Plan Review Stops For Permit 18030566 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2018-04-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-04-05 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-04-05 |
Time |
11:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-04-04 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-04-04 |
Time |
08:56 |
Sent To |
|
|
Notes |
2018-04-04 10:04:39 | COMMERCIAL ROOFING, FOURTH BUILDING REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017). | | | | 1- REVISE RAS 117 CALCULATIONS SUBMITTED: | | A) NEED TO HAVE THE CORRECT ADDRESS OF THE JOB. THIS | | JOB IS NOT IN POMPANO BEACH SEC. 107.2.1 CITY | | AMENDMENTS. | | | | B) ENGINEER TO REVISE THE "CONSTRUCTION TYPE". THIS IS | | A RECOVER ROOFING NOT RE-ROOF. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2018-03-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-03-28 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-28 |
Time |
16:44 |
Sent To |
|
|
Notes |
2018-03-28 16:45:46 | COMMERCIAL ROOFING, THIRD BUILDING REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017). | | | | 1- NOA 15-0731.12 SUBMITTED NOW IS THE SAME NOA THAT | | WAS SUBMITTED THE FIRST TIME. THE SAME COMMENTS FORM | | THE FIRST REVIEW APPLY AGAIN: "PERMIT APPLICATION IS | | FOR ROOF RECOVER. NOA 15-0731.12 SUBMITTED IS NOT FOR | | RECOVER APPLICATIONS. PROVIDE PRODUCT APPROVAL (2 | | COPIES) FOR RECOVER APPLICATIONS AND CLEARLY IDENTIFY | | SELECTED ASSEMBLY. FAC 61G1520-3.001.". | | | | 2- REVISE RAS 117 CALCULATIONS SUBMITTED. NEED TO BE | | REVISED REFERENCING THE NEW CURRENT PRODUCT APPROVAL AS | | REQUIRED BY ITEM #1 ABOVE. SEC. 1609 FBC-BUILDING. | | ALSO, ENGINEER TO CHECK THE DESIGN PRESSURES OF | | SELECTED ASSEMBLY AND CONSTRUCTION TYPE TO MATCH | | SELECTED ASSEMBLY. COORDINATE WITH ITEM #1 ABOVE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-03-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-03-21 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-21 |
Time |
09:57 |
Sent To |
|
|
Notes |
2018-03-21 10:34:51 | COMMERCIAL ROOFING, SECOND BUILDING REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017). | | | | 1- ROOFING RECOVER DECK NOA 15-0731.14 SUBMITTED | | EXPIRED ON 05/16/17. NEED TO PROVIDE CURRENT PRODUCT | | APPROVAL. FAC 61G1520-3.001. | | | | 2- REVISE RAS 117 CALCULATIONS SUBMITTED. NEED TO BE | | REVISED REFERING TO NEW CURRENT PRODUCT APPROVAL AS | | REQUIRED BY ITEM #1 ABOVE. SEC. 1609 FBC-BUILDING. | | | | 3- RAS 117 CALCULATIONS AND FASTENER WITHDRAWAL | | RESISTANCE TEST 105 NEED TO HAVE THE ENGINEER'S | | ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS | | FOR PUBLIC RECORDS AS REQUIRED BY FAC 61G15-23.001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-03-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-03-14 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-13 |
Time |
17:45 |
Sent To |
|
|
Notes |
2018-03-14 08:54:53 | COMMERCIAL ROOFING, BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017). | | | | 1- PERMIT APPLICATION IS FOR ROOF RECOVER. NOA | | 15-0731.12 SUBMITTED IS NOT FOR RECOVER APPLICATIONS. | | PROVIDE PRODUCT APPROVAL (2 COPIES) FOR RECOVER | | APPLICATIONS AND CLEARLY IDENTIFY SELECTED ASSEMBLY. | | FAC 61G1520-3.001. | | | | 2- NOA SUBMITTED IS MISSING THE LAST PAGE THAT LIST ALL | | GENERAL AND SYSTEM LIMITATIONS. PROVIDE COMPLETE NOA. | | FAC 61G1520-3.001. | | | | 3- SUBMIT ALL THE INFORMATION REQUIRED BY ALL THE | | GENERAL AND SYSTEMS LIMITATIONS REQUIRED IN THE PRODUCT | | APPROVAL SUBMITTED FOR RECOVER APPLICATIONS. FOR | | EXAMPLE, PULL OUT TESTING (TAS 105), MOISTURE SURVEYS | | (TAS 126), ETC. REVIEW ALL THE SYSTEMS LIMITATIONS AND | | PROVIDE ALL L REQUIRED TESTING (2 COPIES). SEC. | | 107.2.1.2 CITY AMENDMENTS. | | | | 4- PROVIDE RAS 117 CALCULATIONS (2 COPIES) IF SELECTED | | ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES AND IF | | SELECTED ASSEMBLY ALLOWS FASTENER ENHANCEMENT. SEC. | | 1609 FBC-BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2018-04-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-04-05 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-04-05 |
Time |
11:01 |
Sent To |
|
|
Notes |
2018-04-05 11:02:21 | RAS 117 CALCULATIONS SUBMITTAL. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-04-04 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-30 |
Time |
13:59 |
Sent To |
I |
|
Notes |
2018-04-02 13:59:51 | RESUB ROUTED TO JGOMEZ |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-03-28 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-03-28 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-23 |
Time |
13:40 |
Sent To |
I |
|
Notes |
2018-03-26 13:40:14 | RESUB ROUTED TO JGOMEZ |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-03-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-03-21 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-19 |
Time |
09:37 |
Sent To |
I |
|
Notes |
2018-03-20 09:37:43 | RESUB ROUTED TO JGOMEZ |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-03-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-03-14 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-03-13 |
Time |
16:24 |
Sent To |
I |
|
Notes |
2018-03-13 16:24:38 | JGOMEZ |
|
|