Plan Review Stops For Permit 18030063 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-04-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-02 |
Time |
07:28 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-02 |
Time |
07:03 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-03-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-16 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-16 |
Time |
14:02 |
Sent To |
|
|
Notes |
2018-03-16 14:15:10 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD ENGINEERED DRAWINGS DO NOT LIST | | THE GENERAC 32 KW MODEL RG032 GENERATOR DOCUMENTS THAT | | WERE SUBMITTED. THERE ARE NO 32 KW GENERATORS LISTED ON | | THE AMERICAST GENERATOR PAD DRAWINGS. SUBMIT TWO SETS | | OF MATCHING DOCUMENTS. FBC-R301.1 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-03-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-03-12 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-03-12 |
Time |
16:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-04-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-04-23 |
Time |
06:13 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-04-23 |
Time |
05:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-04-04 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-04-04 |
Time |
14:18 |
Sent To |
|
|
Notes |
2018-04-04 14:29:17 | 04/04/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS NOTE | | | | A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME | | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1) SECOND NOTICE, THE PRINTED INFORMATION ON THE SURVEY | | FOR THE GAS IS SO SMALL IT CAN BARELY BE READ. SUBMIT | | THE SURVEY WITH NOTES THAT CAN BE READ. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 2) SECOND NOTICE, THE SIZING TABLE COPIES FOR THE | | SCHEDULE 40 METALLIC PIPE AND PE PIPE ARE BARELY | | LEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES OF THESE | | SIZING TABLES. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SECOND NOTICE, THE SIZING TABLE YOU SUBMITTED FOR | | THE SCHEDULE 40 METALLIC PIPE HAS A MINIMUM LENGTH OF | | 10 FEET FOR A SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR | | A 3/4 INCH LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE | | SHOWING THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM | | SIZE PIPE ON THE LOW PRESSURE SIDE TO THE GENERATOR | | SHALL BE 1 INCH. | | 4) SECOND NOTICE, SUBMIT PAGES 40 & 41 OF THE | | MANUFACTURES SPECS FOR THE REGULATORS. THESE SHEETS | | DETAIL THE INSTALLATION METHOD FOR THE REGULATORS. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 5) SECOND NOTICE, THERE IS AN EXPIRED GAS PERMIT ON | | THIS PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594 | | ) THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A | | FINAL GAS INSPECTION. PLEASE DISCUSS THIS WITH THE | | CURRENT OWNER OF THE PROPERTY AND I CAN BE CONTACTED | | WITH ANY QUESTIONS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | [email protected] | | 561-805-6720 | | | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-03-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-03-14 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-03-14 |
Time |
05:36 |
Sent To |
|
|
Notes |
2018-03-14 06:26:19 | 1) THE PRINTED INFORMATION ON THE SURVEY FOR THE GAS IS | | SO SMALL IT CAN BARELY BE READ. SUBMIT THE SURVEY WITH | | NOTES THAT CAN BE READ. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) THE SIZING TABLE COPIES FOR THE SCHEDULE 40 METALLIC | | PIPE AND PE PIPE ARE BARELY LEGIBLE. SUBMIT TWO CLEAR | | AND LEGIBLE COPIES OF THESE SIZING TABLES. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 3) THE SIZING TABLE YOU SUBMITTED FOR THE SCHEDULE 40 | | METALLIC PIPE HAS A MINIMUM LENGTH OF 10 FEET FOR A | | SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR A 3/4 INCH | | LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE SHOWING | | THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM SIZE PIPE | | ON THE LOW PREESSURE SIDE TO THE GENERATOR SHALL BE 1 | | INCH. | | 4) SUBMIT PAGES 40 & 41 OF THE MANUF. SPECS FOR THE | | REGULATORS. THESE SHEETS DETAIL THE INSTALLATION METHOD | | FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1. | | 5) NOTE: THERE IS AN EXPIRED GAS PERMIT ON THIS | | PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594 ) | | THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A FINAL | | GAS INSPECTION. PLEASE DISCUSS THIS WITH THE CURRENT | | OWNER OF THE PROPERTY AND I CAN BE CONTACTED WITH ANY | | QUESTIONS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-04-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-04-23 |
Time |
06:14 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-04-12 |
Time |
14:37 |
Sent To |
|
|
Notes |
2018-04-13 14:37:55 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-04-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-04 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-03-23 |
Time |
09:59 |
Sent To |
|
|
Notes |
2018-03-26 09:59:12 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-03-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-16 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-02 |
Time |
08:12 |
Sent To |
|
|
Notes |
2018-03-06 08:12:34 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-04-19 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2018-04-19 |
Time |
17:02 |
Sent To |
G |
|
Notes |
2018-04-19 17:02:50 | LANDSCAPE SCREENING REQUIRED | | | | PAUL GREILICH, SENIOR PLANNER | | 561-822-1443 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-03-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2018-03-27 |
Time |
11:27 |
Sent To |
|
|
Notes |
2018-03-27 11:28:40 | 1.) LABEL ALL SETBACKS FOR PROPOSED GENERATOR (SIDE, | | REAR, FRONT) | | 2.) LANDSCAPE SCREENING REQUIRED. PROVIDE A NOTE ON | | PLAN | | | | PAUL GREILICH, SENIOR PLANNER | | 561-822-1443 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
PG |
Date |
2018-03-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2018-03-09 |
Time |
09:33 |
Sent To |
|
|
Notes |
2018-03-09 09:36:51 | 1.) LABEL PROPOSED FRONT SETBACK (CANNOT ENCROACH MORE | | THAN 4 FEET INTO REQUIRED 25 FOOT FRONT SETBACK) | | | | PAUL GREILICH, SENIOR PLANNER | | 561-822-1443 | | [email protected] |
|
|