Plan Review Details - Permit 18031224
Plan Review Stops For Permit 18031224
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 13:33 Rev Time 0.00
Received By cthroop Date 2018-06-15 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-26 Cont ID  
Sent By cthroop Date 2018-04-26 Time 07:50 Rev Time 0.00
Received By cthroop Date 2018-04-26 Time 07:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-30 Cont ID  
Sent By jwitmer Date 2018-03-30 Time 16:25 Rev Time  
Received By jwitmer Date 2018-03-30 Time 15:44 Sent To  
Notes
2018-03-30 16:25:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18031224
 ADD: 8993 OKEECHOBEE BLVD. SUITE: 112
 CONT: TBD/ TO BE DETERMINED
 TEL: 404-904-4941
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 30/ 2018
 ACTION: DENIED
  
 1) THE TITLESHEET T.1 INDICATES THIS BUILDING IS TYPE
 II-B CONSTRUCTION. SHEET A1 NOTES WALL TYPE P3
 CONSTRUCTION 8FEET TALL AND OF WOOD CONSTRUCTION, 2X4
 STUDS @16 INCHES O.C. PLEASE REVIEW THE REQUIRED
 CONSTRUCTION FOR TYPE II-B CONSTRUCTION. SEE :
  
 2017 FBC-B 603.1.3.(1) FIRE-RETARDANT-TREATED WOOD
 SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 EXCEPTIONS:
 11. PARTITIONS DIVIDING PORTIONS OF STORES, OFFICES OR
 SIMILAR PLACES OCCUPIED BY ONE TENANT ONLY AND THAT DO
 NOT ESTABLISH A CORRIDOR SERVING AN OCCUPANT LOAD OF 30
 OR MORE SHALL BE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD, 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION OR OF WOOD PANELS OR
 SIMILAR LIGHT CONSTRUCTION UP TO 6 FEET (1829 MM) IN
 HEIGHT.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-12 Cont ID  
Sent By ppetty Date 2018-06-12 Time 13:20 Rev Time 0.00
Received By ppetty Date 2018-06-12 Time 13:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By jpearson Date 2018-05-02 Time 11:57 Rev Time 0.00
Received By jpearson Date 2018-05-02 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-02 Cont ID  
Sent By jpearson Date 2018-04-02 Time 09:11 Rev Time 0.00
Received By jpearson Date 2018-04-02 Time 08:44 Sent To  
Notes
2018-04-02 09:11:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS A 10.4 KW EWH ON # 8 WIRE AND A 20 AMP
 BREAKER. 10,400 / 208 = 51.92 AMPS. THE BREAKER AND
 WIRE SIZE STATED ARE NOT SUFFICIENT FOR THIS LOAD.
 PROVIDE CORRECTION. NEC 310.15(B)(16), 240.4, 210.19,
 210.20
 2. PROVIDE DETAILS OF THE METHOD OF SHUTDOWN FOR THE
 ELECTRICAL EQUIPMENT LOCATED UNDER THE HOOD PER NFPA
 96. NFPA 96, SECTION 10.4.1, WPB FBC 107.2.1
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By scaldero Date 2018-06-04 Time 12:34 Rev Time 0.00
Received By scaldero Date 2018-06-04 Time 12:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-30 Cont ID  
Sent By scaldero Date 2018-03-30 Time 11:55 Rev Time 0.00
Received By scaldero Date 2018-03-30 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 13:33 Rev Time 0.00
Received By cthroop Date 2018-05-31 Time 12:54 Sent To I
Notes
2018-06-01 12:54:37B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-05-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-24 Time 14:59 Sent To  
Notes
2018-04-25 15:00:15B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 17:44 Rev Time 0.00
Received By gjohnson Date 2018-03-27 Time 14:05 Sent To  
Notes
2018-03-28 14:06:01B10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-30 Cont ID  
Sent By jwitmer Date 2018-03-30 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2018-03-30 Time 16:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-06-07 Cont ID  
Sent By ccole Date 2018-06-07 Time 13:21 Rev Time 0.00
Received By ccole Date 2018-06-05 Time 11:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By ccole Date 2018-05-02 Time 14:27 Rev Time 0.00
Received By ccole Date 2018-05-02 Time 14:27 Sent To I
Notes
2018-05-02 14:30:48MECHANICAL PROVISO:
  
 1) THE TYPE II EXHAUST HOOD FOR THE POPCORN MACHINE
 SHALL BE A DEFERRED SUBMITTAL UNDER THE MAIN PERMIT.
  
 CCOLE- 5/2/18
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-04 Cont ID  
Sent By ccole Date 2018-04-04 Time 09:40 Rev Time 0.00
Received By ccole Date 2018-04-04 Time 07:44 Sent To  
Notes
2018-04-04 09:55:441ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #18031224
 4/4/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POPCORN
 MACHINE AND LIST THE MAKE AND MODEL ON THE PLANS.
  
 2) PROVIDE A MINIMUM VENILATION SCHEDULE THAT LISTS THE
 REQUIRED AND PROVIDED CFMS OF VENTILATION AIR FOR EACH
 ROOM OR SPACE INCLUDING THE SALES AND STORAGE/PREP
 AREAS- SEE TABLE 403.3.
  
 3) REFER TO SECTION 508.1.2 AIR BALANCE AND SHOW
 COMPLIANCE-
  
 508.1.2 AIR BALANCE.
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION.
  
 3) ADVISORY: A SEPARATE PERMIT IS REQUIRED FOR THE
 POPCORN MACHINE EXHAUST HOOD, HOWEVER IT IS IMPORTANT
 TO NOTE THAT THE HVAC DESIGN FOR THE MAIN FACILITY
 SHALL BE IN COMPLIANCE WITH SECTION C403.2.8 FBC-17
 ENERGY CONSERVATION-
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS.
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-15 Cont ID  
Sent By gjohnson Date 2018-06-15 Time 09:19 Rev Time 0.00
Received By gjohnson Date 2018-06-15 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By gjohnson Date 2018-05-02 Time 14:37 Rev Time 0.00
Received By gjohnson Date 2018-05-02 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 17:31 Rev Time 0.00
Received By gjohnson Date 2018-04-06 Time 15:57 Sent To  
Notes
2018-04-06 17:44:311ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMPARTMENT
 SINK, HAND SINK AND MOP SINK. PER FBC PL 1003.3.1 AND
 CITY OF WPB CODE OF ORDINANCES 90-125(7)(C)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  