Plan Review Details - Permit 18030157
Plan Review Stops For Permit 18030157
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2019-05-17 Cont ID  
Sent By cthroop Date 2019-05-17 Time 16:00 Rev Time 0.00
Received By cthroop Date 2019-05-09 Time 09:52 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 08:12 Rev Time 0.00
Received By cthroop Date 2019-03-12 Time 15:52 Sent To  
Notes
2019-03-13 08:25:08BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADDRESSING IS INCORRECT FOR STRUCTURES
  
 A UNITY OF TITLE WAS FILED ON 2/15/2018 (BOOK
 29652/PG1217)
  
 PARCELS HAVE NOT BEEN UNIFIED ON PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE AS OF THIS DATE
  
 AN E-MAIL HAS BEEN SENT TO MICHAEL ORIO, GIS SUPPORT
 SPECIALIST, CITY OF WEST PALM BEACH AND CAROLINE GLASS,
 PALM BEACH COUNTY REQUESTING THE UNITY OF THE PARCEL
 AND CORRECT ADDRESSING OF THIS PROPERTY BE RECORDED
  
 A NEW SITE PLAN WILL BE REQUIRED WITH THE CORRECT
 ADDRESS OF EACH STRUCTURE ON THE PROPERTY
  
  
  
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By shill Date 2018-10-30 Time 11:23 Rev Time 0.00
Received By shill Date 2018-10-30 Time 11:23 Sent To  
Notes
2018-10-30 11:25:4310/30 - UNITY OF TITLE RECORDED 2/15/18 (BOOK 29652/PG
 1217), CONFIRMED W/VINCE NOEL
  
 THE PLANS DO NOT APPEAR TO BE CONSISTENT - AREA OF WORK
 SHOWN DOES NOT APPEAR TO BE FOR THE CORRECT BUILDING.
  
 TWO DIFFERENT PARCELS HAVE THE SAME ADDRESS. UNIQUE
 ADDRESSES ARE REQUIRED PER CITY STANDARDS.
  
  
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-05-17 Cont ID  
Sent By cthroop Date 2019-05-17 Time 16:33 Rev Time 0.00
Received By cthroop Date 2019-05-09 Time 09:52 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-03-13 Cont ID  
Sent By cthroop Date 2019-03-13 Time 08:25 Rev Time 0.00
Received By cthroop Date 2019-03-12 Time 09:23 Sent To  
Notes
2019-03-13 08:31:01BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. RESUBMITTAL WILL BE REQUIRED AFTER THE CORRECT
 ADDRESSES HAVE BEEN RECORDED WITH PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE. A NEW SITE PLAN SHALL HAVE
 THE CORRECT ADDRESS OF EACH STRUCTURE.
 SEE NOTES UNDER ADDRESS REVIEW.
  
 2. EACH STRUCTURE ON PROPERTY REQUIRES A SEPERATE
 ADDRESS.
  
 3. A SEPERATE PERMIT IS REQUIRED FOR EACH STRUCTURE
 THAT WORK WILL BE PERFORMED ON.
  
 4. ALL STRUCTURES MAY BE INCLUDED ON A SINGLE SET OF
 PLANS. EACH STRUCTURE MUST BE IDENTIFIED BY ADDRESS.
 EACH PLAN AND/OR DETAIL SHALL BE IDENTIFIED BY ADDRESS.
  
 5. AS AN EXAMPLE - PLEASE REFERENCE NOTES 2 & 4 ON PLAN
 PAGE C-1.0. "CUT 5X8 OPENING BETWEEN 925 & 1013" THESE
 TWO BUILDING ARE NOT ATTACHED.
  
 6. REFERENCE PROJECT DATA ON PLAN PAGE C-1.0. PROPOSED
 OCCUPANCY IS LISTED AS MERCANTILE. DEPENDING ON THE
 SPECIFIC BUILDING THERE SHOULD ALSO BE AN A-3 ASSEMBLY
 OCCUPANCY AND A BUSINESS OCCUPANCY.
  
 7. REFER TO PLAN PAGE LS-1.0 - NOTE: THE WORK AREA IS
 THE METHOD USED TO COMPLY WITH THE FBCEB. PLEASE
 CLARIFY?
  
 8. REFER TO PLAN PAGE LS-3.0 - THE USE OF A REVISION
 SYMBOL ON THE PLAN SHOULD COINCIDE WITH A NARRATIVE OF
 ALL WORK INCLUDED UNDER THE REVISION. THIS IS USUALLY
 PLACED IN THE MARGIN OF THE PLAN PAGE FOR REFERENCE.
  
 9. PROVIDE PRODUCT APPROVALS FOR ALL STOREFRONTS, DOORS
 AND WINDOWS TO BE INSTALLED. DESIGNER TO REVIEW AND
 APPROVE IN WRITING. NO SEAL REQUIRED.
  
 10 PROVIDE WINDOW AND DOOR SCHEDULE. LIST ALL ROUGH
 OPENINGS WITH DESIGN PRESSURES FOR EACH OPENING.
 SPECIFY WHICH PRODUCT WILL BE INSTALLED IN EACH
 OPENING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-08-28 Cont ID  
Sent By cthroop Date 2018-08-28 Time 11:33 Rev Time 0.00
Received By cthroop Date 2018-08-28 Time 08:36 Sent To  
Notes
2018-08-28 12:05:05BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SCOPE OF WORK HAS CHANGED DUE TO THE CHANGE OF
 OCCUPANCY. ADDITIONAL REVIEWS REQUIRED - MECH.,
 ELECTRICAL, PLUMBING AND ZONING.
 FBC EXISTING SEC. 1001.2.2 CHANGE OF OCCUPANCY
 CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 2. CHANGE CLASSIFICATION OF WORK ON PLAN PAGE CV-1.0
 FROM ALTERATION LEVEL II TO CHANGE OF OCCUPANCY. NEW
 CLASSIFICATION SHOULD BE A-3 GALLERY.
 303.4 ASSEMBLY GROUP A-3.
 GROUP A-3 OCCUPANCY INCLUDES ASSEMBLY USES INTENDED FOR
 WORSHIP, RECREATION OR AMUSEMENT AND OTHER ASSEMBLY
 USES NOT CLASSIFIED ELSEWHERE IN GROUP A INCLUDING, BUT
 NOT LIMITED TO:
 ART GALLERIES
  
 3. APPLICABLE BUILDING CODES ON PLAN PAGE C-1 ARE
 INCORRECT. CURRENT GOVERNING CODE IS THE 2017 FBC
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 4. DRAWING SCHEDULE ON PLAN PAGE C-1 IS INCORRECT.
 COVER SHEET IS CV-1.0. SITE PLAN IS C-1.
  
 5. DRAWING SCALE ON PLAN PAGES A-1, A-2 AND A-3 IS TOO
 SMALL. MINIMUM SCALE IS 1/8" = 1 FOOT.
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 6. MINIMUM NUMBER OF PLUMBING FACILITIES SHALL COMPLY
 WITH FBC CHPT. 29.
 FBC 2902.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED IN THE MINIMUM
 NUMBER AS SHOWN IN TABLE 2902.1 BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE. USES NOT SHOWN IN TABLE
 2902.1 SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE
 OFFICIAL. THE NUMBER OF OCCUPANTS SHALL BE DETERMINED
 BY THIS CODE.
  
 7. REFERENCE PLAN PAGE S-1.0 FOR THE FOLLOWING
 COMMENTS.
 7A. PROVIDE DESIGN WIND LOADS FOR CONTAINERS.
 ENGINEERING TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL.
 7B. PROVIDE DESIGN FOR FOUNDATION. IF EXISTING, PROVIDE
 CERTIFICATION BY A DESIGN PROFESSIONAL.
 7C. PROVIDE ATTACHMENT DETAIL FOR CONTAINER TO
 FOUNDATION.
 7D. PROVIDE WELD SPECIFICATIONS.
 7E. PROVIDE WELDER CERTIFICATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-13 Cont ID  
Sent By cthroop Date 2018-07-13 Time 08:15 Rev Time 0.00
Received By cthroop Date 2018-07-06 Time 10:14 Sent To  
Notes
2018-07-13 08:10:12THE CITY HAS BEEN REQUESTING AN OVERALL SITE PLAN FOR
 THIS PROJECT IN ORDER TO ASSIGN OCCUPANCIES, FIRE
 SEPARATION DISTANCES, BUILDING HEIGHT AND USE FOR THE
 VARIOUS PIECES AND PARTS THAT ARE PRESENT ON THE SITE.
 TO DATE, A FULL AND COMPRHENSIVE SITE PLAN HAS YET BE
 TO BE PRESENTED. THIS HAS PREVENTED US FROM COMPLETING
 A COMPREHENSIVE REVIEW. THE WORK MAY BE PHASED OR
 STAGED TO VARIOUS COMPONENTS OF THE PROJECT ONCE THE
 OVERALL PROJECT IS DEFINED, CLEARLY STATED, SHOWN ON A
 DIMENSIONED SITE PLAN AND APPROVED FOR THE USES THAT
 ARE BEING REQUESTED. BOTH FIRE AND PLANNING/ZONING NEED
 TO REVIEW THE MIXED USE OF THIS PROPERTY AND APPROVE
 THE USES IN THE LOCATIONS THAT ARE REQUESTED. AT THIS
 TIME, IT IS BELIEVED THERE ARE GOUP B, BUSINESS USE(S),
 GROUP S, STORAGE USE(S), GROUP A, ASSEMBLY USE(S) AND
 POSSIBLY OTHERS. UNTIL AN OVERALL OCCUPANT LOAD, USE
 AND LIMITS OF PROPERTY ARE DETERMINED AND DEFINED, IT
 IS NOT POSSIBLE TO COMPLETE A REVIEW OF THE PROJECT.
  
 THE PLANS SUBMITTED UNDER TJHIS REQUEST ARE MISSING
 IMPORTANT AND VALUABLE INFORMATION NEEDED FOR THE
 REVIEW. THOSE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
 OVERALL SITE PLAN
 USE OF THE PROPERTY
 OCCUPANT LOAD FOR EACH PORTION AND USE
 WIND LOAD CALCULATIONS AND AFFIRMATION OF COMPLIANCE
 WELDING PROCEDURE SPECIFICATION (WPS)
 WELDERS CERTIFICATIONS
 COMPLETE LAYOUT INCLUDING LIMITS OF MIXED USES
 COMPLETE AND COMPREHENSIVE LIFE SAFETY PLAN
 SPRINKLER PLANS
 ALL OTHER REQUIRED INFORMATION BY FLORIDA BUILDING CODE
 - BUILDING SECTION 107
  
 REVIEW IS UNABLE TO BE COMPLETED UNTIL ALL REQUIRED AND
 PREVIOUSLY REQUESTED INFORMATION IS PROVIDED.
  
 DOUGLAS HARVEY
 ASSISTANT BUILDING OFFICIAL
 [email protected]
 561-805-6740
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By cthroop Date 2018-03-16 Time 14:35 Rev Time 0.00
Received By cthroop Date 2018-03-16 Time 14:32 Sent To  
Notes
2018-03-16 14:37:59BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BUILDING ENVELOPE CANNOT BE OPENED WITHOUT DOORS
 ON-SITE TO BE INSTALLED.
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED DOORS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-06-20 Cont ID  
Sent By jpearson Date 2019-06-20 Time 10:56 Rev Time 0.00
Received By jpearson Date 2019-06-20 Time 10:55 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-04-29 Cont ID  
Sent By jpearson Date 2019-04-29 Time 15:34 Rev Time 0.00
Received By jpearson Date 2019-04-29 Time 13:26 Sent To  
Notes
2019-04-29 15:34:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. THERE ARE TWO DIFFERENT RISER DIAGRAMS PROVIDED WITH
 CONFLICTING INFORMATION. PROVIDE CORRECTION. NEC 215.5;
 WPB FBC 107.2.1 (THE PERMIT APPLICATION STATES THE WORK
 FOR THIS PLAN IS FOR 925 RAILROAD. THE ELECTRICAL PLAN
 SHOULD ONLY INCLUDE INFORMATION FOR WORK AT THAT
 ADDRESS. WHY ARE 2 SEPARATE RISER DIAGRAMS INCLUDED?
 PROVIDE CLARIFICATION AND/OR REMOVE INFORMATION NOT
 PERTINENT TO THIS PERMIT APPLICAITON.SOME SHEETS STATE
 THE WORK IS FOR 925 ADDRESS, SOME SHEETS STATE THE WORK
 IS FOR 925/1013, BUT THE FLOOR PLANS DO NOT INDICATE
 WHICH ADDRESS OR WHERE EXACTLY THE WORK IS TO BE
 PERFORMED.)
 2. THE LOAD CALCULATION PROVIDED DOES NOT RECONCILE
 WITH INFORMATION PROVIDED ON PANEL SCHEDULES. PROVIDE
 CORRECTION SO LOAD FOR EACH AREA IS DETAILED CORRECTLY.
 NEC 220; WPB FBC 107.2.1(NOT CORRECTED. LOAD
 CALCULATION ON SHEET E2.0 STATES THE LOAD IS 440.59
 AMPS, WHILE THE PANEL SCHEDULE FOR THE SAME SERVICE
 STATES THE LOAD AS 251 AMPS. PROVIDE CORRECTION AS
 PREVIOUSLY REQUESTED.)
 3. CORRECTED.
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. THE CURRENT
 INFORMATION PROVIDED SHOWS THE AMPERAGE LOAD OF
 LIGHTING, THIS IS NOT ACCEPTABLE FOR CODE COMPLIANCE.
 SEE CODE SECTION FOR DETAILS. FBC EC C405.4.2 (NOT
 PROVIDED.)
 5. THERE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THIS
 PLAN THAT IS CONFLICTING AND/OR MISSING. A FULL REVIEW
 IS NOT POSSIBLE AT THIS TIME. FURTHER COMMENTS MAY BE
 NECESSARY UPON NEXT REVIEW. WPB FBC 107.2.1(COMMENT
 STILL APPLIES.)
  
 NEW COMMENT:
  
 6. FOR NEW SERVICE ON SHEET E2.0, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE AIC RATING OF THE SERVICE EQUIPMENT IS
 ADEQUATE. PROVIDE AIC RATING OF ELECTRICAL PANELS.NEC
 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-25 Cont ID  
Sent By jpearson Date 2019-02-25 Time 14:15 Rev Time 0.00
Received By jpearson Date 2019-02-25 Time 12:13 Sent To  
Notes
2019-02-25 14:15:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE ARE TWO DIFFERENT RISER DIAGRAMS PROVIDED WITH
 CONFLICTING INFORMATION. PROVIDE CORRECTION. NEC 215.5;
 WPB FBC 107.2.1
 2. THE LOAD CALCULATION PROVIDED DOES NOT RECONCILE
 WITH INFORMATION PROVIDED ON PANEL SCHEDULES. PROVIDE
 CORRECTION SO LOAD FOR EACH AREA IS DETAILED CORRECTLY.
 NEC 220; WPB FBC 107.2.1
 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. THE CURRENT
 INFORMATION PROVIDED SHOWS THE AMPERAGE LOAD OF
 LIGHTING, THIS IS NOT ACCEPTABLE FOR CODE COMPLIANCE.
 SEE CODE SECTION FOR DETAILS. FBC EC C405.4.2
 5. THERE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THIS
 PLAN THAT IS CONFLICTING AND/OR MISSING. A FULL REVIEW
 IS NOT POSSIBLE AT THIS TIME. FURTHER COMMENTS MAY BE
 NECESSARY UPON NEXT REVIEW. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By jpearson Date 2018-09-06 Time 14:02 Rev Time 0.00
Received By jpearson Date 2018-09-06 Time 14:02 Sent To  
Notes
2018-09-06 14:02:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE PLAN SUBMITTED IS THE EXACT PLAN THAT WAS
 SUBMITTED FOR PERMIT 17120517. IS THIS PERMIT FOR
 ADDRESS 925 N RAILROAD, OR 1013 N RAILROAD? AS THESE
 ARE 2 SEPARATE LOCATIONS, THE SAME PLAN WOULD NOT BE
 USED FOR BOTH. PROVIDE CLARIFICATION AND SUBMIT PROPER
 PLAN FOR REVIEW, A REVIEW IS NOT POSSIBLE AT THIS TIME.
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-05-01 Cont ID  
Sent By pleduc Date 2019-05-01 Time   Rev Time 0.00
Received By pleduc Date 2019-05-01 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-02-19 Cont ID  
Sent By pleduc Date 2019-02-19 Time   Rev Time 0.00
Received By pleduc Date 2019-02-19 Time 11:17 Sent To  
Notes
2019-02-19 11:19:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET LS .01 - THERE IS NOTE INDICATED, DIAMOND 1,
 FOR A FIRE DEPARTMENT CONNECTION. ACCORDING TO OTHER
 NOTES THERE IS NO FIRE SPRINKLER SYSTEM.
  
 THE FDC NOTE IS NOT APPLICABLE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By pleduc Date 2018-07-03 Time   Rev Time 0.00
Received By pleduc Date 2018-07-03 Time 13:42 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-08 Cont ID  
Sent By pleduc Date 2018-03-08 Time   Rev Time 0.00
Received By pleduc Date 2018-03-07 Time 16:46 Sent To B
Notes
2018-03-08 10:38:53 
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2019-07-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-07-09 Time 16:43 Sent To  
Notes
2019-07-10 16:43:38RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2019-06-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-12 Time 15:36 Sent To  
Notes
2019-06-13 15:37:03RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2019-05-27 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-10 Time 15:57 Sent To  
Notes
2019-05-20 06:56:56TO ZONING BIN
  
  
2019-04-11 15:57:34C05

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-15 Cont ID  
Sent By cpuell Date 2019-03-15 Time 11:36 Rev Time 0.00
Received By cpuell Date 2019-02-06 Time 14:42 Sent To  
Notes
2019-02-07 14:42:28C12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-30 Cont ID  
Sent By shill Date 2018-10-30 Time 11:23 Rev Time 0.00
Received By shill Date 2018-08-23 Time 15:11 Sent To  
Notes
2018-08-24 15:12:01RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-13 Cont ID  
Sent By cthroop Date 2018-07-13 Time 08:15 Rev Time 0.00
Received By cthroop Date 2018-06-29 Time 15:21 Sent To I
Notes
2018-07-02 15:21:51RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-16 Cont ID  
Sent By cthroop Date 2018-03-16 Time 14:38 Rev Time 0.00
Received By cthroop Date 2018-03-05 Time 10:09 Sent To I
Notes
2018-03-07 10:09:35ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-07-15 Cont ID  
Sent By ccole Date 2019-07-15 Time 08:37 Rev Time 0.00
Received By ccole Date 2019-07-15 Time 08:37 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-06-26 Cont ID  
Sent By ccole Date 2019-06-26 Time 12:12 Rev Time 0.00
Received By ccole Date 2019-06-26 Time 12:12 Sent To  
Notes
2019-06-26 12:28:014TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 6/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.0: THE RHEEM AC EQUIPMENT MODELS IN THE
 SCHEDULE ARE STRAIGHT COOL SYSTEMS PER THE
 MANUFACTURER'S SPECIFICATIONS, HOWEWER THE COMCHECK
 ENERGY COMPLIANCE REPORT LISTS THEM AS HEAT PUMPS.
 PLEASE CORRECT THE DATA AND REMOVE THE HSPF RATINGS
 WHICH ARE NOT RELEVANT TO THE SYSTEMS. EFFICIENCIES FOR
 THE SYSTEMS ARE RATED IN SEER FOR SYSTEMS #1, 2, 3, &
 5, AND EER FOR THE 10-TON SYSTEM #4. PLEASE NOTE THAT
 TWO SIGNED AND SEALED COPIES BY THE ENGINEER OF RECORD
 ARE REQUIRED- SECTION 107/.2.1 WPB.
  
 2) AS PREVIOUSLY REQUESTED TWO COMPLETE SETS OF SIGNED
 AND SEALED AC CALCULATIONS ARE REQUIRED. CURRENTLY ONLY
 CALCULATIONS FOR SYSTEMS #1 & 2 HAVE BEEN PROVIDED.
 PLEASE NOTE THAT THE CURRENT CALCULATIONS SHOW NO HEAT
 GAIN FOM VENTILATION AIR WHICH MUST BE INCLUDED AND
 SHOWN IN THE RESUBMITTED CALCULATIONS- SECTION 107.2.1
 WPB.
  
 3) M2.0: THE AC EQUIPMENT SCHEDULE IS INDICATING ONLY
 2000 CFMS FOR THE AHU-4, HOWEVER THE MANUFACTURER'S
 SPECIFICATIONS INDICATE 4000 CFMS NOMINAL FOR THE UNIT-
 RHGL-120.
  
 4) M1.0: THE REVISED AC PLAN IS NOW SHOWING O/A TO BE
 DUCTED THROUGH THE EXTERIOR WALLS USING INTERIOR FANS,
 HOWEVER THE EQUIPMENT SCHEDULE IS INDICATING ROOF
 MOUNTED FANS- GREENHECK SAF. PLEASE CORRECT AND NOTE
 THAT THE O/A OPENINGS IN THE EXTERIOR WALLS MUST BE
 PROTECTED WITH CORROSION-RESISTENT SCREENS, LOUVERS, OR
 GRILLES- SECTION 401.5 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-04-25 Cont ID  
Sent By ccole Date 2019-04-25 Time 10:30 Rev Time 0.00
Received By ccole Date 2019-04-24 Time 17:43 Sent To  
Notes
2019-04-25 10:49:303RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 4/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.0: COMMENT #7 FROM THE 2ND REVIEW STILL
 EXISTS- PLEASE COMPLY.7) M-1.0: DUCT SMOKE DETECTORS
 ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE 5-TON AHU'S
 PER SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN
 EXEMPTION CAN BE APPLIED FOR THE 5-TON SYSTEMS IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THOSE SYSTEMS
 ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR.
  
 2) SHEET M2.0: THE RHEEM AC EQUIPMENT MODELS IN THE
 SCHEDULE ARE STRAIGHT COOL SYSTEMS PER THE
 MANUFACTURER'S SPECIFICATIONS, HOWEVWER THE COMCHECK
 ENERGY COMPLIANCE REPORT LISTS THEM AS HEAT PUMPS-
 PLEASE CORRECT. PLEASE NOTE THAT THE AC SCHEDULE
 INDICATES THE AIR HANDLERS ARE NOT EQUIPPED WITH HEAT
 STRIPS, HOWEVER MINIMUM HEAT IS REQUIRED FOR ALL
 OCCUPIED SPACES- SECTION 309.1 FBC M.
  
 3) COMMENT #3 FROM THE 2ND REVIEW STILL PARTIALLY
 EXISTS. THE ELITE HVAC CALCS HAVE NOT BEEN PROVIDED
 WITH AN ORIGINAL SEAL AND SIGNATURE BY THE EOR. 3)
 ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE HVAC
 CALCS IS A COPIED, REDUCED IN SIZE INK SEAL. PROVIDE
 ORIGINAL 1-7/8" DIAMETER SEALS AND WET SIGNATURES ON
 THE DOCUMENTS- SECTION 61G15-23.002 (2) FAC.
  
 4) PLEASE NOTE THAT THE AC CALCULATIONS ARE INDICATING
 ONLY TWO AIR HANDLERS- 1 & 2, HOWEVER THERE ARE 5 AIR
 HANDLERS IN THE SPACE.
  
 5) COMMENT #8 FROM THE 2ND REVIEW STILL EXISTS- PLEASE
 COMPLY. 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE
 PLAN FOR THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT
 PROTECTION AND WIND LOAD ENGINEERING FOR INSTALLATION-
 SECTION 301.15 FBC M.
  
 6) M-2.0: THE DETAIL PROVIDED FOR THE O/A ROOF FAN
 INSTALLATIONS USING A 6" DUCT EXTENSION ABOVE THE ROOF
 DOES NOT APPEAR TO BE APPLICABLE FOR THE SPECIFIED
 GREENHECK SAF FANS. THESE TYES OF ROOF FANS ARE
 TYPICALLY MOUNTED ON PRE-MANUFACTURED CURBS PER THE
 MANUFACTURER'S SPECIFICATIONS AND PER THE PRODUCT
 APPROVALS OR NOA'S. PLEASE SUBMIT THE SPECS AND THE
 NOA'S.
  
 7) M-2.0: THE NEW AIR BALANCE SCHEDULE INDICATES
 GREATER AMOUNTS OF RETURN AIR TO THE SYSTEMS THAN THE
 AMOUNTS OF SUPPLY AIR PROVIDED? PLEASE SEE SECTION
 601.5 (3) FBC M AND CORRECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-20 Cont ID  
Sent By ccole Date 2019-02-20 Time 08:39 Rev Time 0.00
Received By ccole Date 2019-02-19 Time 16:49 Sent To  
Notes
2019-02-20 09:30:462ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 2/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS.THE
 $10,000 JOB VALUE FOR THE SCOPE OF WORK SHOWN ON THE
 PLANS IS LOW- SEE SECTION 109.3 WPB AND PROVIDE AN
 ACCURATE JOB VALUE.
  
 2) ENGINEER'S TITLE BLOCK MISSING FROM THE MEP PLANS-
 SECTION 61G15-23.002 FAC.
  
 3) ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE
 HVAC CALCS IS A COPIED, REDUCED IN SIZE INK SEAL.
 PROVIDE ORIGINAL 1-7/8" DIAMETER SEALS AND WET
 SIGNATURES ON THE DOCUMENTS- SECTION 61G15-23.002 (2)
 FAC.
  
 4) SHEET M-1.0: THE PROPOSED MECHANICAL PLAN SHALL BE
 DRAWN TO A MINIMUM 1/8" = 1'0" SCALE PER SECTION
 107.2.1.3 WPB. THE SCALE OF THE PLAN IS LISTED AS 3/32
 AT THE BOTTOM OF THE PLAN, HOWEVER LISTED AS 3/16" IN
 THE MARGIN. PLEASE NOTE THAT MUCH OF THE PRINT ON THE
 PRINT IS TOO SMALL TO READ DUE TO THE REDUCED SCALE
 SIZE.
  
 5) THE COMCHECK REPORT IS MISSING ENVELOPE DATA FOR THE
 WEST SIDE OF THE BUILDING WHERE THE NEW STOREFRONT
 GLASS AND WALLS WERE INSTALLED TO ENCLOSED THE GARAGE
 BAYS. THESE ENCLOSURES ARE DEFINED AS ADDITIONS PER
 SECTION 202 FBC EC. THE REPORT IS ALSO LACKING ANY DATA
 FOR THE MECHANICAL SYSTEMS. PLEASE PROVIDE A COMPLETE
 REPORT- SECTION 107.1 WPB.
  
 6) SHEET M-1.0: PROVIDE VENTILATION CALCULATIONS PER SF
 FOR ALL ROOMS AND SPACES TO VERIFY THE AMOUNTS OF O/A
 TO BE PROVIDED BY THE EXISTING SYSTEMS- SEE TABLE
 403.3.1.1 FBC M.
  
 7) M-1.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE AHU'S PER SECTION 606.2.1 FBC M.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED FOR THE
 5-TON SYSTEMS IF THE MANUFACTURER'S SPECIFICATIONS
 INDICATE THOSE SYSTEMS ARE NOT CAPABLE OF PRODUCING
 OVER 2000 CFMS OF SUPPLY AIR.
  
 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR
 THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT PROTECTION
 AND WIND LOAD ENGINEERING FOR INSTALLATION- SECTION
 301.15 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By ccole Date 2018-09-13 Time 11:59 Rev Time 0.00
Received By ccole Date 2018-09-13 Time 11:59 Sent To  
Notes
2018-09-13 12:42:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 9/13/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $10,000.00 JOB VALUE LISTED ON THE PERMIT
 APPLICATION APPEARS TO BE VERY LOW FOR A 13,798 S.F.
 REMODEL AND CHANGE OF OCCUPANCY, WHICH INCLUDES AMONG
 OTHER THINGS A NEW ACCESSIBLE BATHROOM, A NEW HANDICAP
 RAMP, AND NEW ADDITIONS (LOADING BAY CONVERSIONS)
 PLEASE REFER TO SECTION 109.3 WPB AND PROVIDE DETAILED
 ESTIMATES, AND/OR BONA FIDE CONTRACTS FOR ALL PHASES OF
 THE PROJECT INCLUDING STRUCTURAL, ARCHITECTURAL,
 MECHANICAL, ELECTRICAL, PLUMBING, INTERIOR AND EXTERIOR
 FINISH WORK, SITE WORK, DESIGN FEES, AND OVERHEAD AND
 PROFIT. THE TOTAL VALUE SHALL INCLUDE LABOR, MATERIALS,
 EQUIPMENT AND APPLIANCES.
  
 2) THE PROJECT INFORMATION, INDEX, ETC. ON COVER SHEET
 CV-1.0 DESIGNED BY CALITO P.E. DOES NOT MATCH THE REST
 OF THE PLANS IN THE SET THAT ARE DESIGNED BY GOUBRAN
 ARCHITECT. PLEASE CORRECT OR REMOVE THE SHEET FROM THE
 SETS.
  
 3) SHEET M-1: THE O/A CALCULATIONS ARE INCORRECTLY
 IDENTIFYING THE LARGE 11,376 S.F. GALLERY AREAS AS
 SALES. PLEASE SEE TABLE 403.3.1.1 FBC M AND PROVIDE
 CALCULATIONS FOR THE GALLERIES BASED ON AN OCCUPANT
 DENSITY OF 40 PERSONS PER 100 S.F./7.5 CFMS PER PERSON
 + 0,06 CFMS PER S.F. ADJUST THE TABLE TO SHOW THE
 REQUIRED AND PROVIDED CFMS OF OUTSIDE AIR FOR ALL ROOMS
 AND AREAS.
  
 4) M-1: INDICATE HOW THE LARGE STORAGE ROOM ON THE
 SOUTH SIDE OF THE OCCUPANCY IS BEING VENTILATED- TABLE
 403.3.1.1 FBC M.
  
 5) M-1: A MINIMUM 10' CLEARANCE DISTANCE TO THE
 DRIVEWAY IS REQUIRED FOR THE O/A FAN THAT IS PROVIDING
 FAN TO THE ART STORAGE ROOM ON THE NORTH SIDE- SECTION
 401.4 FBC M. THIS REQUIREMENT WILL REMAIN UNTIL THE
 PLAN ACTUALLY SHOWS THE DRIVEWAY WILL BE REMOVED AND
 CONVERTED TO NON-VEHICULAR USE.
  
 6) M-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ART
 STORAGE FAN AND INDICATE HOW THE NEW WALL OPENING WILL
 PROTECTED AGAINST WIND AND RAIN- SECTION 401.5. PLEASE
 NOTE THAT OUTDOOR AIR INTAKE OPENINGS LOCATED IN
 EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR
 WALL OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 7) M-1: THE NEW AIR CONDITIONED DISPLAY AREAS THAT WERE
 PREVIOUSLY LOADING DOCKS ARE DEFINED AS ADDITIONS PER
 SECTION C202 FBC EC. PROVIDE AC LOAD CALCULATIONS IN
 ACCODANCE WITH SECTION C403.2.1 FBC EC.
  
 8) M-1: NEW ADDITIONS AND SPACES THAT CHANGE OCCUPANCY
 ARE SUBJECT TO COMPLIANCE WITH THE CURRENT FBC EC.
 PLEASE SEE SECTION C101.5.1 AND SUBMIT A COMPLIANCE
 REPORT USIBNG APPROVED SOFTWARE. REFER TO THE FOLLOWING
 SECTIONS FOR MORE INFORMATION - C503.2, C101.3, AND
 C401.2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT
 SUBMITTAL OF CORRECTED PLANS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-22 Cont ID  
Sent By gjohnson Date 2019-04-22 Time 11:19 Rev Time 0.00
Received By gjohnson Date 2019-04-22 Time 11:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-02-28 Cont ID  
Sent By jesmith Date 2019-02-28 Time 11:20 Rev Time 0.00
Received By jesmith Date 2019-02-28 Time 07:53 Sent To  
Notes
2019-02-28 11:19:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW: DENIED
 PLUMBING COMMENTS
 1. PLAN SHEET P-2.0:
 A. MINIMUM PLUMBING FIXTURE REQUIREMENTS FOR OCCUPANCY
 LOAD 378 MERCANTILE IS INCORRECT. REQUIRES TWO (2) EACH
 TOILETS, TWO (2) EACH LAVATORIES, ONE (1) EACH SERVICE
 SINK AND ONE (1) EACH DRINKING FOUNTAIN PER FBC PL
 TABLE 403.1. CORRECT ON PLANS PER WPB FBC 107.2.1
 B. EXISTING WOMEN?S TOILET ROOM DOES NOT MEET THE
 REQUIREMENTS OF FBC ACC 604.8.1.7. PLEASE NOTE ADVISORY
 604.8.1.6 LAVATORY AND 604.8.Y WHICH NOTES THAT THE
 FLORIDA REQUIREMENT ONLY APPLIES TO NEW CONSTRUCTION,
 THEY ARE DESIRABLE FOR ALL WHEELCHAIR ACCESSIBLE
 COMPARTMENTS AND SHOULD BE CONSIDERED WHERE FEASIBLE.
 PER FBC ACC 202.4.1 DISPROPORTIONATE COST UP TO 20% (IN
 THIS CASE $5000.00) OF THE PROJECT COST SHALL BE USED
 TO UPGRADE ACCESSIBILITY REQUIREMENTS. PROVIDE
 COMPLIANCE TO FBC ACC 604.8.1.7 OR SHOW INFEASIBILITY
 OF PROVIDING THE UPGRADE WHICH WOULD INCLUDE BUT NOT BE
 LIMITED TO EXCEEDING THE 20% COST. PROVIDE
 DOCUMENTATION FOR THE SAME PER WPB FBC 107.2.1.
 C. ONE EACH (1) VTR (VENT THROUGH THE ROOF OR TO THE
 OUTSIDE) IS REQUIRED FOR EACH BUILDING DRAIN PER FBC PL
 904.1. SANITARY RISER DIAGRAM NOTES ONE (1) EACH
 EXISTING VTR/SV ABOVE CEILING AND TWO (2) EACH NEW
 VTR/SV ABOVE CEILING. WHAT IS THE DEFINITION OF THE
 TERM ?SV?. PER WPB FBC 107.2.1, PLEASE CLARIFY ON PLANS
 AND SHOW THAT AT LEAST ONE OF THE VENTS DOES INDEED
 EXTEND TO THE OUTSIDE.
 D. THE WATER CLOSET IS TO BE SUPPLIED WITH COLD WATER
 ONLY FOR FLUSHING PURPOSES. CORRECT ON WATER RISER
 DIAGRAM PER WPB FBC 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By gjohnson Date 2018-09-25 Time 13:48 Rev Time 0.00
Received By gjohnson Date 2018-09-25 Time 13:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-20 Cont ID  
Sent By aaponte Date 2019-05-20 Time 11:12 Rev Time 0.00
Received By aaponte Date 2019-05-20 Time 11:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-14 Cont ID  
Sent By aaponte Date 2019-03-14 Time 09:57 Rev Time 0.00
Received By aaponte Date 2019-03-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By aaponte Date 2018-10-30 Time 10:01 Rev Time 0.00
Received By aaponte Date 2018-10-30 Time 10:00 Sent To  
Notes
2018-10-30 10:35:421. SCOPE OF WORK ON SHEET CV-1.0 DOES NOT SEEM TO MATCH
 THE BUILDING IN OTHER SHEETS.
 2. EXISTING GARAGE DOORS ALONG RAILROAD AVENUE CANNOT
 BE REPLACED BY WALLS AS A SOLID WALL WILL INCREASE THE
 EXISTING LEGAL NON-CONFORMITY REGARDING TRANSPARENCY
 ALONG RAILROAD AVENUE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439