Plan Review Stops For Permit 18031044 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-12 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-12 |
Time |
10:34 |
Sent To |
|
|
Notes |
2018-07-12 10:38:42 | ****PROVISOS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC B 1803.5, SOILS ARE UNAVAILABLE AT TIME OF | | PERMITTING. PRIOR TO FOUNDATION CONCRETE POUR, SEOR IS | | TO REVIEW SOILS REPORT. PROVIDE THE REVIEWED SOILS AS A | | SUBMITTAL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-15 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-15 |
Time |
08:17 |
Sent To |
|
|
Notes |
2018-06-15 09:52:25 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SHEET SD4, FOUNDATION ITEM 1A, REVISE TO INCORPORATE | | THE SOILS REPORT REFERENCE AND PROVIDE GEOTECHNICAL | | REPORT, FBC B 1803.5. | | | | 2. PROVIDE STRUCTURAL DETAIL FOR THE RAMP, FBC 107. | | | | 3. SPECIFY PRESSURES FOR COMPONENTS & CLADDING, FBC | | 1603.1.4. | | | | 4. SEE THRESHOLD REVIEW. | | | | 5. ITEMS #1 - #3 CAN BE PROVISO ITEMS UPON REQUEST. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-04-04 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-04-02 |
Time |
15:48 |
Sent To |
|
|
Notes |
2018-04-04 13:12:15 | ****PLAN REVIEW COMMENTS**** | | | | ART LANGE BUILDING PLANS EXAMINER | | | | DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS STREET | | WEST PALM BEACH, FL 33402 | | | | 561-805-6718 [email protected] | | | | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | 2017 6TH EDITION | | | | 1. ON PAGE 021 OW LH 207 UPDATE TO THE CURRENT CODE | | CYCLE. SEE NOTES ON THIS PAGE IN VARIOUS LOCATIONS. | | | | PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL BE | | DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH | | EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY | | CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE | | REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE. | | | | 2. PROVIDE ENGINEERING FOR TRELLIS AND PERGOLAS. | | | | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | 3. PROVIDE DETAILS FOR ADA RAMP SHOWN ON PAGES 019 OW | | LH 207 AND 010 OW LH 1. | | | | A) SHOW THE SLOPE 405.1 | | B) HANDRAIL DETAILS 405.8 | | C) EDGE PROTECTION 405.9 | | D) EXTENDED FLOOR OR GROUND SURFACE. SEE DETAIL 405.9.1 | | | | 3. FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, STORE FRONT SUBMITTALS. | | ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED | | SUBMITTAL BY LISTING THEM ON THE COVER SHEET. | | | | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | FOR REVIEW BY THE BUILDING OFFICIAL. | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | OFFICIAL. | | | | 4. NOTE: SEPARATE PERMITS REQUIRED FOR LANDSCAPING, | | SIGNS AND FENCES. | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | THE PERMIT PACKAGE. | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-06-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-06-12 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-06-01 |
Time |
11:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-04-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-04-09 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-04-09 |
Time |
11:37 |
Sent To |
|
|
Notes |
2018-04-09 11:39:22 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | THERE IS A SYMBOL OF A CIRLE WITH A TRIANGLE IN THE | | MIDDLE NOT SHOWN ON LEGEND. | | | | NEED TO SHOW LOCATION OF TRANSFROEMRS AND TIME CLOCKS | | FOR CONTROL. | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-07-12 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-07-12 |
Time |
12:31 |
Sent To |
|
|
Notes |
2019-01-25 11:38:44 | PROVISO COMPLIED WITH 1/25/19 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | 2018-07-12 12:33:19 | GAS PROVISO: | | 1. PLEASE CORRECT THE FOLLOWING PRIOR TO ROUGH | | INSPECTION. | | A) THE BTU LOADS AND THE DEVELOPED LENGTHS ON THE GAS | | FLOOR PLAN AND RISER DO NOT MATCH THE BTU LOAD ON THE | | SIZING CHART OR MANUFACTURE SPECS. PER FBC FG SEC 402 | | B) THE 1? CSST THAT IS SUPPLING 2 BBQ GRILLS IS UNDER | | SIZED AT 200?DEVELOPED LENGTH. IT SHALL BE 11/4 EHD 37 | | PER FBC FG TABLE 402.4(16) | | | | | | GAS NOTE: | | 1. THE BBQ GRILL SHALL COMPLY WITH FBC FG | | 301.3LISTED AND LABELED. | | APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND | | LABELED FOR THE APPLICATION IN WHICH THEY ARE USED | | UNLESS OTHERWISE APPROVED IN ACCORDANCE WITH SECTION | | 104 OF THE FLORIDA BUILDING CODE, BUILDING. THE | | APPROVAL OF UNLISTED APPLIANCES IN ACCORDANCE WITH | | SECTION 104 OF THE FLORIDA BUILDING CODE, BUILDING | | SHALL BE BASED ON APPROVED ENGINEERING EVALUATION. | | 301.4LABELING. | | LABELING SHALL BE IN ACCORDANCE WITH THE PROCEDURES SET | | FORTH IN SECTIONS 301.4.1 THROUGH 301.4.2.3. | | 623.1COOKING APPLIANCES. | | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT | | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, | | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND | | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI | | Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S | | INSTRUCTIONS. | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-06-12 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-12 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-12 |
Time |
14:01 |
Sent To |
|
|
Notes |
2018-06-12 14:04:29 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | GAS COMMENTS: PREVIOUS COMMENTS NOT COMPLIED | | | | 1. PROVIDE A GAS RISER SHOWING THE LENGTH OF EACH | | SECTION OF PIPE, THE TYPE OF PIPE , PRESSURE OF THE | | SYSTEM AND THE EXISTING AND NEW BTU LOAD ON THE PIPE | | AND FOR EACH NEW APPLIANCE. PER FBC-2014 FUEL GAS, | | SECS. 402.4.1, 402.4.2. | | | | 2. PROVIDE THE MANUFACTURE SPECIFICATION FOR THE NEW | | GAS APPLIANCES AND PRESSURE REGULATORS SHALL BE LISTED | | FOR EXTERIOR USE. TO VERIFY COMPLIANCE WITH STANDARDS | | NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-04-19 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-19 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-19 |
Time |
10:16 |
Sent To |
|
|
Notes |
2018-04-19 10:24:09 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | GAS COMMENTS: | | | | 1. PROVIDE A GAS RISER SHOWING THE LENGTH OF EACH | | SECTION OF PIPE, THE TYPE OF PIPE , PRESSURE OF THE | | SYSTEM AND THE EXISTING AND NEW BTU LOAD ON THE PIPE | | AND FOR EACH NEW APPLIANCE. PER FBC-2014 FUEL GAS, | | SECS. 402.4.1, 402.4.2. | | | | 2. PROVIDE THE MANUFACTURE SPECIFICATION FOR THE NEW | | GAS APPLIANCES AND PRESSURE REGULATORS SHALL BE LISTED | | FOR EXTERIOR USE. TO VERIFY COMPLIANCE WITH STANDARDS | | NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 3. PLEASE LIST THE SIZING TABLE FROM FBC FUEL GAS 2014 | | USED TO SIZE SYSTEM. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-17 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2018-07-17 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-07-06 |
Time |
15:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-15 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-18 |
Time |
13:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-07 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-05-07 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-03-29 |
Time |
13:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-06-12 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-12 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-12 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-04-19 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-04-19 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-19 |
Time |
06:52 |
Sent To |
|
|
Notes |
2018-04-19 10:15:53 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHOW NEW LOCATION OF POOL SHOWER. PER WPB AMEND TO | | FBC 107.2.1 | | | | 2. SHT. P1.01 AND P1.02 THE THE SHEETS HAVE SANITARY | | NOTES IS THERE GOING TO BE MODIFICATIONS TO THE | | SANITARY SYSTEM OR ONLY STORM, POOL PIPING , WATER AND | | GAS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | 3. SHT. P1.01 PROVIDE DETAILS FOR THE 8" DRAIN LISTED | | UNDER NOTE #3 AND THE PLANTER DRAINS. PER WPB AMEND TO | | FBC 107.2.1 | | | | 4. SHT. P1.01 AND P1.02 PROVIDE SIZING CALCULATIONS FOR | | THE NEW AND EXISTING STORM DRAINS AND PROVIDE ISO | | SHOWING SIZING AND LOAD. PER WPB AMEND TO FBC 107.2.1 | | | | 5. SHT. P1.02 NOTE # PROVIDE PIPING DIAGRAM FOR POOL | | PIPING OR REMOVE IF POOL PING IS BEING DONE UNDER | | SEPARATE PERMIT. PER WPB AMEND TO FBC 107.2.1 | | | | 6. PROVIDE PLUMBING SITE PLAN SITE PLAN. PER WPB AMEND | | TO FBC 107.2.1 | | | | 7. P1.02 PLAN SHEET IS LABELED AS BOTH POLL AND | | FOUNTAIN AREA PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 8. THE PLUMBING SHEET INDEX LIST P1.03 EQUIPMENT ROOM | | THIS SHEET IS MISSING FROM PLAN SET PLEASE CLARIFY. PER | | WPB AMEND TO FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-12 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-12 |
Time |
10:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-15 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-15 |
Time |
08:18 |
Sent To |
|
|
Notes |
2018-06-15 08:24:20 | SAMANTHA HILL | | 561-805-6724 | | [email protected] | | | | ALL SHEETS, ALL TRADES HAVE BEEN VERIFIED AND COMPLY | | WITH FS471 / FS481. | | | | A NEW SIGNATURE REVIEW IS REQUIRED IN THE NEXT REVIEW | | CYCLE FOR NEW SHEETS. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
aclange |
Date |
2018-04-04 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
aclange |
Date |
2018-04-04 |
Time |
13:12 |
Sent To |
|
|
Notes |
2018-04-04 13:16:19 | PLUMBING, GAS AND ELECTRICAL PAGES NOT DIGITALLY | | SIGNED. | | | | 61G1-16.001 ARCHITECT?S AND INTERIOR DESIGNER?S SEAL. |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
4 |
Status |
P |
Date |
2018-08-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-25 |
Time |
08:02 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-25 |
Time |
08:01 |
Sent To |
|
|
Notes |
2018-08-02 08:02:46 | RECEIVED NEW SI AGREEMENT (ADDRESSED PROVISO) | | | | CONTRACTOR - WEITZ | | JOSEPH MANCUZZI, PE, SI | | ERIC HERNANDEZ, BN3465 | | | | | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
3 |
Status |
P |
Date |
2018-07-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-16 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-16 |
Time |
08:37 |
Sent To |
|
|
Notes |
2018-07-16 08:40:33 | PROVISO, PROVIDE NEW SI AGREEMENT | | | | CONTRACTOR - WEITZ | | JOSEPH MANCUZZI, PE, SI | | ERIC HERNANDEZ, BN3465 | | | | | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
F |
Date |
2018-07-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-12 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-12 |
Time |
11:05 |
Sent To |
|
|
Notes |
2018-07-12 11:05:40 | NEED NEW SI AGREEMENT ON NEW FORM WITH CONTRACTOR'S | | SIGNATURE, NEED PERMIT APPLICATION TO VERIFY | | CONTRACTOR'S SIGNATURE ON SI AGREEMENT | | | | THRESHOLD IN SPECTION PLAN, THRESHOLD STATEMENT ON PLAN | | OK | | | | | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-15 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-15 |
Time |
09:22 |
Sent To |
|
|
Notes |
2018-06-15 09:32:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 553.79(5), IT APPEARS THAT APPLICANT IS PROPOSING | | (LIMITED) STRUCTURAL RENOVATION TO A THRESHOLD | | BUILDING. IS THIS CORRECT? IF YES, THE FOLLOWING IS | | REQUIRED: | | | | 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT | | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO | | [email protected]. | | | | 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL | | PROPOSED INSPECTORS. | | | | 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT | | REQUIRED BY FS553.79(7)(D). | | | | 4. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A). | | | | IF ENGINEER FEELS THAT THIS RENOVATION DOES NOT FALL | | UNDER THE DEFINITION OF "THRESHOLD", PLEASE HAVE HIM | | CONTACT ME. | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-07-17 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-07-17 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-07-17 |
Time |
08:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-06-04 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-06-04 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2018-06-04 15:26:41 | SITE PLAN APPROVAL PROCESS SHALL BE COMPLETED BEFORE | | PERMIT CAN BE APPROVED BY ZONING. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-05-04 |
|
|
Cont ID |
|
Sent By |
AA |
Date |
2018-05-04 |
Time |
08:46 |
Rev Time |
|
Received By |
aaponte |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2018-05-04 08:46:54 | MINOR SITE PLAN AMENDMENT SHALL BE APPROVED BEFORE A | | BUIDING PERMIT CAN BE ISSUED. |
|
|