | | SHOWN IN LOAD CALCULATION THAT ARE NOT SHOWN ANYWHERE | | ELSE ON PLAN. PROVIDE CORRECTIONS.) | | 11. CORRECTED. | | 12. CORRECTED. | | 13. CORRECTED. | | | | NEW COMMENTS: | | | | 14. CORDS ARE NOT TO BE USED IN LIEU OF PERMANENT | | WIRING METHODS, EXCEPT AS PERMITTED PER CODE. | | BREWMATION CONTROL DIAGRAM SHOWS CORDS GOING TO ALL OF | | THE EQUIPMENT FED FROM THIS CONTROL STATION. PROVIDE | | CLARIFICATION AND /OR CORRECTIONS. NEC 110.3, 400.7, | | 400.8 | | 15. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 | | 16. RISER DIAGRAM SHOWS PARALLEL 4/0 WIRE FEEDING METER | | CAN AND PANEL B. THIS WIRE IS UNDERSIZED FOR THE LOAD | | SHOWN. THIS ALSO CONFLICTS WITH WHAT IS SHOWN IN PANEL | | SCHEDULE. PROVIDE CORRECTION. NEC 310.15(B)(16) | | 17. GROUNDING ELECTRODE CONNECTIONS ARE SHOWN IN RISER | | DIAGRAM AT METER CAN AND AT PANEL B. THE GROUNDING | | ELECTRODE SYSTEM IS TIED TO THE SERVICE IN ONE LOCATION | | ONLY. GROUNDING ELECTRODE CONDUCTORS SHOULD NOT BE | | INSTALLED TO PANEL B. PROVIDE CORRECTION. NEC 250.6, | | 250.24 | | 18. SERVICE RISER FROM METER CAN TO FPL SERVICE SHOULD | | NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE | | CORRECTION. NEC 250.6, 250.24, 250.121 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-10-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-10 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-10 |
Time |
13:58 |
Sent To |
|
|
Notes |
2018-10-10 12:27:00 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY | | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR | | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, | | 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC | | 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3 | | PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG). | | INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3 | | PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD | | BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS | | AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.) | | 2. CORRECTED FOR NEW RISER DIAGRAM. | | 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL | | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD | | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO | | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30 (THE PLAN SHOWS AN EXISTING | | RISER DIAGRAM WITH PANEL A AND PANEL A1, AND THEN SHOWS | | A SEPARATE RISER FOR PANEL B WHICH DOES NOT INCLUDE | | PANEL A AND PANEL A1 BE ADVISED THAT ONLY ONE SERVICE | | IS PERMITTED PER NEC 230.2 AND THE RISER DIAGRAM SHOULD | | REFLECT THIS TYPE OF INSTALLATION.) | | 4. CORRECTED. | | 5. CORRECTED. | | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | (NOT PROVIDED.) | | 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS | | EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 (NO | | LIGHTING CIRCUITS OR FIXTURES SHOWN.) | | 8. CORRECTED. | | 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS | | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT | | PROVIDED - NO LIGHTING SHOWN.) | | 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.) | | 11. CORRECTED. | | 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA | | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS | | PRESENT. WPB FBC 105.1, 107.2.1 (NOT PROVIDED.) | | | | NEW COMMENTS: | | | | 13. LOCATION OF PANEL B SHOWN ON PLAN DOES NOT HAVE | | PROPER CLEARANCE REQUIRED. PROVIDE CORRECTION. NEC | | 110.26 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-04-13 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-04-13 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-04-13 |
Time |
07:05 |
Sent To |
|
|
Notes |
2018-04-13 15:35:05 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY | | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR | | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE | | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, | | 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC | | 107.3.5 | | 2. RISER DIAGRAM INDICATES THAT A 2? PVC CONDUIT WILL | | BE INSTALLED TO FPL TRANSFORMER. FOR THE WIRE SIZE | | REQUIRED WITH A 400 AMP SERVICE, A 2? PVC IS NOT OF | | ADEQUATE SIZE. PROVIDE CORRECTION. NEC INFORMATIVE | | ANNEX C | | 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL | | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD | | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO | | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30 | | 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. | | NEC 110.3, 110.9 | | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS | | EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 | | 8. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS | | STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 | | 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 | | 11. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER | | CODE. NEC 210.64 | | 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA | | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS | | PRESENT. WPB FBC 105.1, 107.2.1 | | | | DUE TO EXTENSIVE LACK OF INFORMATION ON PLANS, A | | COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME. FURTHER | | PLAN REVIEW COMMENTS ARE LIKELY. THERE IS A STATEMENT | | ON THE PLAN IN REFERENCE TO NEC 408.4 THAT APPEARS TO | | HAVE NO BEARING ON THE DESIGN IN QUESTION. THE | | DESIGNER?S OPINION OF PLAN REVIEW REQUIREMENTS ASIDE, | | BE ADVISED THAT NO ?ARM WRESTLING? WILL BE REQUIRED AND | | THERE WILL BE NO ?WIGGLE ROOM? ON CODE REQUIREMENTS. | | PROVIDE CORRECTIONS AS NOTED ABOVE. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2019-02-26 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2019-02-26 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2019-02-26 |
Time |
11:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2019-01-15 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2019-01-15 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2019-01-15 |
Time |
11:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2018-10-09 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-10-09 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-10-09 |
Time |
11:04 |
Sent To |
|
|
Notes |
2018-10-09 11:25:58 | PERMIT # 18031402 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 2ND REVIEW - FAILED COMMENTS | | | | 1) REPEAT COMMENT ---- SHEET A4: PLEASE LABEL THE | | EQUIPMENT (BREWING, STORAGE, DISTILLING, ETC.) THAT | | WILL BE USED IN THE BREWING AND KEG ROOMS. IF THE KEG | | ROOM IS SIMPLY TO BE USED FOR STORAGE OF KEGS, PLEASE | | PROVIDE DETAILS AS TO HOW THEY WILL BE STORED AND HOW | | MANY. | | PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION SHEETS | | FOR ALL OF THE SPECIALIZED EQUIPMENT THAT WILL BE | | HOUSED AND UTILIZED IN THESE ROOMS, FOR DETERMINATION | | OF CLASSIFICATION OF HAZARD OF CONTENTS. | | | | 2) REPEAT COMMENT (SHEET NUMBERS HAVE CHANGED) --- | | SHEETS A1 AND M1 HAVE CONFLICTING INFORMATION REGARDING | | THE OFFICE AND KEG AREAS. PLEASE REVIEW AND CONFIRM USE | | FOR THESE AREAS. | | | | 3) SHEET A1: THE OCCUPANCY LOAD FOR THE TAP ROOM IS | | LISTED AS 14 PERSONS. THERE IS SEATING SHOWN FOR 16. | | PLEASE ADJUST SEATING LAYOUT TO SHOW APPROPRIATE NUMBER | | OF SEATS FOR PATRONS. PLEASE NOTE THAT THE OCCUPANCY | | LOAD INCLUDES STAFFING AT THE BAR. | | | | 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE | | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION | | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS | | MAY BE GENERATED DURING PLAN RESUBMISSION. | | | | ***OWNER HAS PROVIDED SOME DETAILS REGARDING DISTILLING | | PROCESS AND KEG ROOM STORAGE, VIA EMAIL. PLEASE BE SURE | | TO INCLUDE THESE ITEMS IN THE RESUBMISSION.*** | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-04-03 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-04-03 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-04-03 |
Time |
11:40 |
Sent To |
|
|
Notes |
2018-04-03 11:51:57 | PERMIT # 18031402 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) SHEET A1 STATES THAT THE BUILDING IS "NOT | | SPRINKLED". SHEET A5 SAYS "SPRINKLED". PLEASE PROVIDE | | EXPLANATION OR CORRECTION. | | | | 2) SHEET A5 DOES NOT SPECIFY THE FIRE RATING FOR THE | | PROVIDED DOORS. PLEASE PROVIDE THE FIRE RATING FOR | | DOORS 101-107. | | | | 3) SHEET A4: PLEASE LABEL THE EQUIPMENT (BREWING, | | STORAGE, DISTILLING, ETC.) THAT WILL BE USED IN THE | | BREWING AND KEG ROOMS. IF THE KEG ROOM IS SIMPLY TO BE | | USED FOR STORAGE OF KEGS, PLEASE PROVIDE DETAILS AS TO | | HOW THEY WILL BE STORED AND HOW MANY. | | PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION SHEETS | | FOR ALL OF THE SPECIALIZED EQUIPMENT THAT WILL BE | | HOUSED AND UTILIZED IN THESE ROOMS, FOR DETERMINATION | | OF CLASSIFICATION OF HAZARD OF CONTENTS. | | | | 4) PLEASE PROVIDE A NARRATIVE OF THE BREWING PROCESS | | AND ORDER OF OPERATIONS. | | | | 5) SHEET A4: THE BREWING ROOM DOES NOT APPEAR TO BE | | RATED. PLEASE CONFIRM WHAT THE WALL RATINGS ARE FOR THE | | KEG ROOM, IF ANY. | | | | 6) SHEETS A3 AND A4 HAVE CONFLICTING INFORMATION | | REGARDING THE OFFICE AND KEG AREAS. PLEASE REVIEW AND | | CONFIRM USE FOR THESE AREAS. | | | | 7) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | 8) SHEET A1 INDICATES THAT THE BUILDING IS EQUIPPED | | WITH A FIRE ALARM SYSTEM. SEPARATE PLANS AND PERMITS | | ARE REQUIRED FOR THE INSTALLATION OR MODIFICATION OF | | THE FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2019-02-15 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2019-02-15 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-02-15 |
Time |
16:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2018-11-14 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2018-11-14 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2018-11-14 |
Time |
10:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2019-03-27 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-03-27 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-03-26 |
Time |
11:13 |
Sent To |
|
|
Notes |
2019-03-27 11:13:45 | RESUB ROUTED TO JDUPREY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2019-03-21 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-03-21 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-02-21 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-02-19 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-02-19 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-01-04 |
Time |
13:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-11-14 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-11-14 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-10-03 |
Time |
10:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-04-17 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-17 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-03-30 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2019-03-27 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-03-27 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-03-27 |
Time |
12:51 |
Sent To |
|
|
Notes |
2019-03-27 12:52:46 | IMPACT FEE | | MU-2019-009121-0000 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-01-28 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-01-28 |
Time |
10:23 |
Sent To |
|
|
Notes |
2019-01-28 10:24:15 | 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | JOSEAN A. DUPREY | | BUILDING PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6716 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-04-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2018-04-05 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2018-04-04 |
Time |
16:47 |
Sent To |
|
|
Notes |
2018-04-05 10:03:57 | 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF | | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR | | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE | | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST | | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE | | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | (561)233-5025 FOR MORE INFORMATION. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-01-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-10 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-09 |
Time |
17:46 |
Sent To |
E |
|
Notes |
2019-01-10 11:00:33 | MECHANICAL PROVISOS: | | | | 1) COMMISSIONING OF THE BREWERY OR DISTILLERY SYSTEM | | SHALL BE PERFORMED BY BMC CONSULTING ENGINEERS, AND A | | SIGNED AND SEALED LETTER OR REPORT CERTIFYING THE | | INSTALLATION AND FUNCTIONING OF THE SYSTEM SHALL BE | | PROVIDED. | | | | 2) MANUFACTURER?S SPECIFICATIONS AND INSTALLATION | | INSTRUCTIONS FOR THE CHILLER AND ALL BREWERY EQUIPMENT | | SHALL BE ONSITE AT TIME OF INSPECTION. | | | | 3) ACCESS AND VENTILATION SHALL BE PROVIDED FOR THE | | CHILLER IN THE MEZZANINE. | | | | 4) THE VENTILATION SYSTEM IN THE BREWERY ROOM SHALL | | OPERATE CONTINUOUSLY. | | | | 5) MANUFACTURER?S SPECIFICATIONS AND THE LOUVER NOA | | AND/OR FLORIDA PRODUCT APPROVAL SHALL BE ONSITE AT TIME | | OF INSPECTION. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-23 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-23 |
Time |
07:40 |
Sent To |
|
|
Notes |
2018-10-23 11:12:21 | 2ND REVIEW FBC-2017 | | PERMIT #18031402 | | 10/22/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS A2 & M1.0: AS PREVIOUSLY REQUESTED IN THE 1ST | | REVIEW, PLEASE SEE SECTION 1009 FBC EX, AND PROVIDE | | MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND | | SPACES PER TABLE 403.3.1 FBC M. PROVIDE A SCHEDULE THAT | | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR | | AIR. PLEASE NOTE THAT THE BAR AND TAP ROOM AREAS ARE | | CALCULATED AT 100 PERSONS PER 1000 SF., AT 7.5 CFMS PER | | PERSON + 0.18 CFMS PER SF. | | | | 2) M1.0: AN AUTOMATIC SHUTOFF DAMPER FOR THE NEW | | OUTDOOR AIR DUCT IS REQUIRED PER SECTION C403.2.4.3 FBC | | EC. INDICATE WHAT TYPE OF DAMPER WILL BE INSTALLED- | | GRAVITY OR MOTORIZED. | | | | 3) M1.0: A DUCT SMOKE DETECTOR IS REQUIRED IN THE | | SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION | | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED | | IF THE MANUFACTURER'S SPECIFICATIONS INDICATES THE | | SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF | | SUPPLY AIR. | | | | 4) A2 & M1.0: THE A2 BREWERY ROOM PLAN SHOWS ADDTIONAL | | TANKS THAT THE MEP PLANS DON'T SHOW. AS PREVIOUSLY | | REQUESTED PLEASE PROVIDE AN EQUIPMENT SCHEDULE THAT | | LISTS ALL THE BREWERY TANKS AND EQUIPMENT, AND IF A | | REMOTE CHILLER, BOILER, AND PROCESS PIPING SYSTEMS WILL | | BE INSTALLED. | | | | 5) M-1 CLARIFY HOW EF-1 WAS SIZED- PROVIDE A | | CALCULATION, AND AN EQUIPMENT SCHEDULE FOR THE FAN. | | | | 6) M-1: PROVIDE A FLORIDA PRODUCT APPROVAL AND/OR A | | MIAMI-DADE NOA FOR THE NEW LOUVERS. | | | | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL BREWERY | | EQUIPMENT AND TANKS WITH SHOP DRAWING APPROVAL STAMPOS | | BY THE EOR- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT | | ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE | | SUBMITTED FOR REVIEW. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-04-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-04-10 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-04-10 |
Time |
12:50 |
Sent To |
|
|
Notes |
2018-04-10 13:20:51 | 1ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING, | | ENERGY CONSERVATION CODES | | PERMIT #18031402 | | 4/10/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW, AND | | THERE ARE NO NOTES ON THE PLANS BY THE ARCHITECT TO | | INDICATE IF THERE ARE EXISTING HVAC SYSTEMS IN THE | | TENANT SPACE, OR HOW THE ROOMS AND SPACES ARE BEING | | VENTILATED. | | | | 2) ACCORDING TO THE BUILDING PLAN REVIEW COMMENTS THE | | PROPOSED PROJECT IS A CHANGE OF OCCUPANCY PER SECTION | | 202 FBC-17 EXISTING BUILDING CODE. PLEASE SEE SECTION | | 1009 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR | | ALL ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 | | MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE | | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | 3) REVISE THE PLAN TO SHOW ALL NEW MECHANICAL | | INSTALLATIONS, OR ALTERATIONS TO THE EXISTING SYSTEMS | | SUCH AS AC REPLACEMENTS, DUCT RELOCATIONS, DUCT | | EXTENSIONS, DIFFUSER OR GRILL REPLACEMENTS, EXHAUST OR | | O/A LOUVER INSTALLATIONS ETC. | | | | 3) BREWERY: A) CLARIFY IF A BOILER AND CHILLER WILL BE | | INSTALLED FOR USE IN THE BREWING PROCESS, AND PROVIDE | | EQUIPMENT SCHEDULES, EQUIPMENT LOCATIONS, AND DETAILS | | ON THE PLAN IF APPLICABLE. B) PROVIDE A PROCESS PIPING | | LAYOUT AND ISOMETRIC DRAWING AND INCLUDE PIPE SPECS. D) | | IDENTIFY AND LABEL ALL BREWERY TANKS, EQUIPMENT ETC. | | | | 4) ADVISORY: PLEASE NOTE THAT A CHANGE OF OCCUPANCY MAY | | BE REQUIRED TO SHOW COMPLIANCE WITH SECTION C505.1 | | FBC-17 ENERGY CONSERVATION, IN WHICH CASE ENERGY | | CALCULATIONS WILL HAVE TO BE SUBMITTED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT | | ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE | | SUBMITTED FOR REVIEW. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2019-03-08 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-03-08 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-03-08 |
Time |
10:16 |
Sent To |
|
|
Notes |
2019-03-08 10:16:47 | PROVISO!!! | | | | | | SHALL COMPLY BEFORE FINAL INSPECTION. | | | | | | PLUMBING COMMENTS: | | | | | | 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | ACCESSIBILITY COMMENTS | | | | SHOW COMPLIANCE WITH THE FOLLOWING: | | | | 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM | | MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4 | | | | 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL | | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER | | FBC ACC 604.5.1 | | | | 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES (610 | | MM) MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 | | | | 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. PER FBC ACC 603.3 | | | | 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR. PER FBC ACC 604.7 | | | | 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER | | FBC ACC 606.3 | | | | 7. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION. PER FBC | | ACC 604.2 | | | | 8. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL | | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE | | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING | | SURFACE. PER FBC ACC 609.4 | | | | 9. CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY WITH | | DIMENSIONS. PER FBC ACC 604.3.1, 606.2 | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-01-23 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-23 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-23 |
Time |
11:17 |
Sent To |
|
|
Notes |
2019-01-23 13:00:16 | PROVISO!!! | | | | | | SHALL COMPLY BEFORE FINAL INSPECTION. | | | | | | PLUMBING COMMENTS: | | | | | | 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | ACCESSIBILITY COMMENTS | | | | SHOW COMPLIANCE WITH THE FOLLOWING: | | | | 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM | | MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4 | | | | 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG | | MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL | | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER | | FBC ACC 604.5.1 | | | | 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES (610 | | MM) MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 | | | | 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS | | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE | | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. PER FBC ACC 603.3 | | | | 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT | | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR. PER FBC ACC 604.7 | | | | 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER | | FBC ACC 606.3 | | | | 7. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 | | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION. PER FBC | | ACC 604.2 | | | | 8. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL | | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE | | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING | | SURFACE. PER FBC ACC 609.4 | | | | 9. CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY WITH | | DIMENSIONS. PER FBC ACC 604.3.1, 606.2 | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2018-10-23 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2018-10-23 |
Time |
14:51 |
Sent To |
|
|
Notes |
2018-10-23 14:51:56 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 2ND REVIEW: | | PLUMBING COMMENTS: DENIED | | PREVIOUS COMMENTS NOT RESPONDED TO. | | | | PLEASE PROVIDE A COST BREAK DOWN TO SHOW WHICH ELEMENTS | | THAT ARE BEING ALTERED TO COMPLY WITH ACCESSIBILITY TO | | MEET THE REQUIREMENTS OF FBC ACC | | 202.4.1DISPROPORTIONATE COST. | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | 4. THE VALUE OF THIS JOB APPEARS LOW WE HAVE SEEN A FEW | | NEW MICRO BREW PUB COME IN FOR PERMITTING WITH MUCH | | HIGHER VALUES PLEASE PROVIDE A DETAILED, QUANTITY | | ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS, VALUE TO | | INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, | | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND | | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; | | EXCLUDING ONLY LAND VALUE. THIS ALSO INCLUDES THE | | BREWING EQUIPMENT. PER WPB AMEND TO FBC 109.3 | | 5. PLEASE LABEL ALL BREWING EQUIPMENT AND SHOW LOCATION | | OF BOILERS AND CHILLERS. PER WPB AMEND TO FBC 107.2.1 | | 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR ALL PROCESS | | PIPING USED IN BREWING PROCESS. PER WPB AMEND TO FBC | | 107.3.5.1.3 | | A. ADDED NOTE: A SCHEMATIC IS ACCEPTABLE. | | | | ADDITIONAL COMMENTS: | | 1. SINK IN THE BREWERY APPEARS TO BE ADDED; PLEASE | | PROVIDE SANITARY AND WATER ISOMETRIC FOR CONNECTION. | | WPB FBC 107.2.1 | | 2. IT IS ASSUMED THAT POTABLE MAKE UP WATER WILL BE | | REQUIRED FOR THE BREWERY PROCESS PIPING. PLEASE SHOW | | HOW THAT IS TO BE PROVIDED. SHOW HOW ANY REQUIRED | | BACKFLOW PREVENTION WILL BE ACCOMPLISHED. WPB FBC | | 107.2.1 | | 3. HOW WILL EQUIPMENT BE DRAINED? | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN | | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-805-6715 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-04-17 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-17 |
Time |
06:20 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-17 |
Time |
06:20 |
Sent To |
|
|
Notes |
2018-04-17 07:56:23 | 1ST REVIEW: FBC 2017 6TH EDITION | | PLUMBING COMMENTS: | | 1. ACCORDING TO THE BUSINESS TAX RECORDS THE PREVIOUS | | OCCUPANCY WAS A MERCANTILE WHICH WILL MAKE THIS A | | CHANGE OF OCCUPANCY AND SHALL COMPLY WITH FBC EX CH 10 | | 2. PER FBC EX 1006.1 THE REQUIREMENTS OF THE FLORIDA | | ACCESSIBILITY CODE SHALL BE MET. | | 3. PLEASE PROVIDE A COST BREAK DOWN TO SHOW WHICH | | ELEMENTS THAT ARE BEING ALTERED TO COMPLY WITH | | ACCESSIBILITY TO MEET THE REQUIREMENTS OF FBC ACC | | 202.4.1DISPROPORTIONATE COST. | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | AN INACCESSIBLE DRINKING FOUNTAIN. | | 4. THE VALUE OF THIS JOB APPEARS LOW WE HAVE SEEN A FEW | | NEW MICRO BREW PUB COME IN FOR PERMITTING WITH MUCH | | HIGHER VALUES PLEASE PROVIDE A DETAILED, QUANTITY | | ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS, VALUE TO | | INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, | | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND | | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; | | EXCLUDING ONLY LAND VALUE. THIS ALSO INCLUDES THE | | BREWING EQUIPMENT. PER WPB AMEND TO FBC 109.3 | | 5. PLEASE LABEL ALL BREWING EQUIPMENT AND SHOW LOCATION | | OF BOILERS AND CHILLERS. PER WPB AMEND TO FBC 107.2.1 | | 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR ALL PROCESS | | PIPING USED IN BREWING PROCESS. PER WPB AMEND TO FBC | | 107.3.5.1.3 | | 7. PLEASE PROVIDE DOMESTIC WATER ISOMETRIC. PER WPB | | AMEND TO FBC 107.3.5.1.3(13) | | 8. PLEASE SHOW LOCATION OF THE WATER HEATER AND SHOW | | COMPLIANCE WITH FBC PL 607.1, 607.2, 607.5 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2019-03-21 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-03-21 |
Time |
11:00 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2019-03-20 |
Time |
16:58 |
Sent To |
PC |
|
Notes |
2019-03-21 11:02:03 | THE TRASH AND A/C ENCLOSURE REQUIRES A SEPARATE PERMIT | | WITH PLANS. | | | | THE BREWERY FUNCTIONS OCCUPY 67% OF THE BUILDING. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2019-02-06 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-02-06 |
Time |
16:34 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2019-02-06 |
Time |
13:50 |
Sent To |
HIST |
|
Notes |
2019-02-06 16:46:09 | FAILED | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | 1) PROVIDE TWO COPIES OF THE SURVEY. | | | | 2) REPEAT COMMENT: PROVIDE A SURVEY BASED SITE PLAN | | WHICH SHOWS WHERE THE REQUIRED ON-SITE LOADING SPACE IS | | LOCATED. THE ALLEY MAY NOT BE USED AS THE LOADING SPACE | | AS THERE IS NO ACCESS FROM THE ALLEY TO THE BUILDING. | | | | 3) THE RESUBMITTED PLANS SHOW A WALK IN COOLER | | CONDENSING UNIT AND GARBAGE RECEPTACLES ON THE EXTERIOR | | OF THE BUILDING. | | | | A. THE DIMENSIONS (LXIX) OF THE CONDENSING UNIT MUST BE | | SHOWN ON THE SITE PLAN, AS WELL AS THE DIMENSION OF THE | | UNIT FROM THE BUILDING. | | B. THE SETBACK FROM THE CONDENSING UNIT TO THE WEST AND | | NORTH PROPERTY LINES MUST BE SHOWN ON THE SITE PLAN. | | C. THE NORTH MIXED USE DISTRICT REQUIRES THAT THE | | CONDENSING UNIT AND GARBAGE RECEPTACLES NOT BE VISIBLE | | FROM THE PUBLIC SIDEWALK. THE SITE PLAN NEEDS TO SHOW | | THE SPECIFIC UNIT AND PROVIDE VERIFICATION OF THE | | SCREENING FOR FULL HEIGHT OF THE UNIT . | | D. THE GARBAGE RECEPTACLES NEED TO BE IN AN ENCLOSURE, | | WHICH REQUIRES A SEPARATE PERMIT, WITH PLANS. | | | | 4) PROVIDE A TABLE THAT BREAKS DOWN THE SQUARE FOOTAGE | | IN THE BUILDING TO VERIFY THAT THE PROPOSED FLOOR PLAN | | INCLUDES AT LEAST 65 PERCENT AND NO MORE THAN 75 | | PERCENT OF THE SQUARE FOOTAGE OF THE FACILITY DEDICATED | | TO THE BREWERY FUNCTION. | | | | 5) PLEASE BE AWARE THAT THE BUSINESS MUST HOLD ONE OF | | THE FOLLOWING LICENSES ISSUED BY THE FLORIDA DEPARTMENT | | OF BUSINESS AND PROFESSIONAL REGULATIONS, DIVISION OF | | ALCOHOLIC BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2018-10-30 |
Time |
14:26 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2018-10-30 |
Time |
14:26 |
Sent To |
|
|
Notes |
2018-10-30 15:47:35 | FAILED | | | | 1) PROVIDE A SURVEY BASED SITE PLAN WHICH SHOWS WHERE | | THE REQUIRED ON-SITE LOADING SPACE IS LOCATED. THE | | ALLEY MAY NOT BE USED AS THE LOADING SPACE AS THERE IS | | NO ACCESS FROM THE ALLEY TO THE BUILDING. | | | | 2) PLEASE NOTE THAT YOU MAY NOT USE THE DOOR BY THE | | BREWERY FOR DELIVERY ACCESS SINCE THIS DOOR FACES | | NORTHWOOD ROAD. | | | | 3) SHEETS A-1 AND A-2 SHOW AN AREA MARKED AS OFFICE. | | THIS AREA IS MARKED AS KEG ROOM ON THE MECHANICAL AND | | PLUMBING PLANS. ALL PLANS SHALL SHOW SAME, ACCURATE | | NOMENCLATURE. | | | | 4) PLEASE NOTE THAT IN ORDER TO MEET THE ALCOHOL | | SEPARATION REQUIREMENTS, YOU MUST HAVE AT LEAST 65 | | PERCENT OF THE SQUARE FOOTAGE OF THE FACILITY DEDICATED | | TO THE BREWERY FUNCTION INCLUDING, BUT NOT LIMITED TO, | | BREW HOUSE, BOILING AND WATER TREATMENT AREAS, BOTTLING | | AND KEGGING LINES, MALT MILLING AND STORAGE, | | FERMENTATION TANKS, CONDITION TANKS AND SERVING TANKS. | | OFFICES ARE NOT INCLUDED IN THIS DEFINITION, SO IF THE | | AREA SHOWN ON A-1 AND A-2 IS OFFICE, YOU WILL NOT BE | | ABLE TO SECUCRE AN ALCOHOL LICENSE FOR THE FACILITY. | | | | 5) PLEASE BE AWARE THAT THE BUSINESS MUST HOLD ONE OF | | THE FOLLOWING LICENSES ISSUED BY THE FLORIDA DEPARTMENT | | OF BUSINESS AND PROFESSIONAL REGULATIONS, DIVISION OF | | ALCOHOLIC BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|
|
|