Plan Review Details - Permit 18031402
Plan Review Stops For Permit 18031402
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-03-06 Cont ID  
Sent By jduprey Date 2019-03-06 Time 09:02 Rev Time 0.00
Received By jduprey Date 2019-03-06 Time 09:02 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-28 Cont ID  
Sent By jduprey Date 2019-01-28 Time 11:14 Rev Time 0.00
Received By jduprey Date 2019-01-28 Time 10:54 Sent To Z
Notes
2019-01-28 11:14:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. A DOOR PRODUCT SUBMITTAL WAS PROVIDED. HOWEVER THIS
 IS BASE ON THE 2014 FBC. PLEASE PROVIDE A NEW PRODUCT
 APPROVAL PER CURRENT BUILDING CODE, ALSO PROVIDE THE
 FRONT PAGE OF THE PRODUCT APPROVAL, WE WANT TO KNOW IF
 IS IMPACT RESISTANT AND WICH PRODUCT SPECIFIC IS
 SELECTED. FBC 107
  
 2. PROVIDE STRUCTURAL DETAILA FOR THE NEW SIDEWALK TO
 THE ENTRANCE. FBC 107
  
 3. THE NEW DOOR OPENING STRUCTURAL DETAIL DO NOT
 SPECIFY HOW THE ANGLE WILL BE INSTALLED (E.I. CLIPS, IN
 THE WALL?, AT THE BOTTOL OF THE HEADER?) ALSO NO REBAR
 WAS SPECIFIED FOR THIS DETAIL. FBC 107

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-07 Cont ID  
Sent By jwitmer Date 2018-11-07 Time 12:23 Rev Time 0.00
Received By jwitmer Date 2018-11-07 Time 10:00 Sent To HIST
Notes
2018-11-07 12:17:502017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18031402
 ADD: 519 NORTHWOOD AVE. SUITE 525
 CONT: CALIBER CONTRACTOR
 TEL: 561-222-1906
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. NOV. 07/2018
 ACTION: DENIED
 NOTICE!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. DO NOT TAKE THE OLD SHEETS AWAY, WE USE
 THEM TO REFER TO THE CHANGES MADE. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
 1) THE COVERSHEET A1: COMPLIED. BUSINESS OCCUPANCY
 DECLARED, NO OCCUPANCY SEPARATION REQUIRED BETWEEN
 BUSINESS AND F1 OCCUPANCY. Q THE COVERSHEET A1 UNDER
 THE HEADING PROJECT DESCRIPTION LIST THIS AS A LEVEL LL
 ALTERATION. PLEASE NOTE THE LAST KNOWN USE (BUSINESS
 TAX) WAS SMYRNA MARKET OR A RETAIL OCCUPANCY. THIS
 WOULD MAKE THE USE A CHANGE OF OCCUPANCY AND UNDER THE
 2017 FBC-EXISTING BUILDING CODE CHAPTER 10 CHANGE OF
 OCCUPANCY. SEE SECTION 1001.2.2.1 OF THE EXISTING
 BUILDING CODE. PARTIAL CHANGE OF OCCUPANCY. WHERE THE
 OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN
 EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY.
 2A) 2ND REQUEST. SHEET A-2 SHOWS A NEW DOOR OPENING TO
 THE EXTERIOR, A NEW 6068 DOUBLE DOORS. PLEASE PROVIDE A
 SITE PLAN FOR WHERE THE 6068 DOORS ARE LEADING TOO. IF
 THERE IS TO BE SEASONAL SEATING PLEASE PROVIDE ON THE
 SITE PLAN THE ADDITIONAL SEATING. 2017 FBC-B 302.1. A
 ROOM OR SPACE THAT IS INTENDED TO BE OCCUPIED AT
 DIFFERENT TIMES FOR DIFFERENT PURPOSES SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS THAT ARE APPLICABLE TO
 EACH OF THE PURPOSES FOR WHICH THE ROOM OR SPACE WILL
 BE OCCUPIED.
 2B) NEW COMMENT. SHEET A2 HAS A NEW MASONRY OPENING
 (WINDOW), PLEASE CORRECT FOR A NEW DOORWAY. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 3) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH SECTION
 202.4.1. OF THE 2017 FBC-ACCESSIBILITY CODE SECTION
 202.4.1 DISPROPORTIONATE COST. PROVIDE AN ITEMIZED LIST
 WHERE 0.20 % OF THE PERMIT VALUE IS GOING TO ACCESSIBLE
 UPGRADES OR UP TO $5,000.00 IN VALUE MEETING THE EVENT
 OF DISPROPORTIONALITY UNDER 202.4.2.
 FBC-ACCESSIBILITY CODE SECTION 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 3A)2ND REQUEST. SHEETS A3 & A4 MISSING FROM THIS
 REVIEW. SHEET A3 & A4 IDENTIFY THE FRONT DOOR AS DOOR
 101. PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE
 FRONT ENTRY. GOOGLE EARTH STREET VIEW SHOWS A COLUMN AT
 THE FRONT ENTRY AS WELL AS A HORIZONTAL BAR
 APPROXIMATELY 36 INCHES ABOVE GRADE. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2017 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. MINIMUM
 MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE
 OR HINGE SIDE CLEARANCE. THE FRONT DOOR APPEARS TO HAVE
 LESS THAN THE REQUIRED 18 INCHES FOR MANEUVERING
 CLEARANCES.
  
 3B) 2ND REQUEST. THERE IS ALSO A RAMP; PLEASE PROVIDE
 THE SLOPE IN INCHES RISE PER FEET IN LENGTH. 2017
 ACCESSIBILITY CODE. 405.2 SLOPE. RAMP RUNS SHALL HAVE A
 RUNNING SLOPE NOT STEEPER THAN 1:12. EXCEPTION: IN
 EXISTING SITES, BUILDINGS, AND FACILITIES, RAMPS SHALL
 BE PERMITTED TO HAVE RUNNING SLOPES STEEPER THAN 1:12
 COMPLYING WITH TABLE 405.2 WHERE SUCH SLOPES ARE
 NECESSARY DUE TO SPACE LIMITATIONS.
  
 3C) 2ND REQUEST. THE EXISTING RESTROOM DOES NOT ALSO
 MEET THE REQUIREMENTS FOR A SINGLE USER TOILET ROOM
 UNDER 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE
 TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603. EXCEPTIONS:
 1.IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE TO
 COMPLY WITH 603, ALTERING EXISTING TOILET ROOMS SHALL
 NOT BE REQUIRED WHERE A SINGLE UNISEX TOILET ROOM
 COMPLYING WITH 213.2.1 IS PROVIDED AND LOCATED IN THE
 SAME AREA AND ON THE SAME FLOOR AS EXISTING IN
 ACCESSIBLE TOILET OR BATHING ROOMS.
  
 4)2ND REQUEST. MISSING SHEETS A3 & A4. SHEET A3 & A4.
 NEW WORK NOT COVERED UNDER THE 20% DISPROPORTIONATE
 COST. PLEASE SHOW COMPLIANCE WITH:
  
 4A) 2ND REQUEST. MISSING SHEETS A3 & A4. 226.1 WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 4B) 2ND REQUEST. MISSING SHEETS A3 & A4. 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4C) 2ND REQUEST. MISSING SHEETS A3 & A4. 206.2.5
 206.2.5 RESTAURANTS AND CAFETERIAS. IN RESTAURANTS AND
 CAFETERIAS, AN ACCESSIBLE ROUTE SHALL BE PROVIDED TO
 ALL DINING AREAS, INCLUDING RAISED OR SUNKEN DINING
 AREAS, AND OUTDOOR DINING AREAS (SEASONAL SEATING).
  
 4D) 2ND REQUEST. 902.1 .DINING SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS.
  
 4D)(1) 2ND REQUEST. MISSING SHEETS A3 & A4. 902.2 CLEAR
 FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305 POSITIONED FOR A FORWARD APPROACH SHALL BE
 PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED.
  
 4D)(2) 2ND REQUEST. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 2ND REQUEST. SHEETS A3 & A4 ARE MISSING. SHEET A4
 THERE IS A DISCREPANCY IN THE WIND SPEEDS; YES THE VULT
 WIND SPEED FOR THIS WIND ZONE FOR A BUILDING CATEGORY
 II STRUCTURE IS 170 VULT. THE PLANS GO ONTO INDICATE
 THE VASD IS 132 WHICH IS ALSO CORRECT. THERE IS ALSO A
 STATEMENT THE CURRENT NOA?S ARE TOO BE BASED ON 146
 VASD. PLEASE NOTE THE 146 VASD WIND ZONES ARE FOR DADE
 AND BROWARD ONLY. IF THE DESIGNER WISHES TO DESIGN TO
 THE HIGHER WIND SPEED THEN ALSO UP THE VULT WIND SPEED
 TO CORRELATE WITH THE 146 VASD. UNTIL THIS IS KNOWN THE
 PRESSURES GIVEN CANNOT BE DETERMINED FOR CODE
 COMPLIANCE. PLEASE ALSO NOTE THE PRESSURES GIVEN NOTE
 MAX. PSF, THIS IS ASSUMED TO BE 10 SQUARE FEET.
 DISCREPANCY IN PLANS. 107.2.1.3. ALL PRESSURES NEED TO
 BE EXPRESSED IN VASD SINCE THE PRODUCT APPROVALS ARE IN
 VASD.
  
 6A) 2ND REQUEST. 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (G) PRE-ENGINEERED A/C STANDS
  
 6B)2ND REQUEST. PLEASE IDENTIFY ON THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 6C)2ND REQUEST. W. P. B. 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-05 Cont ID  
Sent By jwitmer Date 2018-04-05 Time 10:03 Rev Time 0.00
Received By jwitmer Date 2018-04-04 Time 16:46 Sent To  
Notes
2018-04-05 10:03:082017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18031402
 ADD: 519 NORTHWOOD AVE. SUITE 525
 CONT: CALIBER CONTRACTOR
 TEL: 561-222-1906
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THUR. APRIL 05/2018
 ACTION: DENIED
  
 1) THE COVERSHEET A1:
  
 1A) THE COVERSHEET A1 UNDER THE HEADING PROJECT
 DESCRIPTION LIST THIS AS A LEVEL LL ALTERATION. PLEASE
 NOTE THE LAST KNOWN USE (BUSINESS TAX) WAS SMYRNA
 MARKET OR A RETAIL OCCUPANCY. THIS WOULD MAKE THE USE A
 CHANGE OF OCCUPANCY AND UNDER THE 2017 FBC-EXISTING
 BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY. SEE
 SECTION 1001.2.2.1 OF THE EXISTING BUILDING CODE.
 PARTIAL CHANGE OF OCCUPANCY. WHERE THE OCCUPANCY
 CLASSIFICATION OR GROUP OF A PORTION OF AN EXISTING
 BUILDING IS CHANGED, SECTION 1012 SHALL APPLY.
  
 1B) IT WOULD APPEAR THAT THE MAIN OCCUPANCY IS NOT A
 BUSINESS OCCUPANCY BUT A F-1 OCCUPANCY. PLEASE REFER TO
 THE 2017 FBC-B 508.2.3 OF THE EXISTING BUILDING CODE.
 YOU MUST TAKE THE BUILDING AREA PER FLOOR, NOT THE
 TENANT SPACE.
 508.2.3 ALLOWABLE BUILDING AREA. THE ALLOWABLE AREA OF
 THE BUILDING SHALL BE BASED ON THE APPLICABLE
 PROVISIONS OF SECTION 506 FOR THE MAIN OCCUPANCY OF THE
 BUILDING. AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT
 OCCUPY MORE THAN 10 PERCENT OF THE FLOOR AREA OF THE
 STORY IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED
 THE TABULAR VALUES FOR NONSPRINKLERED BUILDINGS IN
 TABLE 506.2 FOR EACH SUCH ACCESSORY OCCUPANCY.
  
 1C) SINCE THE BUSINESS PORTION OF THE TENANT SPACE IS
 ACCESSORY TO THE F-1 OCCUPANCY THERE IS NO NEED OF AN
 OCCUPANCY SEPARATION. 2017 FBC-B 508.2.4 SEPARATION OF
 OCCUPANCIES. NO SEPARATION IS REQUIRED BETWEEN
 ACCESSORY OCCUPANCIES AND THE MAIN OCCUPANCY.
  
 1D) COMMON PATH OF TRAVEL FOR THE F-1 OCCUPANCY IS
 STILL 75 FEET, MUST CHANGE THE OCCUPANCY TYPE. 2017
 FBC-B TABLE 1006.2.1.
  
 1E) THE A-1 SHEET UNDER FIRE PROTECTION LIST THIS
 BUILDING AS NOT-SPRINKLERED, WHEREAS SHEET A5 TABLE
 803.9 IS TAKING CREDIT FOR A FIRE SPRINKLERED BUILDING.
 DISCREPANCY IN PLANS, PLEASE CORRECT. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A-3 SHOWS A NEW DOOR OPENING TO THE EXTERIOR,
 A NEW 6068 DOUBLE DOORS. PLEASE PROVIDE A SITE PLAN FOR
 WHERE THE 6068 DOORS ARE LEADING TOO. IF THERE IS TO BE
 SEASONAL SEATING PLEASE PROVIDE ON THE SITE PLAN THE
 ADDITIONAL SEATING. 2017 FBC-B 302.1. A ROOM OR SPACE
 THAT IS INTENDED TO BE OCCUPIED AT DIFFERENT TIMES FOR
 DIFFERENT PURPOSES SHALL COMPLY WITH ALL OF THE
 REQUIREMENTS THAT ARE APPLICABLE TO EACH OF THE
 PURPOSES FOR WHICH THE ROOM OR SPACE WILL BE OCCUPIED.
  
 3) PLEASE SHOW COMPLIANCE WITH SECTION 202.4.1. OF THE
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. PROVIDE AN ITEMIZED LIST WHERE
 0.20 % OF THE PERMIT VALUE IS GOING TO ACCESSIBLE
 UPGRADES OR UP TO $5,000.00 IN VALUE MEETING THE EVENT
 OF DISPROPORTIONALITY UNDER 202.4.2.
 FBC-ACCESSIBILITY CODE SECTION 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 3A) SHEET A3 & A4 IDENTIFY THE FRONT DOOR AS DOOR 101.
 PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE FRONT
 ENTRY. GOOGLE EARTH STREET VIEW SHOWS A COLUMN AT THE
 FRONT ENTRY AS WELL AS A HORIZONTAL BAR APPROXIMATELY
 36 INCHES ABOVE GRADE. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 2017 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. MINIMUM
 MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE
 OR HINGE SIDE CLEARANCE. THE FRONT DOOR APPEARS TO HAVE
 LESS THAN THE REQUIRED 18 INCHES FOR MANEUVERING
 CLEARANCES.
  
 3B) THERE IS ALSO A RAMP; PLEASE PROVIDE THE SLOPE IN
 INCHES RISE PER FEET IN LENGTH. 2017 ACCESSIBILITY
 CODE. 405.2 SLOPE. RAMP RUNS SHALL HAVE A RUNNING SLOPE
 NOT STEEPER THAN 1:12. EXCEPTION: IN EXISTING SITES,
 BUILDINGS, AND FACILITIES, RAMPS SHALL BE PERMITTED TO
 HAVE RUNNING SLOPES STEEPER THAN 1:12 COMPLYING WITH
 TABLE 405.2 WHERE SUCH SLOPES ARE NECESSARY DUE TO
 SPACE LIMITATIONS.
  
 3C) THE EXISTING RESTROOM DOES NOT ALSO MEET THE
 REQUIREMENTS FOR A SINGLE USER TOILET ROOM UNDER 213.2
 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET ROOMS ARE
 PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH 603.
 EXCEPTIONS:
 1.IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE TO
 COMPLY WITH 603, ALTERING EXISTING TOILET ROOMS SHALL
 NOT BE REQUIRED WHERE A SINGLE UNISEX TOILET ROOM
 COMPLYING WITH 213.2.1 IS PROVIDED AND LOCATED IN THE
 SAME AREA AND ON THE SAME FLOOR AS EXISTING IN
 ACCESSIBLE TOILET OR BATHING ROOMS.
  
 4) SHEET A3 & A4. NEW WORK NOT COVERED UNDER THE 20%
 DISPROPORTIONATE COST. PLEASE SHOW COMPLIANCE WITH:
  
 4A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS (SEASONAL
 SEATING).
  
 4D) 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2 AND
 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE,
 BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS,
 AND BOOTHS.
  
 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) SHEET A4 THERE IS A DISCREPANCY IN THE WIND SPEEDS;
 YES THE VULT WIND SPEED FOR THIS WIND ZONE FOR A
 BUILDING CATEGORY II STRUCTURE IS 170 VULT. THE PLANS
 GO ONTO INDICATE THE VASD IS 132 WHICH IS ALSO CORRECT.
 THERE IS ALSO A STATEMENT THE CURRENT NOA?S ARE TOO BE
 BASED ON 146 VASD. PLEASE NOTE THE 146 VASD WIND ZONES
 ARE FOR DADE AND BROWARD ONLY. IF THE DESIGNER WISHES
 TO DESIGN TO THE HIGHER WIND SPEED THEN ALSO UP THE
 VULT WIND SPEED TO CORRELATE WITH THE 146 VASD. UNTIL
 THIS IS KNOWN THE PRESSURES GIVEN CAN NOT BE DETERMINED
 FOR CODE COMPLIANCE. PLEASE ALSO NOTE THE PRESSURES
 GIVEN NOTE MAX. PSF, THIS IS ASSUMED TO BE 10 SQUARE
 FEET. DISCREPANCY IN PLANS. 107.2.1.3. ALL PRESSURES
 NEED TO BE EXPRESSED IN VASD SINCE THE PRODUCT
 APPROVALS ARE IN VASD.
  
 6A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (G) PRE-ENGINEERED A/C STANDS
  
 6B) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-03-13 Cont ID  
Sent By jpearson Date 2019-03-13 Time 13:10 Rev Time 0.00
Received By jpearson Date 2019-03-13 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-03-04 Cont ID  
Sent By jpearson Date 2019-03-04 Time 15:04 Rev Time 0.00
Received By jpearson Date 2019-03-04 Time 12:23 Sent To  
Notes
2019-03-04 14:50:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 4TH ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS
 BELOW. BE ADVISED THAT A FOUR TIMES FEE FOR PLAN REVIEW
 HAS BEEN ADDED TO PERMIT.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES, NOTED FOR
 THIRD REVIEW. ANY NEW COMMENTS WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC
 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3
 PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG).
 INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3
 PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD
 BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)(3RD
 REVIEW: PANEL SCHEDULES ARE STILL SHOWING THE WRONG
 VOLTAGE. PANEL A IS SHOWN BEING FED FROM B PHASE OF
 PANEL B, WHICH WOULD CREATE A HIGH LEG ON PANEL A AND
 PANEL A1, WHICH SHOW LOADS THAT SHOULD NOT BE CONNECTED
 TO A HIGH LEG.)(4TH REVIEW: AS EXPLAINED IN PREVIOUS
 REVIEWS, AND IN MEETING WITH ENGINEER, THE VOLTAGES
 SPECIFIED IN PANEL SCHEDULES AND USED IN CALCULATION
 SHOULD BE AS NOTED ABOVE,WHICH IS PER NEC 220.5. THIS
 IS IMPORTANT BECAUSE THE CALCULATED CURRENT DRAW WILL
 CHANGE BASED ON USING THE CORRECT NUMBERS. AS THIS IS A
 HIGH LEG SYSTEM, IT SHOULD BE IDENTIFIED AS 120/240
 VOLT 3 PHASE AND 120/240 VOLT 1 PHASE, RESPECTIVELY.
 ADDITIONALLY, THE HIGH LEG IS STILL SHOWN AS FEEDING
 PANEL A. THE PANEL SCHEDULE FOR PANEL A1 HAS BEEN
 REMOVED FROM PLAN.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)(3RD
 REVIEW: LOAD CALCULATION NOT CORRECT. AS EXPLAINED IN
 MEETING WITH EOR, A 50% DEMAND FACTOR FOR RECEPTACLE
 LOAD OVER 10,000 VA IS NOT PERMITTED AS SHOWN. ANY
 EQUIPMENT FED FROM AN OUTLET MUST BE CALCULATED AT 100%
 FOR NON-CONTINUOUS LOAD AND 125% FOR A CONTINUOUS LOAD.
 NEC 215.2, 220.14(A). ADDITIONALLY, THERE ARE LOADS
 SHOWN IN LOAD CALCULATION THAT ARE NOT SHOWN ANYWHERE
 ELSE ON PLAN. PROVIDE CORRECTIONS.)(4TH REVIEW: LOAD
 CALCULATION FOR SERVICE IS NOW CORRECT, BUT THE LOAD
 CALCULATION FOR PANEL A SHOWS THE DEMAND FACTORS FOR
 OUTLETS AT 50% FOR ANY LOAD OVER 10,000. AS STATED
 BEFORE, THIS DEMAND FACTOR CANNOT BE APPLIED TO
 EQUIPMENT, ONLY TO GENERAL RECEPTACLE LOADS. PROVIDE
 CORRECTION.)
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. PER COMMENT REFERENCING CORDS, INSPECTOR WILL NEED
 TO CONFIRM AT TIME OF INSPECTION THAT THE EQUIPMENT IS
 LISTED FOR THIS TYPE OF CONNECTION PER NEC 400.7(8).
 PROVISO WILL BE LISTED ON PLAN WHEN APPROVED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-01-10 Cont ID  
Sent By jpearson Date 2019-01-10 Time 15:20 Rev Time 0.00
Received By jpearson Date 2019-01-10 Time 12:12 Sent To  
Notes
2019-01-10 15:20:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES, NOTED FOR
 THIRD REVIEW. ANY NEW COMMENTS WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 THESE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THE
 SUBMITTED PLANS THAT IS NOT TO CODE. PLEASE BE ADVISED
 THAT SOME OF THESE COMMENTS HAVE NOT BEEN ADDRESSED FOR
 TWO REVIEWS. IF UPON THE NEXT REVIEW, IF IT IS
 NECESSARY TO REJECT THE SUBMITTED PLAN AGAIN FOR THE
 SAME REASONS, AN ADDITIONAL PLAN REVIEW IS REQUIRED.
 FLORIDA STATUTES STATE: WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW. FS 553.80(2)(B) THE ADDITIONAL FEE FOR THIS
 PROJECT WOULD BE $550.00. THIS IS BASED ON CURRENT
 PERMIT VALUE SHOWN OF $25,000.00
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC
 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3
 PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG).
 INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3
 PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD
 BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)(3RD
 REVIEW: PANEL SCHEDULES ARE STILL SHOWING THE WRONG
 VOLTAGE. PANEL A IS SHOWN BEING FED FROM B PHASE OF
 PANEL B, WHICH WOULD CREATE A HIGH LEG ON PANEL A AND
 PANEL A1, WHICH SHOW LOADS THAT SHOULD NOT BE CONNECTED
 TO A HIGH LEG.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (3RD
 REVIEW, NOT PROVIDED. THIS IS A CHANGE OF OCCUPANCY,
 AUTOMATIC LIGHTING CONTROL IS REQUIRED.)
 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)(3RD
 REVIEW: LOAD CALCULATION NOT CORRECT. AS EXPLAINED IN
 MEETING WITH EOR, A 50% DEMAND FACTOR FOR RECEPTACLE
 LOAD OVER 10,000 VA IS NOT PERMITTED AS SHOWN. ANY
 EQUIPMENT FED FROM AN OUTLET MUST BE CALCULATED AT 100%
 FOR NON-CONTINUOUS LOAD AND 125% FOR A CONTINUOUS LOAD.
 NEC 215.2, 220.14(A). ADDITIONALLY, THERE ARE LOADS
 SHOWN IN LOAD CALCULATION THAT ARE NOT SHOWN ANYWHERE
 ELSE ON PLAN. PROVIDE CORRECTIONS.)
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
  
 NEW COMMENTS:
  
 14. CORDS ARE NOT TO BE USED IN LIEU OF PERMANENT
 WIRING METHODS, EXCEPT AS PERMITTED PER CODE.
 BREWMATION CONTROL DIAGRAM SHOWS CORDS GOING TO ALL OF
 THE EQUIPMENT FED FROM THIS CONTROL STATION. PROVIDE
 CLARIFICATION AND /OR CORRECTIONS. NEC 110.3, 400.7,
 400.8
 15. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 16. RISER DIAGRAM SHOWS PARALLEL 4/0 WIRE FEEDING METER
 CAN AND PANEL B. THIS WIRE IS UNDERSIZED FOR THE LOAD
 SHOWN. THIS ALSO CONFLICTS WITH WHAT IS SHOWN IN PANEL
 SCHEDULE. PROVIDE CORRECTION. NEC 310.15(B)(16)
 17. GROUNDING ELECTRODE CONNECTIONS ARE SHOWN IN RISER
 DIAGRAM AT METER CAN AND AT PANEL B. THE GROUNDING
 ELECTRODE SYSTEM IS TIED TO THE SERVICE IN ONE LOCATION
 ONLY. GROUNDING ELECTRODE CONDUCTORS SHOULD NOT BE
 INSTALLED TO PANEL B. PROVIDE CORRECTION. NEC 250.6,
 250.24
 18. SERVICE RISER FROM METER CAN TO FPL SERVICE SHOULD
 NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION. NEC 250.6, 250.24, 250.121
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By jpearson Date 2018-10-10 Time 13:58 Rev Time 0.00
Received By jpearson Date 2018-10-10 Time 13:58 Sent To  
Notes
2018-10-10 12:27:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC
 107.3.5 (ELECTRICAL SERVICES ARE EITHER 120/208 VOLT 3
 PHASE, OR 120/240 VOLT 3 PHASE (WHICH HAS A HIGH LEG).
 INDICATION ON PLAN IS THAT THE SERVICE IS 230 VOLT 3
 PHASE, BUT THERE ARE LOADS SHOWN ON B PHASE WHICH WOULD
 BE THE HIGH LEG. PROVIDE CLARIFICATION AND CORRECTIONS
 AS NEEDED TO ACCURATELY REFLECT THE INSTALLATION.)
 2. CORRECTED FOR NEW RISER DIAGRAM.
 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 (THE PLAN SHOWS AN EXISTING
 RISER DIAGRAM WITH PANEL A AND PANEL A1, AND THEN SHOWS
 A SEPARATE RISER FOR PANEL B WHICH DOES NOT INCLUDE
 PANEL A AND PANEL A1 BE ADVISED THAT ONLY ONE SERVICE
 IS PERMITTED PER NEC 230.2 AND THE RISER DIAGRAM SHOULD
 REFLECT THIS TYPE OF INSTALLATION.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 (NOT PROVIDED.)
 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS
 EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1 (NO
 LIGHTING CIRCUITS OR FIXTURES SHOWN.)
 8. CORRECTED.
 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2 (NOT
 PROVIDED - NO LIGHTING SHOWN.)
 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)
 11. CORRECTED.
 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1 (NOT PROVIDED.)
  
 NEW COMMENTS:
  
 13. LOCATION OF PANEL B SHOWN ON PLAN DOES NOT HAVE
 PROPER CLEARANCE REQUIRED. PROVIDE CORRECTION. NEC
 110.26
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-13 Cont ID  
Sent By jpearson Date 2018-04-13 Time 15:35 Rev Time 0.00
Received By jpearson Date 2018-04-13 Time 07:05 Sent To  
Notes
2018-04-13 15:35:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 215.2, 215.5, 310.15(B)(16), 408.4; WPB FBC
 107.3.5
 2. RISER DIAGRAM INDICATES THAT A 2? PVC CONDUIT WILL
 BE INSTALLED TO FPL TRANSFORMER. FOR THE WIRE SIZE
 REQUIRED WITH A 400 AMP SERVICE, A 2? PVC IS NOT OF
 ADEQUATE SIZE. PROVIDE CORRECTION. NEC INFORMATIVE
 ANNEX C
 3. PROVIDE MORE DETAIL FOR RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. SHOW ON PLAN ALL LIGHTING AND POWER BRANCH CIRCUITS
 EXISTING AND THOSE TO BE INSTALLED. FBC 107.2.1
 8. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 9. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 10. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 11. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 12. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
  
 DUE TO EXTENSIVE LACK OF INFORMATION ON PLANS, A
 COMPLETE REVIEW IS NOT POSSIBLE AT THIS TIME. FURTHER
 PLAN REVIEW COMMENTS ARE LIKELY. THERE IS A STATEMENT
 ON THE PLAN IN REFERENCE TO NEC 408.4 THAT APPEARS TO
 HAVE NO BEARING ON THE DESIGN IN QUESTION. THE
 DESIGNER?S OPINION OF PLAN REVIEW REQUIREMENTS ASIDE,
 BE ADVISED THAT NO ?ARM WRESTLING? WILL BE REQUIRED AND
 THERE WILL BE NO ?WIGGLE ROOM? ON CODE REQUIREMENTS.
 PROVIDE CORRECTIONS AS NOTED ABOVE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 11:49 Rev Time 0.00
Received By scaldero Date 2019-02-26 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-01-15 Cont ID  
Sent By scaldero Date 2019-01-15 Time 11:47 Rev Time 0.00
Received By scaldero Date 2019-01-15 Time 11:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-10-09 Cont ID  
Sent By scaldero Date 2018-10-09 Time 11:29 Rev Time 0.00
Received By scaldero Date 2018-10-09 Time 11:04 Sent To  
Notes
2018-10-09 11:25:58PERMIT # 18031402
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW - FAILED COMMENTS
  
 1) REPEAT COMMENT ---- SHEET A4: PLEASE LABEL THE
 EQUIPMENT (BREWING, STORAGE, DISTILLING, ETC.) THAT
 WILL BE USED IN THE BREWING AND KEG ROOMS. IF THE KEG
 ROOM IS SIMPLY TO BE USED FOR STORAGE OF KEGS, PLEASE
 PROVIDE DETAILS AS TO HOW THEY WILL BE STORED AND HOW
 MANY.
 PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION SHEETS
 FOR ALL OF THE SPECIALIZED EQUIPMENT THAT WILL BE
 HOUSED AND UTILIZED IN THESE ROOMS, FOR DETERMINATION
 OF CLASSIFICATION OF HAZARD OF CONTENTS.
  
 2) REPEAT COMMENT (SHEET NUMBERS HAVE CHANGED) ---
 SHEETS A1 AND M1 HAVE CONFLICTING INFORMATION REGARDING
 THE OFFICE AND KEG AREAS. PLEASE REVIEW AND CONFIRM USE
 FOR THESE AREAS.
  
 3) SHEET A1: THE OCCUPANCY LOAD FOR THE TAP ROOM IS
 LISTED AS 14 PERSONS. THERE IS SEATING SHOWN FOR 16.
 PLEASE ADJUST SEATING LAYOUT TO SHOW APPROPRIATE NUMBER
 OF SEATS FOR PATRONS. PLEASE NOTE THAT THE OCCUPANCY
 LOAD INCLUDES STAFFING AT THE BAR.
  
 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
 ***OWNER HAS PROVIDED SOME DETAILS REGARDING DISTILLING
 PROCESS AND KEG ROOM STORAGE, VIA EMAIL. PLEASE BE SURE
 TO INCLUDE THESE ITEMS IN THE RESUBMISSION.***
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-03 Cont ID  
Sent By scaldero Date 2018-04-03 Time 12:04 Rev Time 0.00
Received By scaldero Date 2018-04-03 Time 11:40 Sent To  
Notes
2018-04-03 11:51:57PERMIT # 18031402
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SHEET A1 STATES THAT THE BUILDING IS "NOT
 SPRINKLED". SHEET A5 SAYS "SPRINKLED". PLEASE PROVIDE
 EXPLANATION OR CORRECTION.
  
 2) SHEET A5 DOES NOT SPECIFY THE FIRE RATING FOR THE
 PROVIDED DOORS. PLEASE PROVIDE THE FIRE RATING FOR
 DOORS 101-107.
  
 3) SHEET A4: PLEASE LABEL THE EQUIPMENT (BREWING,
 STORAGE, DISTILLING, ETC.) THAT WILL BE USED IN THE
 BREWING AND KEG ROOMS. IF THE KEG ROOM IS SIMPLY TO BE
 USED FOR STORAGE OF KEGS, PLEASE PROVIDE DETAILS AS TO
 HOW THEY WILL BE STORED AND HOW MANY.
 PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION SHEETS
 FOR ALL OF THE SPECIALIZED EQUIPMENT THAT WILL BE
 HOUSED AND UTILIZED IN THESE ROOMS, FOR DETERMINATION
 OF CLASSIFICATION OF HAZARD OF CONTENTS.
  
 4) PLEASE PROVIDE A NARRATIVE OF THE BREWING PROCESS
 AND ORDER OF OPERATIONS.
  
 5) SHEET A4: THE BREWING ROOM DOES NOT APPEAR TO BE
 RATED. PLEASE CONFIRM WHAT THE WALL RATINGS ARE FOR THE
 KEG ROOM, IF ANY.
  
 6) SHEETS A3 AND A4 HAVE CONFLICTING INFORMATION
 REGARDING THE OFFICE AND KEG AREAS. PLEASE REVIEW AND
 CONFIRM USE FOR THESE AREAS.
  
 7) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 8) SHEET A1 INDICATES THAT THE BUILDING IS EQUIPPED
 WITH A FIRE ALARM SYSTEM. SEPARATE PLANS AND PERMITS
 ARE REQUIRED FOR THE INSTALLATION OR MODIFICATION OF
 THE FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By fmittner Date 2019-02-15 Time 16:10 Rev Time 0.00
Received By fmittner Date 2019-02-15 Time 16:10 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-11-14 Cont ID  
Sent By fmittner Date 2018-11-14 Time 10:09 Rev Time 0.00
Received By fmittner Date 2018-11-14 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-03-27 Cont ID  
Sent By jduprey Date 2019-03-27 Time 12:52 Rev Time 0.00
Received By jduprey Date 2019-03-26 Time 11:13 Sent To  
Notes
2019-03-27 11:13:45RESUB ROUTED TO JDUPREY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-21 Cont ID  
Sent By cpuell Date 2019-03-21 Time 11:24 Rev Time 0.00
Received By cpuell Date 2019-02-21 Time 14:04 Sent To  
Notes
2019-02-22 14:04:17B29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-19 Cont ID  
Sent By lmarchan Date 2019-02-19 Time 10:01 Rev Time 0.00
Received By lmarchan Date 2019-01-04 Time 13:52 Sent To  
Notes
2019-01-07 13:52:58B34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-14 Cont ID  
Sent By cpuell Date 2018-11-14 Time 10:49 Rev Time 0.00
Received By cpuell Date 2018-10-03 Time 10:15 Sent To  
Notes
2018-10-05 10:15:14B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-17 Cont ID  
Sent By gjohnson Date 2018-04-17 Time 07:58 Rev Time 0.00
Received By gjohnson Date 2018-03-30 Time 14:24 Sent To  
Notes
2018-04-02 14:24:30B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-03-27 Cont ID  
Sent By jduprey Date 2019-03-27 Time 12:52 Rev Time 0.00
Received By jduprey Date 2019-03-27 Time 12:51 Sent To  
Notes
2019-03-27 12:52:46IMPACT FEE
 MU-2019-009121-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-01-28 Cont ID  
Sent By jduprey Date 2019-01-28 Time 10:25 Rev Time 0.00
Received By jduprey Date 2019-01-28 Time 10:23 Sent To  
Notes
2019-01-28 10:24:151) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-04-05 Cont ID  
Sent By jwitmer Date 2018-04-05 Time 10:04 Rev Time 0.00
Received By jwitmer Date 2018-04-04 Time 16:47 Sent To  
Notes
2018-04-05 10:03:571) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-10 Cont ID  
Sent By ccole Date 2019-01-10 Time 10:59 Rev Time 0.00
Received By ccole Date 2019-01-09 Time 17:46 Sent To E
Notes
2019-01-10 11:00:33MECHANICAL PROVISOS:
  
 1) COMMISSIONING OF THE BREWERY OR DISTILLERY SYSTEM
 SHALL BE PERFORMED BY BMC CONSULTING ENGINEERS, AND A
 SIGNED AND SEALED LETTER OR REPORT CERTIFYING THE
 INSTALLATION AND FUNCTIONING OF THE SYSTEM SHALL BE
 PROVIDED.
  
 2) MANUFACTURER?S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CHILLER AND ALL BREWERY EQUIPMENT
 SHALL BE ONSITE AT TIME OF INSPECTION.
  
 3) ACCESS AND VENTILATION SHALL BE PROVIDED FOR THE
 CHILLER IN THE MEZZANINE.
  
 4) THE VENTILATION SYSTEM IN THE BREWERY ROOM SHALL
 OPERATE CONTINUOUSLY.
  
 5) MANUFACTURER?S SPECIFICATIONS AND THE LOUVER NOA
 AND/OR FLORIDA PRODUCT APPROVAL SHALL BE ONSITE AT TIME
 OF INSPECTION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-23 Cont ID  
Sent By ccole Date 2018-10-23 Time 10:46 Rev Time 0.00
Received By ccole Date 2018-10-23 Time 07:40 Sent To  
Notes
2018-10-23 11:12:212ND REVIEW FBC-2017
 PERMIT #18031402
 10/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A2 & M1.0: AS PREVIOUSLY REQUESTED IN THE 1ST
 REVIEW, PLEASE SEE SECTION 1009 FBC EX, AND PROVIDE
 MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3.1 FBC M. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR. PLEASE NOTE THAT THE BAR AND TAP ROOM AREAS ARE
 CALCULATED AT 100 PERSONS PER 1000 SF., AT 7.5 CFMS PER
 PERSON + 0.18 CFMS PER SF.
  
 2) M1.0: AN AUTOMATIC SHUTOFF DAMPER FOR THE NEW
 OUTDOOR AIR DUCT IS REQUIRED PER SECTION C403.2.4.3 FBC
 EC. INDICATE WHAT TYPE OF DAMPER WILL BE INSTALLED-
 GRAVITY OR MOTORIZED.
  
 3) M1.0: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE 5-TON AC SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATES THE
 SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 4) A2 & M1.0: THE A2 BREWERY ROOM PLAN SHOWS ADDTIONAL
 TANKS THAT THE MEP PLANS DON'T SHOW. AS PREVIOUSLY
 REQUESTED PLEASE PROVIDE AN EQUIPMENT SCHEDULE THAT
 LISTS ALL THE BREWERY TANKS AND EQUIPMENT, AND IF A
 REMOTE CHILLER, BOILER, AND PROCESS PIPING SYSTEMS WILL
 BE INSTALLED.
  
 5) M-1 CLARIFY HOW EF-1 WAS SIZED- PROVIDE A
 CALCULATION, AND AN EQUIPMENT SCHEDULE FOR THE FAN.
  
 6) M-1: PROVIDE A FLORIDA PRODUCT APPROVAL AND/OR A
 MIAMI-DADE NOA FOR THE NEW LOUVERS.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL BREWERY
 EQUIPMENT AND TANKS WITH SHOP DRAWING APPROVAL STAMPOS
 BY THE EOR- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT
 ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE
 SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-10 Cont ID  
Sent By ccole Date 2018-04-10 Time 12:54 Rev Time 0.00
Received By ccole Date 2018-04-10 Time 12:50 Sent To  
Notes
2018-04-10 13:20:511ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #18031402
 4/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW, AND
 THERE ARE NO NOTES ON THE PLANS BY THE ARCHITECT TO
 INDICATE IF THERE ARE EXISTING HVAC SYSTEMS IN THE
 TENANT SPACE, OR HOW THE ROOMS AND SPACES ARE BEING
 VENTILATED.
  
 2) ACCORDING TO THE BUILDING PLAN REVIEW COMMENTS THE
 PROPOSED PROJECT IS A CHANGE OF OCCUPANCY PER SECTION
 202 FBC-17 EXISTING BUILDING CODE. PLEASE SEE SECTION
 1009 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3.1 FBC-17
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) REVISE THE PLAN TO SHOW ALL NEW MECHANICAL
 INSTALLATIONS, OR ALTERATIONS TO THE EXISTING SYSTEMS
 SUCH AS AC REPLACEMENTS, DUCT RELOCATIONS, DUCT
 EXTENSIONS, DIFFUSER OR GRILL REPLACEMENTS, EXHAUST OR
 O/A LOUVER INSTALLATIONS ETC.
  
 3) BREWERY: A) CLARIFY IF A BOILER AND CHILLER WILL BE
 INSTALLED FOR USE IN THE BREWING PROCESS, AND PROVIDE
 EQUIPMENT SCHEDULES, EQUIPMENT LOCATIONS, AND DETAILS
 ON THE PLAN IF APPLICABLE. B) PROVIDE A PROCESS PIPING
 LAYOUT AND ISOMETRIC DRAWING AND INCLUDE PIPE SPECS. D)
 IDENTIFY AND LABEL ALL BREWERY TANKS, EQUIPMENT ETC.
  
 4) ADVISORY: PLEASE NOTE THAT A CHANGE OF OCCUPANCY MAY
 BE REQUIRED TO SHOW COMPLIANCE WITH SECTION C505.1
 FBC-17 ENERGY CONSERVATION, IN WHICH CASE ENERGY
 CALCULATIONS WILL HAVE TO BE SUBMITTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT
 ADDITIONAL COMMENTS MAY OCCUR WHEN CORRECTED PLANS ARE
 SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-03-08 Cont ID  
Sent By gjohnson Date 2019-03-08 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2019-03-08 Time 10:16 Sent To  
Notes
2019-03-08 10:16:47PROVISO!!!
  
  
 SHALL COMPLY BEFORE FINAL INSPECTION.
  
  
 PLUMBING COMMENTS:
  
  
 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 ACCESSIBILITY COMMENTS
  
 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4
  
 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 603.3
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER FBC ACC 604.7
  
 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 FBC ACC 606.3
  
 7. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION. PER FBC
 ACC 604.2
  
 8. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 9. CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY WITH
 DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By gjohnson Date 2019-01-23 Time 13:00 Rev Time 0.00
Received By gjohnson Date 2019-01-23 Time 11:17 Sent To  
Notes
2019-01-23 13:00:16PROVISO!!!
  
  
 SHALL COMPLY BEFORE FINAL INSPECTION.
  
  
 PLUMBING COMMENTS:
  
  
 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 ACCESSIBILITY COMMENTS
  
 SHOW COMPLIANCE WITH THE FOLLOWING:
  
 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4
  
 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 603.3
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER FBC ACC 604.7
  
 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 FBC ACC 606.3
  
 7. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION. PER FBC
 ACC 604.2
  
 8. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 9. CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY WITH
 DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-23 Cont ID  
Sent By jesmith Date 2018-10-23 Time 14:52 Rev Time 0.00
Received By jesmith Date 2018-10-23 Time 14:51 Sent To  
Notes
2018-10-23 14:51:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
 PREVIOUS COMMENTS NOT RESPONDED TO.
  
 PLEASE PROVIDE A COST BREAK DOWN TO SHOW WHICH ELEMENTS
 THAT ARE BEING ALTERED TO COMPLY WITH ACCESSIBILITY TO
 MEET THE REQUIREMENTS OF FBC ACC
 202.4.1DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 4. THE VALUE OF THIS JOB APPEARS LOW WE HAVE SEEN A FEW
 NEW MICRO BREW PUB COME IN FOR PERMITTING WITH MUCH
 HIGHER VALUES PLEASE PROVIDE A DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS, VALUE TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. THIS ALSO INCLUDES THE
 BREWING EQUIPMENT. PER WPB AMEND TO FBC 109.3
 5. PLEASE LABEL ALL BREWING EQUIPMENT AND SHOW LOCATION
 OF BOILERS AND CHILLERS. PER WPB AMEND TO FBC 107.2.1
 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR ALL PROCESS
 PIPING USED IN BREWING PROCESS. PER WPB AMEND TO FBC
 107.3.5.1.3
 A. ADDED NOTE: A SCHEMATIC IS ACCEPTABLE.
  
 ADDITIONAL COMMENTS:
 1. SINK IN THE BREWERY APPEARS TO BE ADDED; PLEASE
 PROVIDE SANITARY AND WATER ISOMETRIC FOR CONNECTION.
 WPB FBC 107.2.1
 2. IT IS ASSUMED THAT POTABLE MAKE UP WATER WILL BE
 REQUIRED FOR THE BREWERY PROCESS PIPING. PLEASE SHOW
 HOW THAT IS TO BE PROVIDED. SHOW HOW ANY REQUIRED
 BACKFLOW PREVENTION WILL BE ACCOMPLISHED. WPB FBC
 107.2.1
 3. HOW WILL EQUIPMENT BE DRAINED?
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-17 Cont ID  
Sent By gjohnson Date 2018-04-17 Time 06:20 Rev Time 0.00
Received By gjohnson Date 2018-04-17 Time 06:20 Sent To  
Notes
2018-04-17 07:56:231ST REVIEW: FBC 2017 6TH EDITION
 PLUMBING COMMENTS:
 1. ACCORDING TO THE BUSINESS TAX RECORDS THE PREVIOUS
 OCCUPANCY WAS A MERCANTILE WHICH WILL MAKE THIS A
 CHANGE OF OCCUPANCY AND SHALL COMPLY WITH FBC EX CH 10
 2. PER FBC EX 1006.1 THE REQUIREMENTS OF THE FLORIDA
 ACCESSIBILITY CODE SHALL BE MET.
 3. PLEASE PROVIDE A COST BREAK DOWN TO SHOW WHICH
 ELEMENTS THAT ARE BEING ALTERED TO COMPLY WITH
 ACCESSIBILITY TO MEET THE REQUIREMENTS OF FBC ACC
 202.4.1DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 4. THE VALUE OF THIS JOB APPEARS LOW WE HAVE SEEN A FEW
 NEW MICRO BREW PUB COME IN FOR PERMITTING WITH MUCH
 HIGHER VALUES PLEASE PROVIDE A DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS, VALUE TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. THIS ALSO INCLUDES THE
 BREWING EQUIPMENT. PER WPB AMEND TO FBC 109.3
 5. PLEASE LABEL ALL BREWING EQUIPMENT AND SHOW LOCATION
 OF BOILERS AND CHILLERS. PER WPB AMEND TO FBC 107.2.1
 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR ALL PROCESS
 PIPING USED IN BREWING PROCESS. PER WPB AMEND TO FBC
 107.3.5.1.3
 7. PLEASE PROVIDE DOMESTIC WATER ISOMETRIC. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 8. PLEASE SHOW LOCATION OF THE WATER HEATER AND SHOW
 COMPLIANCE WITH FBC PL 607.1, 607.2, 607.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-03-21 Cont ID  
Sent By eschneid Date 2019-03-21 Time 11:00 Rev Time 0.50
Received By eschneid Date 2019-03-20 Time 16:58 Sent To PC
Notes
2019-03-21 11:02:03THE TRASH AND A/C ENCLOSURE REQUIRES A SEPARATE PERMIT
 WITH PLANS.
  
 THE BREWERY FUNCTIONS OCCUPY 67% OF THE BUILDING.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-02-06 Cont ID  
Sent By eschneid Date 2019-02-06 Time 16:34 Rev Time 1.00
Received By eschneid Date 2019-02-06 Time 13:50 Sent To HIST
Notes
2019-02-06 16:46:09FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) PROVIDE TWO COPIES OF THE SURVEY.
  
 2) REPEAT COMMENT: PROVIDE A SURVEY BASED SITE PLAN
 WHICH SHOWS WHERE THE REQUIRED ON-SITE LOADING SPACE IS
 LOCATED. THE ALLEY MAY NOT BE USED AS THE LOADING SPACE
 AS THERE IS NO ACCESS FROM THE ALLEY TO THE BUILDING.
  
 3) THE RESUBMITTED PLANS SHOW A WALK IN COOLER
 CONDENSING UNIT AND GARBAGE RECEPTACLES ON THE EXTERIOR
 OF THE BUILDING.
  
 A. THE DIMENSIONS (LXIX) OF THE CONDENSING UNIT MUST BE
 SHOWN ON THE SITE PLAN, AS WELL AS THE DIMENSION OF THE
 UNIT FROM THE BUILDING.
 B. THE SETBACK FROM THE CONDENSING UNIT TO THE WEST AND
 NORTH PROPERTY LINES MUST BE SHOWN ON THE SITE PLAN.
 C. THE NORTH MIXED USE DISTRICT REQUIRES THAT THE
 CONDENSING UNIT AND GARBAGE RECEPTACLES NOT BE VISIBLE
 FROM THE PUBLIC SIDEWALK. THE SITE PLAN NEEDS TO SHOW
 THE SPECIFIC UNIT AND PROVIDE VERIFICATION OF THE
 SCREENING FOR FULL HEIGHT OF THE UNIT .
 D. THE GARBAGE RECEPTACLES NEED TO BE IN AN ENCLOSURE,
 WHICH REQUIRES A SEPARATE PERMIT, WITH PLANS.
  
 4) PROVIDE A TABLE THAT BREAKS DOWN THE SQUARE FOOTAGE
 IN THE BUILDING TO VERIFY THAT THE PROPOSED FLOOR PLAN
 INCLUDES AT LEAST 65 PERCENT AND NO MORE THAN 75
 PERCENT OF THE SQUARE FOOTAGE OF THE FACILITY DEDICATED
 TO THE BREWERY FUNCTION.
  
 5) PLEASE BE AWARE THAT THE BUSINESS MUST HOLD ONE OF
 THE FOLLOWING LICENSES ISSUED BY THE FLORIDA DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATIONS, DIVISION OF
 ALCOHOLIC BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By eschneid Date 2018-10-30 Time 14:26 Rev Time 1.00
Received By eschneid Date 2018-10-30 Time 14:26 Sent To  
Notes
2018-10-30 15:47:35FAILED
  
 1) PROVIDE A SURVEY BASED SITE PLAN WHICH SHOWS WHERE
 THE REQUIRED ON-SITE LOADING SPACE IS LOCATED. THE
 ALLEY MAY NOT BE USED AS THE LOADING SPACE AS THERE IS
 NO ACCESS FROM THE ALLEY TO THE BUILDING.
  
 2) PLEASE NOTE THAT YOU MAY NOT USE THE DOOR BY THE
 BREWERY FOR DELIVERY ACCESS SINCE THIS DOOR FACES
 NORTHWOOD ROAD.
  
 3) SHEETS A-1 AND A-2 SHOW AN AREA MARKED AS OFFICE.
 THIS AREA IS MARKED AS KEG ROOM ON THE MECHANICAL AND
 PLUMBING PLANS. ALL PLANS SHALL SHOW SAME, ACCURATE
 NOMENCLATURE.
  
 4) PLEASE NOTE THAT IN ORDER TO MEET THE ALCOHOL
 SEPARATION REQUIREMENTS, YOU MUST HAVE AT LEAST 65
 PERCENT OF THE SQUARE FOOTAGE OF THE FACILITY DEDICATED
 TO THE BREWERY FUNCTION INCLUDING, BUT NOT LIMITED TO,
 BREW HOUSE, BOILING AND WATER TREATMENT AREAS, BOTTLING
 AND KEGGING LINES, MALT MILLING AND STORAGE,
 FERMENTATION TANKS, CONDITION TANKS AND SERVING TANKS.
 OFFICES ARE NOT INCLUDED IN THIS DEFINITION, SO IF THE
 AREA SHOWN ON A-1 AND A-2 IS OFFICE, YOU WILL NOT BE
 ABLE TO SECUCRE AN ALCOHOL LICENSE FOR THE FACILITY.
  
 5) PLEASE BE AWARE THAT THE BUSINESS MUST HOLD ONE OF
 THE FOLLOWING LICENSES ISSUED BY THE FLORIDA DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATIONS, DIVISION OF
 ALCOHOLIC BEVERAGES AND TOBACCO: CMB, AMW, BMWC, DD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]