2018-04-02 09:43:31 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| |
| DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| 561-805-6718 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE |
| 2017 6TH EDITION |
| |
| FIRST REVIEW: |
| |
| 1) SHT. A100 - FIXTURE ELEVATIONS & ELEV. #01- THE |
| TOILET PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7 |
| INCHES AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER |
| CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER AND |
| THE OUTLET SHALL BE A MINIMUM OF 14 INCHES AND A |
| MAXIMUM OF 19 INCHES ABOVE THE FINISH FLOOR. 2017 |
| FBC-ACCESS. SEC. 604.9.6. |
| |
| 2) SHT. A100 - ELEVATIONS #01 & #02 - THE GRAB BARS |
| SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE, |
| NOT TO THE CENTER. 2017 FBC-ACCESS. SEC.609.4. |
| |
| 3) SHT. A100 - ELEV. #02 - THE OPERABLE PARTS OF THE |
| HAND DRYER AND THE SANITARY NAPKIN DISPENSER SHALL BE |
| LOCATED A MAXIMUM OF 48 INCHES ABOVE THE FINISH FLOOR |
| PER 2017 FBC-ACCESS. SECS. 308 & 309. |
| |
| 4) SHOW THE CLEAR INSIDE DIMENSIONS ( LENGTH X WIDTH) |
| OF THE NEW TOILET ROOM. IN ADDITION, SHOW THE CLEAR |
| FLOOR SPACE DIMENSIONS FOR THE WATER CLOSET AND THE |
| LAVATORY. COMPLY WITH 2017 FBC-ACCESS. SECS.604.3 AND |
| 606.2. |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |
| |
| |
| |
| PROVISO: |
| |
| |
| 1. PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH |
| ARE REGULATED BY FAC RULE 9N-3 REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. SPECIFICALLY, |
| STOREFRONT AND DOOR SUBMITTALS. FBC 107.3.4 |
| |
| FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| |