Plan Review Details - Permit 18030944
Plan Review Stops For Permit 18030944
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-14 Cont ID  
Sent By cthroop Date 2018-08-14 Time 11:15 Rev Time 0.00
Received By cthroop Date 2018-08-14 Time 06:54 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-18 Cont ID  
Sent By cthroop Date 2018-06-18 Time 09:24 Rev Time 0.00
Received By cthroop Date 2018-06-18 Time 08:54 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By jleahy Date 2018-04-24 Time 09:02 Rev Time 0.00
Received By cthroop Date 2018-04-24 Time 08:45 Sent To  
Notes
2018-04-24 09:05:22BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SCOPE OF WORK ON PLANS SPECIFIES INSTALLATION OF A
 35KW GENERATOR.
 2. APPLICATION IS FOR THE INSTALLATION OF MA 30KW
 GENERATOR. PLEASE CLARIFY.
 3. VALUE OF PROPOSED WORK APPEARS LOW.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-08-11 Cont ID  
Sent By jleahy Date 2018-08-11 Time 12:19 Rev Time 0.00
Received By jleahy Date 2018-08-11 Time 12:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-21 Cont ID  
Sent By jleahy Date 2018-06-21 Time 16:34 Rev Time 0.00
Received By jleahy Date 2018-06-21 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By jleahy Date 2018-06-06 Time 17:26 Rev Time 0.00
Received By jleahy Date 2018-06-06 Time 17:27 Sent To B
Notes
2018-06-06 17:26:33FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PERMIT STILL SHOWS 30 KW GENERATOR.
  
  
 PLEASE INCLUDE THE COST OF THE CUSTOMER SUPPLIED
 GENERATOR AND TRANSFER SWITCH IN THE COST OF THE JOB.
  
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 .
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-14 Cont ID  
Sent By fgiaquin Date 2018-04-14 Time 08:28 Rev Time 0.00
Received By jleahy Date 2018-04-14 Time 07:26 Sent To B
Notes
2018-04-16 16:02:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 VALUE FOR WORK SHOWN IS LOW.
  
 PERMIT STATES A 30KW GENERATOR AND PLANS CALL FOR A
 35KW
  
 NEED TO SUBMIT A VOLTAGE DROP CALCULATION ON THE
 FEEDERS FROM THE GENERATOR.
  
 NEED TO SUBMIT A FAULT CURRENT CALCULATION FOR THE
 EXISTING SERVICE EQUIPMENT TO BE USED IN THIS
 INSTALLATION.
  
 LOAD CALCULATION FOR GENERATOR.
  
 WIRE SIZES SHOWN COPPER OR ALUMINUM?
  
 HOW DO YOU GET TO THE ROOF, STAIRWELL?????
2018-04-14 08:28:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 14:01 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 14:00 Sent To E
Notes
2018-07-31 14:01:27SEE ALL PREVIOUS REVIEW COMMENTS BY P. LEDUC ON
 5/31/18.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-31 Cont ID  
Sent By pleduc Date 2018-05-31 Time   Rev Time 0.00
Received By pleduc Date 2018-05-31 Time 12:48 Sent To E
Notes
2018-05-31 14:19:182ND REVIEW COMMENTS:
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED INSTALLATION SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA? 37
  
 STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION
  
 PLEASE ENSURE COMPLIANCE.
  
  
 2) NO DIMENSION IS INDICATED FOR THE WIDTH FROM THE
 EXISTING BUILDING,
  
 PER NFPA 37
  
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
 PLEASE ENSURE COMPLIANT SEPARATION AND/OR FIRE
 RESISTNACE RATING.
  
 3) THERE IS NO INDICATION OF COMPLAINCE WITH NFPA 54
  
 PER NFPA 37
  
 5.1* GAS PIPING.
 5.1.1 GAS PIPING SHALL BE INSTALLED IN ACCORDANCE WITH
 THE
 FOLLOWING METHODS:
 (1) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES EQUAL TO
 OR LESS
 THAN A GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF
 125 PSI) SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 54,
 NATIONAL FUEL GAS CODE.
 (2) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES IN EXCESS
 OF A
 GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF 125 PSI),
 OTHER THAN LP-GAS SYSTEMS, SHALL BE INSTALLED IN
 ACCORDANCE
 WITH ANSI/ASME B31.3, PROCESS PIPING.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By pleduc Date 2018-04-09 Time   Rev Time 0.00
Received By pleduc Date 2018-04-09 Time 13:01 Sent To E
Notes
2018-04-09 14:37:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED INSTALLATION SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA? 37
  
 STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION
  
 PLEASE ENSURE COMPLIANCE.
  
  
 2) NO DIMENSION IS INDICATED FOR THE WIDTH FROM THE
 EXISTING BUILDING,
  
 PER NFPA 37
  
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
 PLEASE ENSURE COMPLIANT SEPARATION AND/OR FIRE
 RESISTNACE RATING.
  
 3) THERE IS NO INDICATION OF COMPLAINCE WITH NFPA 54
  
 PER NFPA 37
  
 5.1* GAS PIPING.
 5.1.1 GAS PIPING SHALL BE INSTALLED IN ACCORDANCE WITH
 THE
 FOLLOWING METHODS:
 (1) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES EQUAL TO
 OR LESS
 THAN A GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF
 125 PSI) SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 54,
 NATIONAL FUEL GAS CODE.
 (2) ALL FUEL GAS SYSTEMS AT SERVICE PRESSURES IN EXCESS
 OF A
 GAUGE PRESSURE OF 860 KPA (GAUGE PRESSURE OF 125 PSI),
 OTHER THAN LP-GAS SYSTEMS, SHALL BE INSTALLED IN
 ACCORDANCE
 WITH ANSI/ASME B31.3, PROCESS PIPING.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-14 Cont ID  
Sent By lcrespo Date 2018-08-13 Time 17:39 Rev Time 0.00
Received By lcrespo Date 2018-08-13 Time 17:39 Sent To  
Notes
2018-08-13 17:40:0108/13/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-19 Cont ID  
Sent By lcrespo Date 2018-06-19 Time 16:22 Rev Time 0.00
Received By lcrespo Date 2018-06-19 Time 16:22 Sent To  
Notes
2018-06-19 16:24:3006/19/2018 2ND REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. SHEET P-1 UNDER NOTES AND GAS PIPE DESIGN
 INFORMATION ITEM 1 NEED THE CHANGE FROM 2014 FBC FG TO
 2017 FBC FG, PER WPB AMEND TO FBC 107.2.1.
  
 2. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 SHALL BE ONSIDE FOR FINAL GAS INSPECTION. THE GENERATOR
 SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 3. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS.
 ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED,
 THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5
 FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE
 FOLLOWING CONDITIONS EXIST;
  
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5
 FT. FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE
 RATING OF AT LEAST 1 HOUR.
  
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 4. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
  
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1.
  
 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-14 Cont ID  
Sent By cthroop Date 2018-08-14 Time 11:15 Rev Time 0.00
Received By cthroop Date 2018-07-24 Time 13:59 Sent To  
Notes
2018-07-25 13:59:46RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By lcrespo Date 2018-06-19 Time 16:24 Rev Time 0.00
Received By lcrespo Date 2018-05-21 Time 13:45 Sent To  
Notes
2018-06-16 11:51:056/16/ TO CT DESK
  
2018-05-22 13:45:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 09:05 Rev Time 0.00
Received By cthroop Date 2018-03-22 Time 13:04 Sent To I
Notes
2018-03-23 13:04:50ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-07-30 Time   Rev Time 0.00
Received By pgreilic Date 2018-07-30 Time 11:38 Sent To FIRE
Notes
2018-07-30 11:38:28PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By mc to pg Date 2018-05-30 Time   Rev Time 0.00
Received By pgreilic Date 2018-05-30 Time 12:22 Sent To FIRE
Notes
2018-05-30 12:22:48LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-04-06 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-06 Time 10:57 Sent To FIRE
Notes
2018-04-06 10:58:08LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]