Plan Review Details - Permit 18030117
Plan Review Stops For Permit 18030117
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 15:22 Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-16 Cont ID  
Sent By skennedy Date 2019-01-16 Time 11:32 Rev Time 0.00
Received By skennedy Date 2019-01-16 Time 11:31 Sent To  
Notes
2019-01-16 11:44:283RD REVIEW: FBC 2017 5TH EDITION
 FBC 2017 EXISTING BUILDING
  
 1/16/19 - A NEW DESIGN HAS BEEN SUBMITTED BY A NEW
 DESIGNER. SEE PREVIOUS REVIEWS AND NOTE THE STATUS IS
 SIMILAR TO THE PREVIOUS REVIEW.
  
 TO PROCEED WITH LEGALLY ESTABLISHING THE THIRD UNIT,
 THE APPLICANT MUST NOW DEVELOP A PLAN TO DEMONSTRATE
 COMPLIANCE WITH CURRENT APPLICABLE CODE AS IF CHANGING
 THE LAYOUT ON FILE TO A LEGAL DWELLING UNIT UNDER THE
 REQUIREMENTS OF THE FBC 2017 EXISTING BUILDING CHAPTER
 10 CHANGE OF OCCUPANCY. THE PLAN MUST SHOW COMPLIANCE
 WITH PLUMBING REGARDING THE CONNECTIONS TO THE KITCHEN
 AS THE BATHROOM IS PRESUMED TO BE EXISTING, COMPLETE
 ELECTRICAL COMPLIANCE FOR THE INTERIOR IN TERMS OF
 REQUIRED ELECTRICAL CIRCUITS, DEVICES AND SMOKE ALARMS,
 ETC; NOTE A RECENT ELECTRICAL PERMIT WAS COMPLETED FOR
 WORK IN THIS AREA, SEE ELECTRICAL PLAN REVIEW. A
 MECHANICAL PLAN FOR REQUIRED HEAT AND ANY PROVIDED
 COOLING, AND AN ENERGY SUBMITTAL. ADDITIONALLY
 COMPLIANCE WITH CHAPTER 9 FBC IS REQUIRED AS TO FIRE
 PROTECTION SYSTEMS INCLUDING INCLUDING FIRE SPRINKLER
 AND FIRE ALARM. THE ARCHITECTURAL PLAN MUST PROVIDE THE
 CODE REFERENCE AND A SCOPE OF WORK DISCUSSING THE
 ATTEMPT TO LEGALIZE EXISTING WORK THROUGH ASSURING THE
 RECONFIGURATION OF THE SPACE COMPLIES WITH THE
 AFOREMENTIONED FBC 2017 EXISTING BUILDING CHAPTER 10
 CHANGE OF OCCUPANCY. PRIOR TO PERMIT ISSUANCE THE
 APPROVED PLAN WILL NEED TO BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE AND A FEE MAY BE DUE TO THEM. AN
 APPROPRIATE VALE FOR THIS WORK WILL NEED TO BE
 ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW WORK IS TO
 BE DONE, SEPARATE PERMITS PER TRADE WILL BE REQUIRED.
  
 THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE
 MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND
 THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW
 CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS
 COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT
 TO CHANGE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-18 Cont ID  
Sent By skennedy Date 2018-05-18 Time 13:49 Rev Time 0.00
Received By skennedy Date 2018-05-18 Time 13:49 Sent To  
Notes
2018-06-07 08:44:452ND REVIEW: FBC 2017 5TH EDITION
 FBC 2017 EXISTING BUILDING
  
 UNDER REVIEW
  
 5/18/18 MET WITH OWNER, EXPLAINED FIRST REVIEW COMMENTS
 OF 4/18/18 WERE NOT SUFFIENTLY ADDRESSED.
  
 FIRST REVIEW COMMENTS SEE BELOW:
  
 AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA
 EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE
 SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY
 PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY
 A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964.
 THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO
 CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM
 WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE
 RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING
 AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM
 MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED
 SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF
 A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE
 RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE
 PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT
 ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY
 ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I
 PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR
 CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE
 EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO
 VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY
 ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW
 DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT
 APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A
 LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC
 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY.
 THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING
 THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS
 PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE
 FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL
 CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL
 PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN
 ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER
 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS
 INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE
 ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND
 A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE
 EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF
 THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017
 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR
 TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE
 DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL
 NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW
 WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE
 REQUIRED.
  
 THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE
 MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND
 THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW
 CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS
 COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT
 TO CHANGE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
 1ST REVIEW: FBC 2017 5TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
  
 AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA
 EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE
 SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY
 PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY
 A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964.
 THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO
 CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM
 WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE
 RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING
 AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM
 MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED
 SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF
 A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE
 RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE
 PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT
 ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY
 ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I
 PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR
 CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE
 EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO
 VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY
 ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW
 DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT
 APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A
 LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC
 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY.
 THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING
 THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS
 PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE
 FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL
 CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL
 PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN
 ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER
 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS
 INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE
 ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND
 A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE
 EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF
 THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017
 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR
 TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE
 DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL
 NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW
 WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE
 REQUIRED.
  
 THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE
 MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND
 THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW
 CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS
 COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT
 TO CHANGE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-17 Cont ID  
Sent By skennedy Date 2018-04-17 Time 07:58 Rev Time 0.00
Received By skennedy Date 2018-04-17 Time 07:58 Sent To FIRE
Notes
2018-05-18 13:54:172ND REVIEW: FBC 2017 5TH EDITION
 FBC 2017 EXISTING BUILDING
  
 UNDER REVIEW
  
 5/18/18 MET WITH OWNER, EXPLAINED FIRST REVIEW COMMENTS
 OF 4/18/18 WERE NOT SUFFIENTLY ADDRESSED.
  
 FIRST REVIEW COMMENTS SEE BELOW:
  
 AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA
 EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE
 SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY
 PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY
 A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964.
 THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO
 CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM
 WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE
 RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING
 AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM
 MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED
 SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF
 A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE
 RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE
 PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT
 ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY
 ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I
 PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR
 CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE
 EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO
 VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY
 ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW
 DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT
 APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A
 LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC
 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY.
 THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING
 THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS
 PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE
 FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL
 CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL
 PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN
 ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER
 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS
 INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE
 ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND
 A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE
 EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF
 THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017
 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR
 TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE
 DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL
 NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW
 WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE
 REQUIRED.
  
 THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE
 MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND
 THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW
 CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS
 COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT
 TO CHANGE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
2018-04-18 11:34:051ST REVIEW: FBC 2017 5TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
  
 AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA
 EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE
 SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY
 PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY
 A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964.
 THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO
 CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM
 WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE
 RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING
 AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM
 MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED
 SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF
 A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE
 RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE
 PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT
 ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY
 ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I
 PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR
 CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE
 EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO
 VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY
 ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW
 DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT
 APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A
 LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC
 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY.
 THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING
 THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS
 PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE
 FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL
 CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL
 PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN
 ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER
 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS
 INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE
 ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND
 A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE
 EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF
 THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017
 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR
 TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE
 DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL
 NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW
 WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE
 REQUIRED.
  
 THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE
 MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND
 THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW
 CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS
 COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT
 TO CHANGE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 14:26 Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 14:26 Sent To  
Notes
2019-06-04 14:26:30SEE PERMIT 17071002. WILL NEED AN ADDITIONAL ELECTRICAL
 PERMIT TO FACILITATE MECHANICAL.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-01-16 Cont ID  
Sent By skennedy Date 2019-01-16 Time 11:35 Rev Time 0.00
Received By skennedy Date 2019-01-16 Time 11:35 Sent To  
Notes
2019-01-16 11:36:11NO ELECTRICAL WAS SUBMITTED WITH THIS NEWLY DESIGNED
 PLAN SET. PLEASE SEE THE COMMENTS UNDER THE BUILDING
 REVIEW.
  
  
 ELECTRICAL WORK COMPLETED UNDER PERMIT NUMBER 17071002.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By ppetty Date 2018-05-21 Time 11:15 Rev Time 0.00
Received By ppetty Date 2018-05-21 Time 10:29 Sent To  
Notes
2018-05-21 11:15:24PASS 5/21/2018 PHIL PETTY
 CHANGED STATUS TO FAIL ON 4-20-18. NEED TO REVIEW PLAN
 WHEN SUBMITTED.
  
  
 ELECTRICAL WORK COMPLETED UNDER PERMIT NUMBER 17071002.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-20 Cont ID  
Sent By jpearson Date 2018-04-20 Time 14:04 Rev Time 0.00
Received By jpearson Date 2018-03-09 Time 14:04 Sent To  
Notes
2018-04-20 14:18:09CHANGED STATUS TO FAIL ON 4-20-18. NEED TO REVIEW PLAN
 WHEN SUBMITTED.
  
  
2018-03-09 14:04:00ELECTRICAL WORK COMPLETED UNDER PERMIT NUMBER 17071002.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2019-06-04 Time   Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 14:16 Sent To  
Notes
2019-06-04 14:18:36DISCUSSED WITH CHIEF LEDUC, SEE 19011123 & 19020268.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2018-12-06 Cont ID  
Sent By scaldero Date 2018-12-06 Time 09:41 Rev Time 0.00
Received By scaldero Date 2018-12-06 Time 09:38 Sent To  
Notes
2018-12-06 09:40:28PERMIT # 18030117
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 3RD REVIEW - FAIL COMMENTS
  
 1) REPEAT COMMENT (3RD TIME): PER NFPA 101, CHAPTER 30
 - NEW APARTMENTS
 30.3.5.1: ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
 PLEASE PROVIDE DRAWING NOTE INDICATING COMPLIANCE OF
 THIS REQUIREMENT, OR PROVIDE JUSTIFICATION.
  
 2) REPEAT COMMENT (2ND TIME): A 1-HOUR FIRE RATED
 SEPERATION IS PROVIDED BETWEEN THE TWO BOTTOM UNITS,
 HOWEVER THE SEPERATION BETWEEN THE TOP AND BOTTOM UNITS
 IS NOT PROVIDED.
 PLEASE PROVIDE THE SEPERATION, IF ANY, BETWEEN THE TOP
 AND BOTTOM UNITS.
  
 3) SHEETS A-1 & A-2: THE FIRE RATED WALL IS MARKED AND
 IDENTIFIED, HOWEVER, THE FIRE RATING FOR THE FLOOR THAT
 SEPERATES THE TOP AND BOTTOM STORIES IS NOT PROVIDED.
  
 4) A LAWN SPRINKLER DRAWING IS PROVIDED, HOWEVER THIS
 DOES NOT APPLY TO COMMENT #1. A LAWN SPRINKLER SYSTEM
 IS NOT THE SAME AS A FIRE SPRINKLER SYSTEM.
  
  
 THANK YOU,
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-05-07 Cont ID  
Sent By scaldero Date 2018-05-07 Time 14:51 Rev Time 0.00
Received By scaldero Date 2018-05-07 Time 13:40 Sent To  
Notes
2018-05-07 14:48:48PERMIT # 18030117
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW -
  
 1) REPEAT COMMENT: PER NFPA 101, CHAPTER 30 - NEW
 APARTMENTS
 30.3.5.1: ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
 PLEASE PROVIDE DRAWING NOTE INDICATING COMPLIANCE OF
 THIS REQUIREMENT, OR PROVIDE JUSTIFICATION.
  
 2) A 1-HOUR FIRE RATED SEPERATION IS PROVIDED BETWEEN
 THE TWO BOTTOM UNITS, HOWEVER THE SEPERATION BETWEEN
 THE TOP AND BOTTOM UNITS IS NOT PROVIDED.
 PLEASE PROVIDE THE SEPERATION, IF ANY, BETWEEN THE TOP
 AND BOTTOM UNITS.
  
  
 THANK YOU,
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-23 Cont ID  
Sent By scaldero Date 2018-04-23 Time 11:03 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 10:59 Sent To I
Notes
2018-04-23 11:03:29PERMIT # 18030117
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PER NFPA 101, CHAPTER 30 - NEW APARTMENTS
 30.3.5.1: ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
  
 2) HARD-WIRED MULTI-STATION SMOKE ALARMS SHALL BE
 INSTALLED ON ALL LEVELS OF THE DWELLING UNIT, INSIDE
 EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS.
  
 3) PLEASE REVIEW AND COMPLY WITH ALL OTHER PLAN REVIEW
 COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 15:22 Rev Time 0.00
Received By skennedy Date 2019-04-26 Time 14:50 Sent To  
Notes
2019-04-29 14:50:33RESUB ROTUED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-16 Cont ID  
Sent By skennedy Date 2019-01-16 Time 11:32 Rev Time 0.00
Received By skennedy Date 2018-11-29 Time 14:32 Sent To  
Notes
2018-12-03 14:32:43C13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2018-05-01 Time 09:55 Sent To  
Notes
2018-05-02 09:56:02C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-17 Cont ID  
Sent By skennedy Date 2018-04-23 Time 07:59 Rev Time 0.00
Received By skennedy Date 2018-03-05 Time 15:50 Sent To  
Notes
2018-04-09 14:19:07R16
2018-03-21 07:15:213/21/18 REMOVED FROM REVIEW; A THIRD UNIT IS NOT
 PERMITTED, SEE ZONING REVIEW.
 PLAN HAS BEEN SCANNED AND ADDED AS AN ATTACHMENT TO
 THIS PERMT RECORD.
  
  
2018-03-06 15:50:33R14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 14:26 Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 14:26 Sent To  
Notes
2019-06-04 14:27:38MU 2019-012671-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-04-17 Cont ID  
Sent By skennedy Date 2018-04-17 Time 07:58 Rev Time 0.00
Received By skennedy Date 2018-04-17 Time 07:58 Sent To  
Notes
2018-04-18 15:19:10 
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 14:46 Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 14:46 Sent To  
Notes
2019-06-04 14:47:23SEE PERMIT 19051564. USED NEXT AVAILABLE SIZE VS.
 REQUIRED COOLING CAPACITY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-01-16 Cont ID  
Sent By skennedy Date 2019-01-16 Time 11:32 Rev Time 0.00
Received By skennedy Date 2019-01-16 Time 11:32 Sent To  
Notes
2019-01-16 12:20:383RD REVIEW: FBC 2017 5TH EDITION
 FBC 2017 EXISTING BUILDING
  
 THE RESUBMITTED PLAN INDICATES ONLY GENERALLY, THE USE
 OF A WINDOW CONDITIONING UNIT.
  
 PLEASE SEE FIRST REVIEW COMMENTS BELOW.
  
 PROVIDE AND ENERY SUBMITTAL, AND MECHANICAL PLAN PER
 FBC 107. NO REVIEW CAN BE CONDUCTED AS NOTHING IS
 PROVIDED.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-18 Cont ID  
Sent By skennedy Date 2018-05-18 Time 15:05 Rev Time 0.00
Received By skennedy Date 2018-05-18 Time 15:05 Sent To  
Notes
2018-05-18 15:08:222ND REVIEW: FBC 2017 5TH EDITION
 FBC 2017 EXISTING BUILDING
  
 THE RESUBMITTED PLAN INDICATES ONLY GENERALLY, THE USE
 OF A WINDOW CONDITIONING UNIT.
  
 PLEASE SEE FIRST REVIEW COMMENTS BELOW.
  
 PROVIDE AND ENERY SUBMITTAL, AND MECHANICAL PLAN PER
 FBC 107. NO REVIEW CAN BE CONDUCTED AS NOTHING IS
 PROVIDED.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-17 Cont ID  
Sent By skennedy Date 2018-04-17 Time 07:58 Rev Time 0.00
Received By skennedy Date 2018-04-17 Time 07:58 Sent To  
Notes
2018-04-18 15:22:461ST REVIEW: FBC 2017 5TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 PROVIDE AND ENERY SUBMITTAL, AND MECHANICAL PLAN PER
 FBC 107. NO REVIEW CAN BE CONDUCTED AS NOTHING IS
 PROVIDED.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 15:36 Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 15:36 Sent To  
Notes
2019-06-04 15:38:03IRRIGATION ONLY REVIEW BY GEORGE JOHNSON. SEPARATE
 APPLICATION REQUIRED & SEPARATE BACKFLOW REQUIRED.

Review Stop P PLUMBING
Rev No 4 Status N Date 2019-06-04 Cont ID  
Sent By skennedy Date 2019-06-04 Time 14:29 Rev Time 0.00
Received By skennedy Date 2019-06-04 Time 14:29 Sent To  
Notes
2019-06-04 14:30:00SEE 18080900

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-01-08 Cont ID  
Sent By gjohnson Date 2019-01-08 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2019-01-08 Time 17:08 Sent To  
Notes
2019-01-08 17:08:043ND REVIEW: FBC 2017 6TH EDITION
  
 IT IS UNCLEAR WHAT NEW PLUMBING WORK WAS DONE IN ORDER
 TO CLARIFY WHAT WAS DONE I AM REQUESTING A MEETING BE
 SCHEDULED SEE CONTACT INFORMATION BELOW, WITHOUT
 CLARIFICATION A PERMIT WILL NOT BE APPROVED.
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 3RD
 REQUEST
  
 1. PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.3.5.1.3
  
 3. PLACE NOTE ON PLAN PIPES MAY NEED TO BE EXPOSED FOR
 INSPECTION UP TO THE DISCRETION OF THE FIELD INSPECTOR.
 PER FBC PL 312
  
 PREVIOUS COMMENTS 2ND REQUEST
  
 1. THE LAVATORY,S NOT NOT APPEAR TO HAVE THE REQUIRED
 21" INFRONT OF FIXTURE PER FBC PL 405.3.1
  
 2. SHT. A.02 THE PIPING FOR THE NEW KITCHEN SHALL NOT
 CONNECT TO THE WET VENT OF THE BATHROOM PER FBC PL
 912.1
  
 3. PLEASE INDICATE ON THE PLAN LOCATION OF THE WATER
 HEATER AND MARK THE FIXTURE AS NEW OR EXISTING. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By gjohnson Date 2018-06-06 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2018-06-06 Time 11:14 Sent To  
Notes
2018-06-06 14:13:142ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.3.5.1.3
  
 3. PLACE NOTE ON PLAN PIPES MAY NEED TO BE EXPOSED FOR
 INSPECTION UP TO THE DISCRETION OF THE FIELD INSPECTOR.
 PER FBC PL 312
  
 NEW COMMENTS:
  
 1. THE LAVATORY,S NOT NOT APPEAR TO HAVE THE REQUIRED
 21" INFRONT OF FIXTURE PER FBC PL 405.3.1
  
 2. SHT. A.02 THE PIPING FOR THE NEW KITCHEN SHALL NOT
 CONNECT TO THE WET VENT OF THE BATHROOM PER FBC PL
 912.1
  
 3. PLEASE INDICATE ON THE PLAN LOCATION OF THE WATER
 HEATER AND MARK THE FIXTURE AS NEW OR EXISTING. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-10 Cont ID  
Sent By gjohnson Date 2018-04-10 Time 11:15 Rev Time 0.00
Received By gjohnson Date 2018-04-10 Time 09:54 Sent To  
Notes
2018-04-10 11:26:151ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.3.5.1.3
  
 2. PROVIDE DIMENSIONS FOR BATHROOMS TO SHOW COMPLIANCE
 WITH FBC PL 405.3.1
  
 3. PLACE NOTE ON PLAN PIPES MAY NEED TO BE EXPOSED FOR
 INSPECTION UP TO THE DISCRETION OF THE FIELD INSPECTOR.
 PER FBC PL 312
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-06-04 Cont ID  
Sent By awooten Date 2019-06-04 Time   Rev Time 0.00
Received By awooten Date 2019-06-04 Time   Sent To  
Notes
2019-06-04 15:20:07APPROVAL PER ANGELLA JONES-VANN TO MAKE THIRD UNIT
 LEGAL.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
2019-01-16 11:33:41SKIPPED THIS STOP AS BUILDING REVIEW RESPONSE IS THE
 MAIN ISSUE NEEDING RE-SUBMTTAL. SAK

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-10 Cont ID  
Sent By AW Date 2018-05-10 Time   Rev Time 0.00
Received By awooten Date 2018-05-10 Time   Sent To  
Notes
2018-05-10 11:10:09********************************ZONING
 NOTE************************************
  
 ZONING PASSED PER THE ZONING ADMINISTRATOR, ANGELLA
 VANN.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-03-22 Time   Rev Time 0.00
Received By   Date 2018-03-22 Time   Sent To  
Notes
2018-03-22 12:49:10********************************ZONING
 NOTE************************************
  
 ZONING PASSED PER THE ZONING ADMINISTRATOR, ANGELLA
 VANN.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AW Date 2018-03-20 Time   Rev Time  
Received By   Date 2018-03-20 Time   Sent To  
Notes
2018-03-20 13:59:05********************************************ZONING
 REVIEW FAILED*********************************
  
 THE THIRD UNIT IS NOT PERMITTED. PERMIT HISTORY SHOWS
 ONLY 2 UNITS AND CURRENT ZONING IS A SINGLE FAMILY
 DISTRICT.
  
 ALANA WOOTEN
 ASSOICATE PLANNER
 561-822-1449