2018-05-17 16:08:23 | 05/17/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS NOTE |
| - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. IT APPEARS THAT THERE ARE A GAS STOVE AND WATER |
| HEATER PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND |
| THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC |
| FUEL GAS RES. SEC. G2413. |
| 2. YOU ARE MISSING THE FIREPLACE IN THE BTU 7. INDICATE |
| THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN |
| PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. SEC. |
| G2413.2. |
| 3. THE PLAN REVIEW INDICATES AN EXISTING GAS APPLIANCE. |
| THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED |
| TO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE |
| EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE |
| EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3 |
| 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| GAS RES. SEC. G2413.2 AND G2404.3 |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| (CLOTHES DRYERS, GAS HEATER, AND STOVE) 2017 FBC FUEL |
| GAS RES. SEC. G2407.1 AND G2439.4. |
| 6. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A |
| ROOF. WPB AMEND. TO FBC SEC. 107.2.1 |
| 7. VALUE* JOB VALVE SEEM LOW, PROVIDED BONA FIDE SIGN |
| CONTRACT. WPB AMEND TO THE FBC 109.3 BUILDING PERMIT |
| VALUATIONS. IF IN THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONA CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |