Plan Review Details - Permit 18030590
Plan Review Stops For Permit 18030590 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-05-12 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-05-12 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-05-12 |
Time |
10:46 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-03-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-03-22 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-03-22 |
Time |
14:30 |
Sent To |
|
|
Notes |
2018-03-22 14:55:01 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC 107, TOO MANY SHEETS WERE SUBMITTED. | | SPECIFICATIONS, GENERAL NOTES, ARE NOT REQUIRED FOR AN | | INTERIOR DEMO PERMIT. MUCH OF THE INFORMATION IS NOT | | APPLICABLE, AND THE PORTION THAT DEMONSTRATES CODE | | COMPLIANCE AND IS APPLICABLE SHOULD BE ABLE TO BE | | CONDENSED ONTO THE PAGE WHICH SHOWS ACTUAL WORK | | PROPOSED. | | | | 2. FBC B 3006, IT APPEARS THAT AN ELEVATOR LOBBY IS | | REQUIRED. DEMO PLAN PROPOSES TO REMOVE A DOOR FOR THE | | ELEVATOR LOBBY. REVISE TO RETAIN THE REQUIRED ELEVATOR | | LOBBY OR REVISE TO STATE WHY AN ELEVATOR LOBBY IS NOT | | REQUIRED. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-05-15 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-05-15 |
Time |
07:20 |
Sent To |
I |
|
Notes |
2018-05-15 07:23:51 | DEMO ONLY | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-04-04 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-04-04 |
Time |
15:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-05-11 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-05-15 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-05-11 |
Time |
11:01 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-03-26 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-03-26 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-03-26 |
Time |
11:55 |
Sent To |
E |
|
Notes |
2018-03-26 12:00:53 | PERMIT # 18030590 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND | | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF | | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE | | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL | | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE | | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | 4) REVIEW AND RESPOND TO BUILDING DEPT. REVIEW | | COMMENTS. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-05-15 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-05-09 |
Time |
13:22 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-04-04 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-03-14 |
Time |
13:05 |
Sent To |
|
|
Notes |
2018-03-22 14:55:20 | 3/22 TO FIRE | | | 2018-03-15 13:06:02 | ROUTED TO SHILL |
|
|
|