2018-03-16 14:15:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERED DRAWINGS DO NOT LIST
 THE GENERAC 32 KW MODEL RG032 GENERATOR DOCUMENTS THAT
 WERE SUBMITTED. THERE ARE NO 32 KW GENERATORS LISTED ON
 THE AMERICAST GENERATOR PAD DRAWINGS. SUBMIT TWO SETS
 OF MATCHING DOCUMENTS. FBC-R301.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-12 Cont ID  
Sent By jleahy Date 2018-03-12 Time 16:31 Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 16:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-04-23 Cont ID  
Sent By tklarge Date 2018-04-23 Time 06:13 Rev Time 0.00
Received By tklarge Date 2018-04-23 Time 05:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-04-04 Cont ID  
Sent By lcrespo Date 2018-04-04 Time 14:18 Rev Time 0.00
Received By lcrespo Date 2018-04-04 Time 14:18 Sent To  
Notes
2018-04-04 14:29:1704/04/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS NOTE
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) SECOND NOTICE, THE PRINTED INFORMATION ON THE SURVEY
 FOR THE GAS IS SO SMALL IT CAN BARELY BE READ. SUBMIT
 THE SURVEY WITH NOTES THAT CAN BE READ. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) SECOND NOTICE, THE SIZING TABLE COPIES FOR THE
 SCHEDULE 40 METALLIC PIPE AND PE PIPE ARE BARELY
 LEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES OF THESE
 SIZING TABLES. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SECOND NOTICE, THE SIZING TABLE YOU SUBMITTED FOR
 THE SCHEDULE 40 METALLIC PIPE HAS A MINIMUM LENGTH OF
 10 FEET FOR A SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR
 A 3/4 INCH LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE
 SHOWING THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM
 SIZE PIPE ON THE LOW PRESSURE SIDE TO THE GENERATOR
 SHALL BE 1 INCH.
 4) SECOND NOTICE, SUBMIT PAGES 40 & 41 OF THE
 MANUFACTURES SPECS FOR THE REGULATORS. THESE SHEETS
 DETAIL THE INSTALLATION METHOD FOR THE REGULATORS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SECOND NOTICE, THERE IS AN EXPIRED GAS PERMIT ON
 THIS PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594
 ) THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A
 FINAL GAS INSPECTION. PLEASE DISCUSS THIS WITH THE
 CURRENT OWNER OF THE PROPERTY AND I CAN BE CONTACTED
 WITH ANY QUESTIONS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By tklarge Date 2018-03-14 Time 09:11 Rev Time 0.00
Received By tklarge Date 2018-03-14 Time 05:36 Sent To  
Notes
2018-03-14 06:26:191) THE PRINTED INFORMATION ON THE SURVEY FOR THE GAS IS
 SO SMALL IT CAN BARELY BE READ. SUBMIT THE SURVEY WITH
 NOTES THAT CAN BE READ. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE SIZING TABLE COPIES FOR THE SCHEDULE 40 METALLIC
 PIPE AND PE PIPE ARE BARELY LEGIBLE. SUBMIT TWO CLEAR
 AND LEGIBLE COPIES OF THESE SIZING TABLES. WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) THE SIZING TABLE YOU SUBMITTED FOR THE SCHEDULE 40
 METALLIC PIPE HAS A MINIMUM LENGTH OF 10 FEET FOR A
 SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR A 3/4 INCH
 LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE SHOWING
 THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM SIZE PIPE
 ON THE LOW PREESSURE SIDE TO THE GENERATOR SHALL BE 1
 INCH.
 4) SUBMIT PAGES 40 & 41 OF THE MANUF. SPECS FOR THE
 REGULATORS. THESE SHEETS DETAIL THE INSTALLATION METHOD
 FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1.
 5) NOTE: THERE IS AN EXPIRED GAS PERMIT ON THIS
 PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594 )
 THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A FINAL
 GAS INSPECTION. PLEASE DISCUSS THIS WITH THE CURRENT
 OWNER OF THE PROPERTY AND I CAN BE CONTACTED WITH ANY
 QUESTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-23 Cont ID  
Sent By tklarge Date 2018-04-23 Time 06:14 Rev Time 0.00
Received By tklarge Date 2018-04-12 Time 14:37 Sent To  
Notes
2018-04-13 14:37:55RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-04 Cont ID  
Sent By rmcdouga Date 2018-04-04 Time 14:19 Rev Time 0.00
Received By lcrespo Date 2018-03-23 Time 09:59 Sent To  
Notes
2018-03-26 09:59:12RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-16 Cont ID  
Sent By rmcdouga Date 2018-03-16 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2018-03-02 Time 08:12 Sent To  
Notes
2018-03-06 08:12:34ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-04-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-19 Time 17:02 Sent To G
Notes
2018-04-19 17:02:50LANDSCAPE SCREENING REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-03-27 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-27 Time 11:27 Sent To  
Notes
2018-03-27 11:28:401.) LABEL ALL SETBACKS FOR PROPOSED GENERATOR (SIDE,
 REAR, FRONT)
 2.) LANDSCAPE SCREENING REQUIRED. PROVIDE A NOTE ON
 PLAN
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-03-09 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-09 Time 09:33 Sent To  
Notes
2018-03-09 09:36:511.) LABEL PROPOSED FRONT SETBACK (CANNOT ENCROACH MORE
 THAN 4 FEET INTO REQUIRED 25 FOOT FRONT SETBACK)
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]