Plan Review Details - Permit 18030135
Plan Review Stops For Permit 18030135
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-06-15 Cont ID  
Sent By thunt Date 2018-06-15 Time 07:57 Rev Time 0.00
Received By thunt Date 2018-06-15 Time 07:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 05:11 Rev Time 0.00
Received By thunt Date 2018-03-09 Time 05:11 Sent To  
Notes
2018-03-09 05:21:4503/09/2019 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
 MASTER # 17090752 DID NOT HAVE A GAS REVIEW OR SHOW ANY
 OF THE APPLIANCES AS BEING GAS
  
  
 1) PLEASE EXPLAIN HOW YOU CAME UP WITH THE 80' AS THE
 MOST REMOTE OUTLET OF THIS SYSTEM. SHOW THE DISTANCE
 FROM THE POINT OF DELIVERY, (GAS METER / MP REGULATOR /
 LP TANK) TO THE MOST REMOTE OUTLET IN THE BUILDING AND
 / OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR
 2014 FBC-RES. SEC. G 2413.3
  
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1, 614.5 (CLOTHES DRYERS) OR
 2014 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS). SUBMIT COMBUSTION AIR CALCULATIONS FOR THE
 ADDED GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED
 BY THE BUILDING'S MECHANICAL VENTILATION SYSTEM, THE
 SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE
 IN ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 7) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE AND THE TOTAL LOAD ON EACH REGULATOR. COMPLY
 WITH 2014 FBC-FUEL GAS TABLE 402.4 (28) FOR THE PROPER
 PIPE SIZE AND BTU LOAD.
  
 8) VALUE- THE VALUE OF GAS APPLIANCES MUST BE INCLUDED
 IN THIS PERMIT AS THEY WERE NOT INCLUDED IN THE MASTER
 PERMIT# 17090752.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 9) YOU INDICATE A TANKLESS WATER HEATER ON YOU
 ISOMETRIC BUT IT IS NOT INCLUDED ON YOUR PROPOSAL. FBC
 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-15 Cont ID  
Sent By thunt Date 2018-06-15 Time 07:57 Rev Time 0.00
Received By thunt Date 2018-06-14 Time 16:22 Sent To I
Notes
2018-06-14 16:22:53RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 05:21 Rev Time 0.00
Received By thunt Date 2018-03-05 Time 11:34 Sent To I
Notes
2018-03-06 11:34:44PLUMB <5K