Plan Review Details - Permit 18030154
Plan Review Stops For Permit 18030154
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By jwitmer Date 2018-03-23 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2018-03-23 Time 06:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-12 Cont ID  
Sent By jwitmer Date 2018-03-12 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2018-03-12 Time 11:53 Sent To  
Notes
2018-03-12 14:27:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 18030154
 W. P. B. PERMIT: 17070327
 ADD: 1885 OKEECHOBEE BLVD. / SUITE 1885
 CONT: DUKE INDIANA CONSTRUCTION
 TEL: 954-453-5261
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 12/ 2018
 ACTION: DENIED
  
 1) THE REVISION INDICATES AN INCREASED VALUE OF
 $14,750.00 IN VALUE. THIS INCREASE SEEMS LOW, ALSO WORK
 NOT SHOWN AS A REVISION (DELTA):
  
 1A) SHEET A200 NOTE 11 INDICATES ONLY 2 TO REMOVE THE
 EDGE OF THE DOCK LEVELERS WHERE REQUIRED FOR DOCK BAYS
 11-15.
  
 1B) SHEET A201 DOES NOT SHOW NEW WORK ON THE RAMP FOR
 BAYS 12-15.
  
 1C) SHEET A201 THE WALL LEGEND SHOWS NEW WALLS TO THE
 UNDERSIDE OF THE CEILING, THE PLANS SHOWS (2) NEW SUCH
 WALLS AND A COUNTER TOP.
  
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A300 SHOWS VARIOUS DETAILS:
  
 2A) DETAIL B3 THE BACK WALL OF THE WATER CLOSET SHOWS
 THE BACK GRAB BAR ONLY 4 INCHES FROM THE CORNER, THIS
 ONLY WORKS IF YOU INSTALL THE WATER CLOSET 16 INCHES
 FROM THE SIDE WALL.
 2014 ACCESS. CODE. 604.5.2 REAR WALL. THE REAR WALL
 GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND
 FROM THE CENTERLINE OF THE WATER CLOSET 12 INCHES
 MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE OTHER
 SIDE.
  
 2B) DETAIL B3. THE REAR AND SIDE GRAB BAR DETAILS SHOW
 THE GRAB BARS BEING DIMENSIONED FROM THE CENTERLINE TO
 THE FINISH FLOOR. PLEASE NOTE THE GRAB BARS ARE TO BE
 MEASURED FROM THE TOP OF THE GRASPING SURFACE TO FINISH
 FLOOR. SEE 2014 ACCESS. CODE SECTION 609.4. 33 TO 36
 INCHES FROM FINISH FLOOR.
  
 2C) DETAIL D3. THE TOILET PAPER DISPENSERS, SHOWS
 COMPLIANCE FOR THE HEIGHT BUT NOT THE HORIZONTAL
 DIMENSION FROM THE FRONT OF THE WATER CLOSET SHALL BE 7
 TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. 2014
 ACCESS. CODE 604.7.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-20 Cont ID  
Sent By jpearson Date 2018-03-20 Time 08:52 Rev Time 0.00
Received By jpearson Date 2018-03-20 Time 08:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-13 Cont ID  
Sent By jpearson Date 2018-03-13 Time 09:19 Rev Time 0.00
Received By jpearson Date 2018-03-13 Time 06:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By pleduc Date 2018-03-22 Time   Rev Time 0.00
Received By pleduc Date 2018-03-22 Time 09:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-08 Cont ID  
Sent By pleduc Date 2018-03-08 Time   Rev Time 0.00
Received By pleduc Date 2018-03-08 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-27 Cont ID  
Sent By hmoser Date 2018-03-27 Time 13:48 Rev Time 0.00
Received By hmoser Date 2018-03-23 Time 11:38 Sent To  
Notes
2018-03-27 11:38:32REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-23 Cont ID  
Sent By gjohnson Date 2018-03-23 Time 08:42 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 15:14 Sent To  
Notes
2018-03-19 15:15:17C08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-05 Time 16:17 Sent To  
Notes
2018-03-06 16:17:17C09

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-27 Cont ID  
Sent By ccole Date 2018-03-27 Time 13:48 Rev Time 0.00
Received By hmoser Date 2018-03-27 Time 13:00 Sent To I
Notes
2018-03-27 13:48:29PASS PROVISO
 1) REFER TO SECTION 301.15 WIND RESISTANCE 2014
 FBC (M) . PROVIDE A ENGINEER DETAIL ON CURB TIEDOWN
 TO ROOF, CURB ADAPTER TIE DOWN TO CURB, A/C EQUIPMENT
 ANCHORED TO CURBS. ALL ROOF TOP FANS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-21 Cont ID  
Sent By ccole Date 2018-03-21 Time 08:53 Rev Time 0.00
Received By ccole Date 2018-03-21 Time 08:53 Sent To  
Notes
2018-03-21 09:06:392ND REVIEW FBC-2017 MECHANICAL
 REVISION PERMIT #18030154
 3/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ORIGINAL INCREASE IN VALUE OF $14,750.00
 APPARENTLY DID NOT INCLUDE THE RTU-2 REPLACEMENT, WHICH
 IS NOW BEING SHOWN ON THE SECOND PLAN SUBMITTAL. PLEASE
 INCREASE THE VALUE ACCORDINGLY- SECTION 109.3 WEST PALM
 BEACH AMENDMENTS TO THE FBC-17.
  
 2) PROVIDE COMPLETE WIND LOAD ENGINEERING FOR
 ATTACHMENT OF THE RTU TO THE EXISTING CURB. IF A CURB
 ADAPTER IS REQUIRED PLEASE INCLUDE THE ATTACHMENT IN
 THE ENGINEERING , AND SUBMIT A CUT SHEET FROM THE
 MANUFACTURER- SECTION 301.15.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 16:57 Rev Time 0.00
Received By ccole Date 2018-03-13 Time 16:57 Sent To I
Notes
2018-03-13 17:00:091ST REVIEW FBC-2014 MECHANICAL
 REVISION #18030154
 MASTER #17070327
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PER FIELD INSPECTOR'S NOTE, RTU #2 HAS BEEN
 REPLACED, HOWEVER IT IS SHOWN AS "EXISTING" IN THE
 REVISED PLAN. PLEASE REVISE THE PLANS TO SHOW THE
 REPLACEMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By thunt Date 2018-03-23 Time 08:42 Rev Time 0.00
Received By gjohnson Date 2018-03-23 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-08 Cont ID  
Sent By gjohnson Date 2018-03-08 Time 05:28 Rev Time 0.00
Received By thunt Date 2018-03-07 Time 08:21 Sent To B
Notes
2018-03-08 05:31:2703/08/2018 PLUMBING 1ST REVISION REVIEW**DENIED**
  
 1) THIS IS A CHANGE OF OCCUPANCY AS THE EXISTING
 GOODWILL PERMIT #03040660 WAS LISTED AS A GROUP F-
 FACTORY INDUSTRIAL. PER FBC-EXISTING 1001.3 THE
 PROVISIONS OF SECTIONS 1002 THROUGH 1012 SHALL APPLY.
 FOR PLUMBING THIS WILL AFFECT THE ACCESSIBILITY OF THE
 RESTROOMS THAT ARE NOT CURRENTLY IN COMPLIANCE WITH THE
 FBC-ACCESSIBILITY . LIST ON PLAN THAT THIS IS A CHANGE
 OF OCCUPANCY.
  
 2) SHOW THE REAR GRAB BAR AS BEING MOUNTED 12" OFF
 CENTER LINE OF THE TOILET AS YOU CURRENTLY SHOW 4? THIS
 WOULD BE INCORRECT IF THE TOILET IS INSTALLED @ 18? AS
 SHOWN AS THE MAX ON YOUR PLAN IT WOULD MAKE THE GRAB
 BAR 6? OFF THE SIDE TO BE COMPLAINT. FBC-A 604.5.2
  
 3) SHOW ALL REQUIRED CLEAR FLOOR SPACES FOR THE TOILET
 COMPARTMENTS. FBC-A 604.9
  
 4) SHOW CLEAR FLOOR SPACE FOR EACH OF THE REQUIRE
 NUMBER OF COMMON USE SINKS IN THE RESTROOMS WITH KNEE
 AND TOE CLEARANCE. FBC-A 606.2
  
 5) SHOW SINKS HEIGHT MAX AS BEING 34" FBC-A 606.3
  
 6) SHOW REQUIRED NUMBER OF FIXTURES FOR OCCUPANT LOAD
 NEEDED. FBC-P 403.1
  
 7) SHOW DIMENSIONS OF ALL WALLS ( LENGTH AND WIDTH ) OF
 ALL RESTROOMS INCLUDING STALLS. FBC 107.2.1
  
 8) ALL FIXTURES BEING RE-USED MUST MEET ALL
 REQUIREMENTS SET FORTH IN THE FBC-P 2014 AND NSF61
  
 9) VALUE OF JOB SHALL BE CORRECT TO ADJUST FOR REQUIRED
 CHANGES. WPB AMEND TO THE FBC 109.3 BUILDING VALUATION
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  