Plan Review Details - Permit 18030566
Plan Review Stops For Permit 18030566
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-04-05 Cont ID  
Sent By jgomez Date 2018-04-05 Time 11:14 Rev Time 0.00
Received By jgomez Date 2018-04-05 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-04-04 Cont ID  
Sent By jgomez Date 2018-04-04 Time 10:04 Rev Time 0.00
Received By jgomez Date 2018-04-04 Time 08:56 Sent To  
Notes
2018-04-04 10:04:39COMMERCIAL ROOFING, FOURTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- REVISE RAS 117 CALCULATIONS SUBMITTED:
 A) NEED TO HAVE THE CORRECT ADDRESS OF THE JOB. THIS
 JOB IS NOT IN POMPANO BEACH SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) ENGINEER TO REVISE THE "CONSTRUCTION TYPE". THIS IS
 A RECOVER ROOFING NOT RE-ROOF. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-03-28 Cont ID  
Sent By jgomez Date 2018-03-28 Time 17:29 Rev Time 0.00
Received By jgomez Date 2018-03-28 Time 16:44 Sent To  
Notes
2018-03-28 16:45:46COMMERCIAL ROOFING, THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- NOA 15-0731.12 SUBMITTED NOW IS THE SAME NOA THAT
 WAS SUBMITTED THE FIRST TIME. THE SAME COMMENTS FORM
 THE FIRST REVIEW APPLY AGAIN: "PERMIT APPLICATION IS
 FOR ROOF RECOVER. NOA 15-0731.12 SUBMITTED IS NOT FOR
 RECOVER APPLICATIONS. PROVIDE PRODUCT APPROVAL (2
 COPIES) FOR RECOVER APPLICATIONS AND CLEARLY IDENTIFY
 SELECTED ASSEMBLY. FAC 61G1520-3.001.".
  
 2- REVISE RAS 117 CALCULATIONS SUBMITTED. NEED TO BE
 REVISED REFERENCING THE NEW CURRENT PRODUCT APPROVAL AS
 REQUIRED BY ITEM #1 ABOVE. SEC. 1609 FBC-BUILDING.
 ALSO, ENGINEER TO CHECK THE DESIGN PRESSURES OF
 SELECTED ASSEMBLY AND CONSTRUCTION TYPE TO MATCH
 SELECTED ASSEMBLY. COORDINATE WITH ITEM #1 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 10:34 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 09:57 Sent To  
Notes
2018-03-21 10:34:51COMMERCIAL ROOFING, SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- ROOFING RECOVER DECK NOA 15-0731.14 SUBMITTED
 EXPIRED ON 05/16/17. NEED TO PROVIDE CURRENT PRODUCT
 APPROVAL. FAC 61G1520-3.001.
  
 2- REVISE RAS 117 CALCULATIONS SUBMITTED. NEED TO BE
 REVISED REFERING TO NEW CURRENT PRODUCT APPROVAL AS
 REQUIRED BY ITEM #1 ABOVE. SEC. 1609 FBC-BUILDING.
  
 3- RAS 117 CALCULATIONS AND FASTENER WITHDRAWAL
 RESISTANCE TEST 105 NEED TO HAVE THE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS AS REQUIRED BY FAC 61G15-23.001.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jgomez Date 2018-03-14 Time 09:19 Rev Time 0.00
Received By jgomez Date 2018-03-13 Time 17:45 Sent To  
Notes
2018-03-14 08:54:53COMMERCIAL ROOFING, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PERMIT APPLICATION IS FOR ROOF RECOVER. NOA
 15-0731.12 SUBMITTED IS NOT FOR RECOVER APPLICATIONS.
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR RECOVER
 APPLICATIONS AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 FAC 61G1520-3.001.
  
 2- NOA SUBMITTED IS MISSING THE LAST PAGE THAT LIST ALL
 GENERAL AND SYSTEM LIMITATIONS. PROVIDE COMPLETE NOA.
 FAC 61G1520-3.001.
  
 3- SUBMIT ALL THE INFORMATION REQUIRED BY ALL THE
 GENERAL AND SYSTEMS LIMITATIONS REQUIRED IN THE PRODUCT
 APPROVAL SUBMITTED FOR RECOVER APPLICATIONS. FOR
 EXAMPLE, PULL OUT TESTING (TAS 105), MOISTURE SURVEYS
 (TAS 126), ETC. REVIEW ALL THE SYSTEMS LIMITATIONS AND
 PROVIDE ALL L REQUIRED TESTING (2 COPIES). SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 4- PROVIDE RAS 117 CALCULATIONS (2 COPIES) IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES AND IF
 SELECTED ASSEMBLY ALLOWS FASTENER ENHANCEMENT. SEC.
 1609 FBC-BUILDING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-04-05 Cont ID  
Sent By jgomez Date 2018-04-05 Time 11:14 Rev Time 0.00
Received By jgomez Date 2018-04-05 Time 11:01 Sent To  
Notes
2018-04-05 11:02:21RAS 117 CALCULATIONS SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-04-04 Cont ID  
Sent By jgomez Date 2018-04-04 Time 10:04 Rev Time 0.00
Received By jgomez Date 2018-03-30 Time 13:59 Sent To I
Notes
2018-04-02 13:59:51RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-28 Cont ID  
Sent By jgomez Date 2018-03-28 Time 17:29 Rev Time 0.00
Received By jgomez Date 2018-03-23 Time 13:40 Sent To I
Notes
2018-03-26 13:40:14RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 10:35 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 09:37 Sent To I
Notes
2018-03-20 09:37:43RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-14 Cont ID  
Sent By jgomez Date 2018-03-14 Time 09:44 Rev Time 0.00
Received By jgomez Date 2018-03-13 Time 16:24 Sent To I
Notes
2018-03-13 16:24:38JGOMEZ