2018-03-09 13:55:37****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. ON BATHROOM DOORS 4 AND 5 DO THEY HAVE DOOR
 CLOSURES? IT IS NOT SHOWN ON THE DOOR SCHEDULE.
  
 IF A CLOSURE IS PROVIDED SHOW A 12 INCH CLEARANCE AT
 THE LATCH PULL SIDE OF THE DOOR.
  
 ACCESSIBILITY 404.2.4 MANEUVERING CLEARANCES.
  
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
 DOORS AT THE CARE SUITES AND THE ATTACHED BATHROOMS
 SHALL HAVE A CLEAR DISTANCE ON THE LATCH PUSH SIDE OF
 THE DOOR OF A MINIMUM OF 12 INCHES. SEE FLORIDA
 ACCESSIBILITY CODE FIGURE 404.2.4.1 DETAIL (C).
  
 2. STAFF ROOM 110 APPEARS TO BE ABOUT 5 FT 3 INCHED
 WIDE. THE MINIMUM ROOM WIDTH IS 7 FT.
 FBC 1208.1 MINIMUM ROOM WIDTHS.
 HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-15 Cont ID  
Sent By jpearson Date 2018-05-15 Time 10:47 Rev Time 0.00
Received By jpearson Date 2018-05-15 Time 10:43 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-27 Cont ID  
Sent By jpearson Date 2018-04-27 Time 13:01 Rev Time 0.00
Received By jpearson Date 2018-04-27 Time 10:16 Sent To  
Notes
2018-04-27 13:01:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1,
 BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED
 TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE
 CORRECTION. FBC 107.2.1 (PANELS ARE NOW NAMED
 DIFFERENTLY, BUT THE PANEL SCHEDULES ARE NOT SUPPLIED
 FOR THE PANELS SHOWN, AND THE LOAD FOR EACH PANEL IS
 NOT DETAILED. PROVIDE COMPLETED PANEL SCHEDULES WITH
 LOADS FOR THE PANELS TO CONFIRM THE PANELS ARE NOT
 OVERLOADED.)
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)
 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1 (NOT PROVIDED. A NOTE THAT STATES ALL
 NON-ESSENTIAL OUTLETS TO BE TIME CLOCK CONTROLLED IS
 NOT SUFFICIENT. THE EXCEPTION NOTED IN RESPONSE LETTER
 IS ONLY FOR RECEPTACLES DESIGNATED FOR EQUIPMENT THAT
 REQUIRES CONTINUOUS OPERATION. SHOW ON PLAN WHICH
 RECEPTACLES WILL BE TIME CLOCK CONTROLLED, IN
 COMPLIANCE WITH ABOVE REQUIREMENT.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-22 Cont ID  
Sent By jpearson Date 2018-03-22 Time 14:49 Rev Time 0.00
Received By jpearson Date 2018-03-22 Time 14:49 Sent To  
Notes
2018-03-22 14:49:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTE 1 AND 17 ON SHEETS CS-1 AND MEP 1
 THROUGH 4 STATE THAT THE 2011 NEC IS USED FOR DESIGN.
 THIS IS NOT THE CURRENT CODE IN EFFECT. PROVIDE
 CORRECTIONS. FBC PREFACE
 2. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN
 KITCHEN. NEC 210.8(B)(2)
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
 4. PANELS ARE SHOWN AS 3?, 120/240 VOLT, WHICH WOULD
 HAVE B? AS A HIGH LEG. HOWEVER, THE PANEL SCHEDULES
 SHOWS 120 VOLT LOADS ON B?. PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1
 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1,
 BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED
 TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE
 CORRECTION. FBC 107.2.1
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-24 Cont ID  
Sent By pleduc Date 2018-04-24 Time   Rev Time 0.00
Received By pleduc Date 2018-04-24 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-08 Cont ID  
Sent By pleduc Date 2018-03-08 Time   Rev Time 0.00
Received By pleduc Date 2018-03-08 Time 13:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-05-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-10 Time 12:34 Sent To  
Notes
2018-05-14 12:34:40RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 15:32 Rev Time 0.00
Received By shill Date 2018-04-12 Time 10:56 Sent To  
Notes
2018-04-17 10:57:00B13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-23 Cont ID  
Sent By gjohnson Date 2018-03-23 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2018-03-05 Time 15:54 Sent To  
Notes
2018-03-06 15:54:08B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-09 Cont ID  
Sent By aclange Date 2018-03-09 Time 13:39 Rev Time 0.00
Received By aclange Date 2018-03-09 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-21 Cont ID  
Sent By ccole Date 2018-05-21 Time 15:00 Rev Time 0.00
Received By ccole Date 2018-05-21 Time 14:52 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-24 Cont ID  
Sent By ccole Date 2018-04-24 Time 16:43 Rev Time 0.00
Received By ccole Date 2018-04-24 Time 16:27 Sent To  
Notes
2018-04-24 16:51:012ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18030167
 4/24/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLAN SHOWS RETURN AIR BEING TAKEN FROM THE
 ADJACENT MAINTENANCE ROOM, HOWEVER THE CONTENTS OF THAT
 ROOM ARE UNKNOWN, AND RETURN AIR FROM THAT ROOM MAY BE
 PROHIBITED- SEE SECTION 601.5 ITEMS #1, 2 & 7. AND
 VERIFY COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By ccole Date 2018-03-15 Time 16:56 Rev Time 0.00
Received By ccole Date 2018-03-15 Time 16:56 Sent To  
Notes
2018-03-16 07:57:111ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18030167
 3/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MEP-1: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ALTERED ROOMS AND SPACES PER TABLE
 403.3.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) MEP-1: FLEX DUCT CANNOT BE USED FOR THE TOILET ROOM
 EXHAUST PER UL AND MANUFACTURER'S SPECIFICATIONS.
 PROVIDE METAL DUCTWORK PER SMACNA STANDARDS.
  
 3) MEP-1: CLARIFY IF THE EF-1 FANS ARE NEW OR EXISTING.
 PROVIDE EQUIPMENT SCHEDULES FOR NEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-23 Cont ID  
Sent By gjohnson Date 2018-04-23 Time 17:40 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By gjohnson Date 2018-03-23 Time 10:01 Rev Time 0.00
Received By gjohnson Date 2018-03-23 Time 07:42 Sent To  
Notes
2018-03-23 10:16:291ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. THE
 SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR
 SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES (485
 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 2. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.7
  
 3. GRAB BARS TO BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE OFF FINISHED FLOOR. PER FBC ACC 609.4
  
 4. PLEASE SHOW COMPLIANCE WITH THE REQUIREMENT FOR A
 WATER FOUNTAIN. PER FBC PL TABLE 403.1
  
 5. SHT. A-3 UNDER NOTE SCOPE OF WORK IN EXISTING
 BATHROOM THERE ARE NO EXISTING BATHROOMS SHOWN IN AREA
 OF WORK PLEASE CLARIFY WHERE THIS WORK IS BEING DONE.
 PER WPB AND TO FBC 107.2.1
  
 6. PLEASE STATE ON THE PLAN WHAT LEVEL OF ALTERATION
 THIS PROJECT IS PER FBC EX CH 2
  
 7. SHOW COMPLIANCE WITH FBC PL 607.3
  
 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 9. WHAT TYPE OF PIPE IS SHOWN ON THE FIRE STOPPING
 DETAILS PROVIDE DETAILS FOR ALL TYPES OF PIPE AND
 INSTALLATIONS PER WPB AMEND TO FBC 107.2.1.3
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-04-18 Cont ID  
Sent By elevesqu Date 2018-04-18 Time 10:09 Rev Time 0.00
Received By elevesqu Date 2018-04-18 Time 10:09 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved