Plan Review Details - Permit 18031284
Plan Review Stops For Permit 18031284
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-30 Cont ID  
Sent By fgiaquin Date 2018-06-30 Time 07:16 Rev Time 0.00
Received By fgiaquin Date 2018-06-30 Time 07:10 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-10 Cont ID  
Sent By fgiaquin Date 2018-04-10 Time 07:05 Rev Time 0.00
Received By fgiaquin Date 2018-04-10 Time 06:47 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-27 Cont ID  
Sent By scaldero Date 2018-06-27 Time 11:33 Rev Time 0.00
Received By scaldero Date 2018-06-27 Time 11:25 Sent To E
Notes
2018-06-27 11:33:05PERMIT #18031284
 REVIEW COMMENTS
  
 1) ADDITIONAL HORN STROBE REQUIRED IN MEETING ROOM
 AREA. (MARKED ON PLAN FOR REFERENCE.)
  
 2) PLEASE NOTE THAT AT NO POINT WERE ADDITIONAL SMOKE
 DETECTORS REQUESTED OR REQUIRED BY THE AHJ, AS
 INCORRECTLY NOTED IN RESUBMISSION NOTES BY CONTRACTOR.
 THE INITIAL REVIEW COMMENTS SPECIFICALLY STATED
 "AUDIO/VISUAL DEVICES".
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 WPBFR
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-30 Cont ID  
Sent By scaldero Date 2018-03-30 Time 11:35 Rev Time 0.00
Received By scaldero Date 2018-03-30 Time 11:30 Sent To E
Notes
2018-03-30 11:35:34PERMIT # 18031284
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) THERE IS NOT SUFFICIENT AUDIO/VISUAL DEVICE COVERAGE
 ON THE SECOND FLOOR.
 THE MEETING ROOM REQUIRES AT LEAST ONE MORE DEVICE AND
 THE LOBBY AREA HAS MULTIPLE POINTS WHERE THE SINGLE
 DEVICE PROVIDED DOES
 NOT REACH AND PROVIDE THE REQUIRED COVERAGE.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-05 Cont ID  
Sent By hmoser Date 2018-07-05 Time 09:12 Rev Time 0.00
Received By hmoser Date 2018-06-22 Time 14:35 Sent To  
Notes
2018-06-25 14:35:52RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-10 Cont ID  
Sent By hmoser Date 2018-04-10 Time 11:09 Rev Time 0.00
Received By hmoser Date 2018-03-28 Time 12:32 Sent To  
Notes
2018-03-29 12:32:45ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By hmoser Date 2018-07-05 Time 09:12 Rev Time 0.00
Received By hmoser Date 2018-07-05 Time 08:45 Sent To I
Notes
2018-07-05 09:12:27PASS PROVISO
 1) REFER TO SECTION 603.3 DETECTORS SHALL MONITOR THE
 INTIRE AIRFLOW
 ACCESS DOORS REQUIRED. 2017 FBC (M)
 2) REFER TO SECTION 606.2.1 DETECTORS MUST BE INSTALLED
 ON THE SUPPLY
 SIDE OF AIR FLOW. 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-10 Cont ID  
Sent By hmoser Date 2018-04-10 Time 11:09 Rev Time 0.00
Received By hmoser Date 2018-04-10 Time 11:09 Sent To  
Notes
***NONE***