2018-03-27 14:15:01 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18021224 |
| ADD: 425 KANUGA RD. |
| CONT: PERK CONSTRUCTION |
| TEL: 561-401-5984 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. MARCH 27/2018 |
| ACTION: DENIED |
| |
| 1) SHEET 006-LS2.1: |
| 1A) UNDER THE CODE ANALYSIS THE PLANS INDICATE THIS IS |
| A LEVEL 3 ALTERATION. PLEASE NOTE THIS BUILDING IS A |
| MIXED USE OCCUPANCY AS STATED IN THE PLANS AND WILL |
| ALSO NEED TO SHOW COMPLIANCE WITH THE 2017 EXISTING |
| BUILDING CODE SECTION 1001.2.2.1 PARTIAL CHANGE OF |
| OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP |
| OF A PORTION OF AN EXISTING BUILDING IS CHANGED, |
| SECTION 1012 SHALL APPLY. |
| |
| 1B) 2017 EXIST. BLDG. CODE 1012.4 MEANS OF EGRESS, |
| GENERAL. HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND |
| MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH TABLE |
| 1012.4. |
| |
| 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD |
| CATEGORY. WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS |
| MADE TO A HIGHER HAZARD CATEGORY (LOWER NUMBER) AS |
| SHOWN IN TABLE 1012.4, THE MEANS OF EGRESS SHALL COMPLY |
| WITH THE REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| FOR THE A-2 OCCUPANCY THE OCCUPANT LOAD IS OVER 50 |
| WHICH REQUIRE (2) MEANS OF EGRESS. EVEN THOUGH THIS IS |
| A MIXED OCCUPANCY NON-SEPARATED YOU CANNOT TAKE THE A2 |
| OCCUPANTS INTO THE HIGHER HAZARD F2 OCCUPANCY. PLEASE |
| REVIEW 2017 FBC-B SECTION 1016.2 EGRESS THROUGH |
| INTERVENING SPACES. |
| EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| ADJOINING OR INTERVENING ROOMS OR SPACES IN GROUP H, S |
| OR F OCCUPANCY WHERE THE ADJOINING OR INTERVENING ROOMS |
| OR SPACES ARE THE SAME OR A LESSER HAZARD OCCUPANCY |
| GROUP. |
| PLEASE PROVIDE THE 2ND MEANS OF EGRESS FOR THE A-2 |
| OCCUPANCY WITHOUT GOING THROUGH THE F-2 OCCUPANCY. |
| |
| 1C) THE LS2.1 SHEET UNDER THE HEADING MINIMUM NUMBER OF |
| EXITS ALSO INDICATES 50% OF THE EXITS ARE ACCESSIBLE. |
| 2017 EXISTING BUILDING CODE SECTION 1012.1.4 |
| ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION |
| 1012.8. 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT |
| UNDERGO A CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION |
| SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA |
| BUILDING CODE, ACCESSIBILITY. |
| 2017 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES. |
| (DOORWAYS). IN ADDITION TO ENTRANCES REQUIRED BY |
| 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT (2 X 0.60 |
| = 1.2 OR 2) OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH |
| 404. BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND |
| EXITS OF BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS |
| WITH THE GENERAL PUBLIC THAT ARE EXISTING, UNDER |
| CONSTRUCTION, OR UNDER CONTRACT FOR CONSTRUCTION WHICH |
| WOULD PREVENT A PERSON FROM USING SUCH ENTRANCES OR |
| EXITS SHALL BE REMOVED. PLEASE SHOW WHERE THE 2ND |
| ACCESSIBLE MEANS OF EGRESS WILL BE LOCATED AND NOT IN |
| THE F-2 OCCUPANCY. |
| |
| 1D) THE LS2.1 SHEET UNDER THE CODE ANALYSIS/ TOTAL |
| NUMBER OF OCCUPANTS NEEDS TO CORRECT THE A-2 OCCUPANT |
| LOAD. 1,578 SQ. FT. / 15 = 105.2 OR 106 OCCUPANT LOAD, |
| YOU ALWAYS ROUND UP ON OCCUPANTS TO THE NEXT WHOLE |
| NUMBER. FBC-B TABLE 1004.1.2. |
| |
| 1E) SHEET LS2.1 UNDER THE HEADING FIRE RESISTANCE |
| RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON |
| SEPARATION DISTANCE (TABLE 602). PLEASE PROVIDE A |
| SURVEY SHOWING THE DISTANCE FROM BOTH THE REAR WALL AND |
| WALL CLOSEST TO THE RAILROAD TRACKS. |
| 2017 EXISTING BUILDING CODE 1012.6 EXTERIOR WALL |
| FIRE-RESISTANCE RATINGS. HAZARD CATEGORIES IN REGARD TO |
| FIRE-RESISTANCE RATINGS OF EXTERIOR WALLS SHALL BE IN |
| ACCORDANCE WITH TABLE 1012.6. |
| 1012.6.1 EXTERIOR WALL RATING FOR CHANGE OF OCCUPANCY |
| CLASSIFICATION TO A HIGHER HAZARD CATEGORY. |
| WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| HIGHER HAZARD CATEGORY AS SHOWN IN TABLE 1012.6, |
| EXTERIOR WALLS SHALL HAVE FIRE RESISTANCE AND EXTERIOR |
| OPENING PROTECTIVES AS REQUIRED BY THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| 1F) SHEET LS2.1 SHOW COMPLIANCE WITH: 2017 EXISTING |
| BUILDING CODE SECTION 1012.6.3 OPENING PROTECTIVES. |
| OPENINGS IN EXTERIOR WALLS SHALL BE PROTECTED AS |
| REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING. WHERE |
| OPENINGS IN THE EXTERIOR WALLS ARE REQUIRED TO BE |
| PROTECTED BECAUSE OF THEIR DISTANCE FROM THE LOT LINE, |
| THE SUM OF THE AREA OF SUCH OPENINGS SHALL NOT EXCEED |
| 50 PERCENT OF THE TOTAL AREA OF THE WALL IN EACH STORY. |
| 2017 FBC-B TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL |
| OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE |
| OF OPENING PROTECTION. |
| |
| 1G) THE LS2.1 SHEET SHOWS THE PROPOSED EXITS, BUT DOES |
| NOT PROVIDE COMPLIANCE WITH 2017 FBC-B SECTION 1028.5 |
| ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE SHALL |
| PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC |
| WAY. |
| |
| 1H) THE LS2.1 SHEET INDICATES THE USE OF A LIFT. PLEASE |
| PROVIDE THE ASME STANDARD THIS LIFT IS TO BE DESIGNED |
| TOO? PLEASE ALSO PROVIDE THE MANUFACTURES SPEC ON THIS |
| LIFT. |
| 2017 ACCESSIBILITY CODE SECTIONS: |
| 408.1 LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL |
| COMPLY WITH 408 AND WITH ASME A17.1 (INCORPORATED BY |
| REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1). |
| THEY SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME |
| A17.1. ELEVATOR OPERATION SHALL BE AUTOMATIC. |
| 410.1. PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1 |
| (1999 EDITION OR 2003 EDITION) (INCORPORATED BY |
| REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1). |
| PLATFORM LIFTS SHALL NOT BE ATTENDANT-OPERATED AND |
| SHALL PROVIDE UNASSISTED ENTRY AND EXIT FROM THE LIFT. |
| |
| 1I) THE LS2.1 SHEET WILL NEED TO HAVE MORE EXIT |
| DIRECTIONAL LIGHT TO COMPLY WITH THE 2017 FBC-B 1013.1. |
| WHERE REQUIRED. THE PATH OF EGRESS TRAVEL TO EXITS AND |
| WITHIN EXITS SHALL BE MARKED BY READILY VISIBLE EXIT |
| SIGNS TO CLEARLY INDICATE THE DIRECTION OF EGRESS |
| TRAVEL IN CASES WHERE THE EXIT OR THE PATH OF EGRESS |
| TRAVEL IS NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS. |
| INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE |
| MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH |
| THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT |
| PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE |
| LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS |
| LESS, FROM THE NEAREST VISIBLE EXIT SIGN. |
| |
| 2) THE LIFE SAFETY SHEET LS2.1 DOES NOT SHOW COMPLIANCE |
| WITH THE 2014 FBC-ACCESSIBILITY CODE; |
| 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| SEATING SPACES AND STANDING SPACES AT THE DINING |
| SURFACES SHALL COMPLY WITH 902. |
| |
| 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| SURFACES AND WORK SURFACES. |
| |
| 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| BE PROVIDED TO ALL DINING AREAS, AND BARS INCLUDING |
| RAISED OR SUNKEN DINING AREAS, AND OUTDOOR DINING |
| AREAS. |
| |
| 2D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| TABLES, LUNCH COUNTERS, AND BOOTHS. |
| |
| 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 3) SHEET 003-A2. |
| 3A) IN THE BOTTOM RIGHT OF THE SHEET THERE IS A NEW |
| STAIRS. SHEET 004 A2.2 DETAIL 4 IS OF THE STAIRS AND |
| GUARD/HAND RAIL SYSTEMS. THE PLANS ARE SILENT AS TO THE |
| TYPE OF FRAMING THAT IS ANCHORED TO THE FLOOR AND THE |
| TYPE OF ANCHORS, SIZE AND QUANTITY OF ANCHORS FOR THE |
| FLOOR FRAMING AND WALL FRAMING THE STAIRS ARE ANCHORED |
| TOO? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3B) IN THE BOTTOM RIGHT OF THE SHEET THERE IS A NEW |
| STAIRS. SHEET 004 A2.2 DETAIL 4 IS OF THE STAIRS AND |
| GUARD/HAND RAIL SYSTEMS. THE PLANS ARE SILENT AS TO THE |
| TYPE OF MATERIAL THE GUARDRAIL AND HANDRAIL SYSTEMS ARE |
| MADE. THE PLANS DO NOT INDICATE HOW THEY ARE ANCHORED |
| TO THE FLOOR? |
| |
| 3B)(1)1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND |
| GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50 |
| POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH SECTION |
| 4.5.1 OF ASCE 7. |
| |
| 3B)(2) 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND |
| GUARDS SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD |
| OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE |
| 7. |
| |
| 3B)(3) 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE |
| RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND |
| PANEL FILLERS SHALL BE DESIGNED TO RESIST A |
| CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH |
| SECTION 4.5.1 OF ASCE 7. |
| |
| 4) SHEET 033A2.1 INDICATES THE USE OF OVERHEAD DOORS |
| WITH GLASS PANELS IDENTIFIED AS DOOR # 2. PLEASE SHOW |
| COMPLIANCE WITH 2017 FBC-B 2405.2 ALLOWABLE GLAZING |
| MATERIALS AND LIMITATIONS. SLOPED GLAZING SHALL BE ANY |
| OF THE FOLLOWING MATERIALS, SUBJECT TO THE LISTED |
| LIMITATIONS. |
| 4.1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING |
| MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE |
| LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM) |
| POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED |
| GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE |
| REQUIREMENTS OF SECTION 2607, HEAT-STRENGTHENED GLASS |
| OR FULLY TEMPERED GLASS. |
| |
| |
| 4.2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR |
| LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS |
| SPECIFIED IN ITEM 1 ABOVE. |
| ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED IN |
| EXCEPTIONS 2 AND 3 OF SECTION 2405.3. |
| FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE |
| SECTION 2610. GLASS-BLOCK CONSTRUCTION SHALL CONFORM TO |
| THE REQUIREMENTS OF SECTION 2110.1. |
| |
| THE SUBMITTED PRODUCT APPROVAL FL 16549-R9 IS FOR A |
| CLOPAY OVERHEAD GARAGE DOOR. |
| SHEET 2 OF 7 IDENTIFY WHICH MODEL, NUMBER AND NAME OF |
| DOOR TO BE INSTALLED. |
| SHEET 3 OF 7. PLEASE IDENTIFY THE BRAND AND IF THE DOOR |
| IS MODERN STEEL OR COMMERCIAL DOORS, IDENTIFY THE SIZE |
| OF PANEL FOR THE IMPACT RESISTANT GLAZING. ALSO |
| IDENTIFY BOTTOM CENTER GLAZING PATTERN TO BE INSTALLED. |
| SHEET 2 OF 5 DWG. B. IMPACT RESISTANT CONSTRUCTION |
| PLEASE IDENTIFY THE TYPE OF GLAZING TO BE INSTALLED TO |
| MEET THE WIND LOAD TESTING AND SAFETY GLAZING |
| REQUIREMENTS OF FBC-B 2405.2 AND OR 2606. |
| |
| 5) SHEET 005A2.3 EXTERIOR ELEVATIONS; |
| 5A) THE ENGINEERING CRITERIA LIST THE WIND EXPOSURE AS |
| AN EXPOSURE B. THE VULT AND VASD WIND SPEEDS ARE BOTH |
| EXPRESSED, BUT THE PRESSURES GIVEN DO NOT STATE IF THEY |
| ARE IN VULT OR VASD? 107.2.1.3 ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 5B) THE SOUTH ELEVATION SHOWS THE NEW STOREFRONT ENTRY |
| WITH TRANSOM, SIDE LIGHTS, BOTH VERTICAL AND HORIZONTAL |
| MULLIONS AND STOREFRONT DOORS. PLEASE PROVIDE |
| DOCUMENTATION OF CODE COMPLIANCE WITH: |
| |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| |
| 5C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 5D) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF |
| PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH |
| MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT |
| DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| |
| 5E) MULTICERAMICS EZ ROOF SYSTEM IS A |
| CONTINUOUS-FILAMENT, SINGLE-PLY, FLUID APPLIED ROOFING |
| SYSTEM. PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-B |
| 1507.15 LIQUID-APPLIED ROOFING. THE INSTALLATION OF |
| LIQUID-APPLIED ROOFING SHALL COMPLY WITH THE PROVISIONS |
| OF THIS SECTION. |
| |
| 5E)(1)1507.15.1 SLOPE. LIQUID-APPLIED ROOFING SHALL |
| HAVE A DESIGN SLOPE OF NOT LESS THAN ONE-FOURTH UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE). |
| |
| 5E)(2) 1507.15.2 MATERIAL STANDARDS. LIQUID-APPLIED |
| ROOFING SHALL COMPLY WITH ASTM C836, ASTM C957, ASTM |
| D1227 OR ASTM D3468, ASTM D6083, ASTM D6694 OR ASTM |
| D6947. |
| |
| 5F) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 6) BOTH THE LIFE SAFETY SHEET AND 003A2.1 SHOW THE |
| BREWHOUSE ON THE THICKENED SLAB, BUT NO OTHER |
| INFORMATION IS GIVEN TO THE PLATFORM, LANDING GUARDRAIL |
| NOR HANDRAIL. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| CONSTRUCTION / STRUCTURAL REQUIREMENTS FOR : |
| PLATFORMS SHOW COMPLIANCE WITH FBC-B 410.4. |
| STAIRS FBC-B 1011.7 STAIRWAY CONSTRUCTION / LIVE LOADS |
| TABLE 1607.1. |
| GUARDRAILS / HANDRAILS |
| 1607.8.1HANDRAILS AND GUARDS. |
| 1607.8.1.1 CONCENTRATED LOAD. |
| 1607.8.1.2 INTERMEDIATE RAILS. |
| |
| 7) 004A2.2 DETAILS 2 & 3 HAVE PROVIDED THE HORIZONTAL |
| DISTANCES APART BUT THE DETAILS DO NOT PROVIDE THE |
| REQUIRED HEIGHT FOR THE ACCESSIBLE ELEMENTS; |
| WATER CLOSET |
| GRAB BARS |
| SINK |
| URINAL |
| MIRROR |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO |
| DETERMINE CODE COMPLIANCE. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |