Plan Review Details - Permit 18021186
Plan Review Stops For Permit 18021186
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-04-18 Cont ID  
Sent By pvalenti Date 2019-04-18 Time 10:39 Rev Time 0.00
Received By pvalenti Date 2019-04-18 Time 07:26 Sent To  
Notes
2019-04-18 10:44:37***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 1. THE UPPER STORAGE AREA IS FOR STORAGE ONLY WITH A
 LIMITED OCCUPANCY. FOR ANY ALTERATION OR INCREASE IN
 OCCUPANCY, AN ADDITIONAL PERMIT WILL BE REQUIRED AS PER
 R. BROWN (BUILDING OFFICIAL).
  
 NOTE: STAMPED PLAN AND RECEIPT FOR IMPACT FEES ARE
 STILL DUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-29 Cont ID  
Sent By pvalenti Date 2019-01-29 Time 16:18 Rev Time 0.00
Received By pvalenti Date 2019-01-29 Time 16:18 Sent To  
Notes
2019-01-29 16:37:39****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1A OK
 1B OK
  
 1C (FBC B 505.2.1), (PAGES LS-1, A-1, S-1,& E-1) THE
 SECOND FLOOR STILL DOES NOT MEET THE CRITERIA OF A
 MEZZANINE. WE MAY BE ABLE TO LABEL THE SECOND FLOOR AS
 A MEZZANINE IF THE WALL SEPERATING THE EXISTING
 BUILDING FROM THE PROPOSED NEW SECTION HAS AN OPENING
 (LARGER THAN THE DOORWAY) TO CLEARLY COMBINE THE TWO
 AREAS AS ONE.
  
 2. OK
 3. & 4. OK THE STRUCTURE AT THE FRONT ENTRY AREA DOES
 NOT EXIST, PER THE CONTRACTOR AND THE STRUCTURE AT THE
 ADJACENT LOT TO THE WEST IS TO BE REMOVED THROUGH THE
 DEMO PERMIT # 18111011.
  
 5A & 5C (FBC B 107.3.5(4)/FBC B 704/FBC B 705), (PAGES
 A-1 & S-1) SPECIFIC DETAILS ARE NEEDED (AN APPROVED
 ASSEMBLY) ON HOW THE THREE HOUR FIRE RATING WILL BE
 ACHIEVED AT THE 8" CMU WALL.
  
 5B OK
  
 6. (FBC B 505.2.1), (PAGES LS-1, A-1, S-1 & E-1) SAME
 AS ITEM 1C (MEZZANINE).
  
 7. (FBC B 1014) (PAGE A-1) PROVIDE A DETAIL FOR THE
 HAND RAIL IN ADDITION TO THE GUARD RAIL FOR THE STAIRS.
  
 8, 9, 10, 11, 12, 13, & 14. OK
  
 15. COUNTY IMPACT FEES, TO BE PAID PRIOR TO COMPLETE
 PERMIT APPROVAL.
  
 16. OK
  
 17. MISSING THE RESIDENT INSPECTOR FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By pvalenti Date 2018-10-29 Time 09:12 Rev Time 0.00
Received By pvalenti Date 2018-10-29 Time 09:12 Sent To  
Notes
2018-10-29 09:34:33****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW FROM FASTRACK RESPONSE LIST:
  
 1.A. (OK).
 1.B. (OK).
 1.C. (PENDING PER FBC 505.2.1)(PAGES LS-1, A-1, S-1, &
 E-1) THIS ROOM DOES NOT APPEAR TO MEET THE CRITERIA FOR
 MEZZANINE. THE ROOM DESIGNATION NEEDS TO BE CHANGED ON
 PLANS.
 2. (OK).
 3. AND 4. (PENDING PER FBC 705.2) (PAGE LS-1) THE
 BUILDING AT FRONT ENTRANCE DOES NOT EXIST, PER THE
 CONTRACTOR. A CORRECTION OF THE BOUNDARIES SEPERATING
 THE TWO LOTS ON THE EXISTING SITE PLAN SHOWN ON PAGE
 LS-1 IS REQUIRED. AS FAR AS THE ADJOINING LOT ATTACHED
 ROOF/COVERED AREA GOES, THERE ARE TWO OPTIONS:
 1. APPLY FOR DEMO PERMIT TO REMOVE THE STRUCTURE OR,
 2. APPLY TO THE CITY ENGINEERING DEPARTMENT (USING THE
 APPLICATION FOR UNITY OF TITLE) FOR A UNITY OF CONTROL
 PERMIT IN LIEU OF A UNITY OF TITLE PERMIT. THIS
 APPROVAL MAY ALLOW YOU TO KEEP DEVELOPMENT RIGHTS.
 5.A. (PENDING PER FBC 107.3.5(4)/FBC 704/FBC 705) (PAGE
 A-1 & S-1) PROVIDE DETAILS SHOWING HOW THE 8? CMU WALL
 IS RATED FOR 3 HOURS.
 5.B. (OK) THE NEW WEST WALL IS NOT ON THE PROPERTY
 LINE.
 5.B.1 (OK) NO OPENINGS ON THE WEST SIDE OF THE ADJACENT
 BUILDING TO THE EAST, PER THE CONTRACTOR.
 5.C. (PENDING FBC 107.3.5(4)/FBC 704/FBC 705) (PAGE A-1
 & S-1) PROVIDE DETAILS SHOWING HOW THE 8? CMU WALLS ARE
 RATED FOR 3 HOURS.
 6. (PENDING FBC 505.2.1) (PAGE LS-1, A-1, S-1, & E-1)
 THE AREA LABELED AS MEZZANINE DOES NOT APPEAR TO MEET
 THE CRITERIA OF MEZZANINE PER FBC 505.2.1. PLEASE
 REVIEW & RESUBMIT.
 7. (PENDING FBC 1014) (PAGE A-1) THE LANDING IS NOW
 SHOWN ON PLAN. PROVIDE DETAIL FOR HAND RAIL IN ADDITION
 TO GUARD DETAIL.
 8. (PENDING FBC TABLE 1006.2.1) (PAGE LS-1) PROVIDE
 ACTUAL TRAVEL DISTANCE ON LIFE SAFETY PLAN AND SHOW
 RACKING/SHELVING LAYOUT.
 9. (PENDING FBC 107) (PAGE A-2) PROVIDE THE PRODUCT
 APPROVAL FOR WHAT APPEARS TO BE A MULLION BAR BETWEEN
 FIXED WINDOWS AT 2ND LEVEL WEST ELEVATION.
 10. ? 14. (OK)
 15. (PENDING) IMPACT FEES WILL BE PAID TO THE COUNTY
 UPON APPROVAL OF PLANS.
 16. (OK).
 17. (PENDING) STILL NEED THE RESIDENT INSPECTOR
 APPLICATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-08 Cont ID  
Sent By aclange Date 2018-03-08 Time 12:56 Rev Time 0.00
Received By aclange Date 2018-03-07 Time 09:26 Sent To  
Notes
2018-03-08 12:58:55****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. BUILDING CODE ANALYSIS.
  
 A. SHOWN AS EXISTING BUILDING CODE LEVEL TWO
 ALTERATION. THIS SHOULD BE SHOWN AS AN ADDITION.
  
 SHOW COMPLIANCE WITH THIS CHAPTER.
 1101.1 SCOPE.
 AN ADDITION TO A BUILDING OR STRUCTURE SHALL COMPLY
 WITH THE FLORIDA BUILDING CODE AS ADOPTED FOR NEW
 CONSTRUCTION WITHOUT REQUIRING THE EXISTING BUILDING OR
 STRUCTURE TO COMPLY WITH ANY REQUIREMENTS OF THOSE
 CODES OR OF THESE PROVISIONS, EXCEPT AS REQUIRED BY
 THIS CHAPTER. WHERE AN ADDITION IMPACTS THE EXISTING
 BUILDING OR STRUCTURE, THAT PORTION SHALL COMPLY WITH
 THIS CODE.
 1101.2 CREATION OR EXTENSION OF NONCONFORMITY.
 AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS.
 1101.3 OTHER WORK.
 ANY REPAIR OR ALTERATION WORK WITHIN AN EXISTING
 BUILDING TO WHICH AN ADDITION IS BEING MADE SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS FOR THE WORK AS
 CLASSIFIED IN CHAPTER 5.
 507.1 SCOPE. PROVISIONS FOR ADDITIONS SHALL APPLY WHERE
 WORK IS CLASSIFIED AS AN ADDITION AS DEFINED IN CHAPTER
 2.
 507.2 APPLICATION. ADDITIONS TO EXISTING BUILDINGS
 SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 11.
  
 B. SHOW THE PROPOSED USE OF THIS SPACE. THE PREVIOUS
 BUSINESS LICENSE IS CLOSED. FBC 107.1 SUBMITTAL
 DOCUMENTS
  
 C. LABEL ALL OF THE ROOMS . FBC 107.1 SUBMITTAL
 DOCUMENTS SEE ALSO FBC 107.3.5 FOR MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
  
 2. WORK ON EXISTING BUILDING NOTE SHOWN. FBC 107.1
 SUBMITTAL DOCUMENTS.
  
 3. PROVIDE INFORMATION FOR THE BUILDINGS AT THE FRONT
 ENTRANCE TO THE PROPERTY AND THE SHED ROOF ATTACHED TO
 THE WEST SIDE OF THE EXISTING BUILDING EXTENDING ON TO
 THE ADJACENT PROPERTY. IS IT THE INTENT TO KEEP THESE
 BUILDINGS? IF SO, SHOWN THIS THE ON PLANS. I COULD NOT
 LOCATE ANY PERMITS FOR THESE STRUCTURES. PROVIDE
 SUPPORTING DOCUMENTS FOR THE EXISTING STRUCTURES.
  
 FBC 107.1 SUBMITTAL DOCUMENTS. FBC 105.1 PERMITS
 REQUIRED.
 ANY OWNER OR OWNER?S AUTHORIZED AGENT WHO INTENDS TO
 CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH OR
 CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO
 ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT
 OR REPLACE ANY IMPACT-RESISTANT COVERINGS, ELECTRICAL,
 GAS, MECHANICAL OR PLUMBING SYSTEM, THE INSTALLATION OF
 WHICH IS REGULATED BY THIS CODE, OR TO CAUSE ANY SUCH
 WORK TO BE PERFORMED, SHALL FIRST MAKE APPLICATION TO
 THE BUILDING OFFICIAL AND OBTAIN THE REQUIRED PERMIT.
  
 4. PROVIDE A UNITY OF TITLE FOR 1405 ALLENDALE RD AND
 1413 ALLENDALE RD.
  
 5. FIRE WALLS 706.1.1 PARTY WALLS.
 ANY WALL LOCATED ON A LOT LINE BETWEEN ADJACENT
 BUILDINGS, WHICH IS USED OR ADAPTED FOR JOINT SERVICE
 BETWEEN THE TWO BUILDINGS, SHALL BE CONSTRUCTED AS A
 FIRE WALL IN ACCORDANCE WITH SECTION 706. PARTY WALLS
 SHALL BE CONSTRUCTED WITHOUT OPENINGS AND SHALL CREATE
 SEPARATE BUILDINGS.
 706.4 FIRE-RESISTANCE RATING.
 FIRE WALLS SHALL HAVE A FIRE-RESISTANCE RATING OF NOT
 LESS THAN THAT REQUIRED BY TABLE 706.4. A THREE HOUR
 RATING IS REQUIRED.
  
 A. EAST WALL OF THE ADDITION IS ON THE PROPERTY LINE
 WITH ZERO CLEARANCE TO THE ADJACENT BUILDING.
  
 B. THE WEST WALL IS ON THE PROPERTY LINE AND SHOWS NEW
 OPENINGS.
  
 B. CONFIRM THAT THE ADJACENT BUILDING DOES NOT HAVE ANY
 OPENINGS ON THE WEST SIDE.
  
 C. SHOW HOW THE EAST AND WEST WALL OF THE ADDITION WILL
 ACHIEVE A 3 HOUR RATING USING 8? BLOCK.
  
 D. THE EAST ELEVATION ON A-2 SHOWS AN OPENING AT THE
 COVERED PARKING LOCATION. NO OPENINGS ARE PERMITTED.
  
 E. NOTE: IF A UNITY OF TITLE IS PROVIDED AS MENTIONED
 ABOVE THIS WILL ELIMINATE THE REQUIREMENT OF THE 3 HOUR
 RATED WALL ON THE WEST SIDE.
  
 6. MEZZANINE
  
 THE AREA OF THE NEW MEZZANINE EXCEEDS THE ALLOWABLE
 AREA LIMITATIONS. SEE THE FOLLOWING SECTION AND
 EXCEPTION 1.
  
 FBC 505.2.1 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN
 A ROOM SHALL BE NOT GREATER THAN ONE-THIRD OF THE FLOOR
 AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTION OF A ROOM SHALL NOT BE INCLUDED IN
 A DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH
 THE MEZZANINE IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE MEZZANINE SHALL NOT BE
 INCLUDED IN THE FLOOR AREA OF THE ROOM.
  
 WHERE A ROOM CONTAINS BOTH A MEZZANINE AND AN EQUIPMENT
 PLATFORM, THE AGGREGATE AREA OF THE TWO RAISED FLOOR
 LEVELS SHALL BE NOT GREATER THAN TWO-THIRDS OF THE
 FLOOR AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE
 LOCATED.
 EXCEPTIONS: 1.THE AGGREGATE AREA OF MEZZANINES IN
 BUILDINGS AND STRUCTURES OF TYPE I OR II CONSTRUCTION
 FOR SPECIAL INDUSTRIAL OCCUPANCIES IN ACCORDANCE WITH
 SECTION 503.1.1 SHALL BE NOT GREATER THAN TWO-THIRDS OF
 THE FLOOR AREA OF THE ROOM.
  
 7. STAIRS
  
 THE VERTICAL RISE OF THE STAIRS IS OVER 12 FT. PROVIDE
 A LANDING.
  
 FBC 1011.8 VERTICAL RISE.
 A FLIGHT OF STAIRS SHALL NOT HAVE A VERTICAL RISE
 GREATER THAN 12 FEET (3658 MM) BETWEEN FLOOR LEVELS OR
 LANDINGS.
  
 8. SHOW EXISTING SECOND FLOOR PLAN AND INCLUDE THIS ON
 THE LIFE SAFETY PLANS WITH TRAVEL DISTANCES SHOWN.
 NOTE: TRAVEL DISTANCES SHOULD BE MEASURED USING THE
 NATURAL PATH OF TRAVEL AND NOT NECESSARILY DIAGONALS OF
 THE ROOM.
  
 FBC 1017.3 MEASUREMENT.
 EXIT ACCESS TRAVEL DISTANCE SHALL BE MEASURED FROM THE
 MOST REMOTE POINT WITHIN A STORY ALONG THE NATURAL AND
 UNOBSTRUCTED PATH OF HORIZONTAL AND VERTICAL EGRESS
 TRAVEL TO THE ENTRANCE TO AN EXIT.
  
 9. PRODUCT APPROVALS
  
 A. PRODUCT APPROVAL FOR GAF MODIFIED BITUMEN ROOF
 SYSTEM. SELECT THE ASSEMBLY TO BE USED. CHECK TO SEE IF
 LIMITATION NUMBER 7 APPLIES. IF SO PROVIDE SUPPORTING
 INFORMATION AS SHOWN. FBC 107.1 SUBMITTAL DOCUMENTS.
  
 B. PROVIDE A PRODUCT APPROVAL FOR WINDOW MULLIONS.
  
 10. PROVIDE A DIMENSIONED BATHROOM PLAN. FBC 107.1
 SUBMITTAL DOCUMENTS.
  
 11. STRUCTURAL NOTES NUMBER 5 SHOWS WOOD TRUSSES. THEY
 ARE NOT PERMITTED IN TYPE IIB CONSTRUCTION. FBC 107.1
 SUBMITTAL DOCUMENTS.
  
 12. PROVIDE LAYOUT / SHOP DRAWINGS FOR THE ROOF PRECAST
 DOUBLE TEES. ALSO SHOW BEARING LOCATION DETAIL. FBC
 107.1 SUBMITTAL DOCUMENTS.
  
 13. LINTEL SCHEDULE NOT PROVIDED. FBC 107.1 SUBMITTAL
 DOCUMENTS.
  
 14. PROVIDE A GEOTECHNICAL SOILS REPORT. FBC 1803.2
  
 15. IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 16. PERMIT VALUE IS TOO LOW.
  
 VALUATION
  
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
  
  
 17. RESIDENT INSPECTOR
  
 A RESIDENT INSPECTOR WILL BE REQUIRED FOR THIS
 PROJECT PER WEST PALM BEACH ADMINISTRATIVE CODE
 SECTION:
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS
 SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A
 CERTIFICATE CALLED FOR BY ANY PROVISION OF THE
 TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS
 UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-04-05 Time 12:24 Rev Time 0.00
Received By jpearson Date 2019-04-05 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-21 Cont ID  
Sent By jpearson Date 2019-01-21 Time 09:26 Rev Time 0.00
Received By jpearson Date 2019-01-21 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By jpearson Date 2018-09-24 Time 08:22 Rev Time 0.00
Received By jpearson Date 2018-09-24 Time 08:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jpearson Date 2018-03-14 Time 08:07 Rev Time 0.00
Received By jpearson Date 2018-03-14 Time 06:39 Sent To  
Notes
2018-03-14 08:07:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTION FOR RECEPTACLE IN BATHROOM.
 NEC 210.8(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2019-01-31 Cont ID  
Sent By RRossano Date 2019-01-31 Time   Rev Time 0.00
Received By rrossano Date 2019-01-31 Time   Sent To I
Notes
2019-01-31 08:00:04PASSED WITH PROVISO BY MGONZALEZ ON 4/02/18.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-04-02 Cont ID  
Sent By mgonzale Date 2018-04-02 Time   Rev Time  
Received By rrossano Date 2018-04-02 Time   Sent To  
Notes
2018-04-02 08:59:53PASSED WITH PROVISOS:
  
 SITE WILL ADHERE TO ARTICLE V. - STORMWATER POLLUTION
 PREVENTION
  
 HTTPS://LIBRARY.MUNICODE.COM/FL/WEST_PALM_BEACH/CODES/C
 ODE_OF_ORDINANCES?NODEID=PTIICOOR_CH90UT_ARTVSTPOPR
  
 SEC. 94-316. - VACANT LOT AND CONSTRUCTION SITE
 MAINTENANCE.
  
 HTTPS://LIBRARY.MUNICODE.COM/FL/WEST_PALM_BEACH/CODES/C
 ODE_OF_ORDINANCES?NODEID=PTIICOOR_CH94ZOLADERE_ARTXSUDI
 RE_DIV1GE_S94-316VALOCOSIMA
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 ? ? ? ? ?
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-04-01 Cont ID  
Sent By scaldero Date 2019-04-01 Time 10:42 Rev Time 0.00
Received By scaldero Date 2019-04-01 Time 10:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-01-10 Cont ID  
Sent By scaldero Date 2019-01-10 Time 11:15 Rev Time 0.00
Received By scaldero Date 2019-01-10 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-14 Cont ID  
Sent By scaldero Date 2018-09-14 Time 10:20 Rev Time 0.00
Received By scaldero Date 2018-09-14 Time 10:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-02 Cont ID  
Sent By scaldero Date 2018-03-02 Time 12:04 Rev Time 0.00
Received By scaldero Date 2018-03-02 Time 12:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-06-12 Cont ID  
Sent By jgomez Date 2019-06-12 Time 08:42 Rev Time 0.00
Received By jgomez Date 2019-06-10 Time 13:59 Sent To I
Notes
2019-06-11 14:00:08IMPACT FEES ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-04-18 Cont ID  
Sent By pvalenti Date 2019-04-18 Time 10:47 Rev Time 0.00
Received By pvalenti Date 2019-03-28 Time 13:16 Sent To  
Notes
2019-03-29 13:16:58C06

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-31 Cont ID  
Sent By cpuell Date 2019-01-31 Time 13:46 Rev Time 0.00
Received By cpuell Date 2019-01-07 Time 13:28 Sent To  
Notes
2019-01-08 13:28:53C26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-29 Cont ID  
Sent By cpuell Date 2018-10-29 Time 09:56 Rev Time 0.00
Received By cpuell Date 2018-09-11 Time 11:14 Sent To  
Notes
2018-09-13 11:14:23C26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-04 Cont ID  
Sent By shill Date 2018-04-04 Time 07:43 Rev Time 0.00
Received By shill Date 2018-02-28 Time 12:44 Sent To  
Notes
2018-03-01 12:44:15C18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-06-12 Cont ID  
Sent By jgomez Date 2019-06-12 Time 08:24 Rev Time 0.00
Received By jgomez Date 2019-06-12 Time 08:24 Sent To  
Notes
2019-06-12 08:26:19$1351.17 PAID (INCLUDES $32.96 INTERNET SERVICE
 CHARGE-BUILDING).
 MU-2019-016095.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By pvalenti Date 2019-04-18 Time 10:46 Rev Time 0.00
Received By pvalenti Date 2019-04-18 Time 10:45 Sent To  
Notes
2019-04-18 10:47:35***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 REVIEW DENIED:
  
 IMPACT FEES (STAMPED PLAN AND RECEIPT FROM COUNTY) ARE
 STILL DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-07 Cont ID  
Sent By aclange Date 2018-03-07 Time 12:34 Rev Time 0.00
Received By aclange Date 2018-03-07 Time 12:34 Sent To  
Notes
2018-03-07 12:34:57IMPACT FEES
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-04-15 Cont ID  
Sent By ccole Date 2019-04-15 Time 09:12 Rev Time 0.00
Received By ccole Date 2019-04-15 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-01-14 Cont ID  
Sent By ccole Date 2019-01-14 Time 10:27 Rev Time 0.00
Received By ccole Date 2019-01-14 Time 10:27 Sent To  
Notes
2019-01-14 10:39:303RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18021186
 1/14/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR OPENING ON THE WEST SIDE OF THE
 BUILDING MUST BE RELOCATED BECAUSE IT IS WITHIN THE
 REQUIRED 10' MINIMUM CLEARANCE TO THE VEHICLE DRIVE AND
 PARKING AREA- SECTION 401.4 FBC M.
  
 2) PLEASE IDENTIFY THE COVERED PARKING AREA AS EITHER A
 GARAGE ON CARPORT. PLEASE NOTE THAT PRIVATE GARAGES AND
 CARPORTS ARE CLASSIFED AS U OCCUPANCIES AND SHALL HAVE
 FIRE SEPARATION FROM S-1 OCCUPANCIES. PLEASE SEE
 SECTION 406.3.1 AND TABLE 602 FBC B.
  
 3) AS PREVIOUSLY REQUESTED PLEASE SUBMIT A FL. PRODUCT
 APPROVAL AND/OR MIAMI-DADE NOA FOR THE LOUVER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-25 Cont ID  
Sent By ccole Date 2018-09-25 Time 16:14 Rev Time 0.00
Received By ccole Date 2018-09-25 Time 16:14 Sent To  
Notes
2018-09-25 16:32:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18021186
 9/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: THE VENTILATION SCHEDULE SHOWS NO O/A
 PROVIDED TO THE WAREHOUSE, AND THE PLAN SHOWS AN
 UNDERSIZED EXHAUST FAN AND NO MEANS OF PROVIDING MAKEUP
 AIR OR CROSS-VENTILATION.
  
 2) E-1: PLEASE PROVIDE ELEVATION DRAWINGS OF THE
 CARPORT TO VERIFY THAT IT MEETS THE CRITERIA OF AN OPEN
 PARKING GARAGE AS DEFINED IN SECTION 406.5.2 FBC B.
  
 3) E-1: OPENING PROTECTION REQUIRED AT THE NEW EXHAUST
 FAN LOCATION IN THE WALL- SECTION 1609.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By ccole Date 2018-03-15 Time 08:31 Rev Time 0.00
Received By ccole Date 2018-03-15 Time 07:36 Sent To  
Notes
2018-03-15 08:49:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18021186
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW.
 PLEASE INDICATE HOW THE WAREHOUSE, MEZZANINE, AND
 TOILET ROOM WILL BE VENTILATED- REFER TO SECTION 401.2.
 DEPENDING ON WHICH METHOD IS TO BE USED- EITHER NATURAL
 OR MECHANCIAL- VENTILATION CALCULATIONS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 402.2 OR TABLE
 403.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By gjohnson Date 2019-01-23 Time 15:50 Rev Time 0.00
Received By gjohnson Date 2019-01-23 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By gjohnson Date 2018-10-10 Time 10:48 Rev Time 0.00
Received By gjohnson Date 2018-10-10 Time 10:38 Sent To  
Notes
2018-10-10 10:58:122ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT HAS NOT BEEN
 COMPLIED WITH.
  
 1. THE NEW BATHROOM SHALL COMPLY WITH FBC ACC 213,
 PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3, 604.2,
 604.3, 604.4, 604.5.1, 604.5.2, 604.7, 606.3
  
 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 (405 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE
 SIDE WALL OR PARTITION
  
 604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION.
  
 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
  
 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
  
 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE
  
 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
  
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2. PROVIDE DIMENSIONS ON THE CLEAR FLOOR SPACE FOR THE
 TOILET AND LAVATORY ALSO SHOW THE OVERALL DIMENSIONS OF
 THE BATHROOM. PER WPB AMEND TO FBC 107.2.1
  
 3. PLUMBING PAGE MISSING FROM NEW PLAN SET PLEASE
 PROVIDE PLUMBING PLANS INCLUDING BUT NOT LIMITED TO
 WATER AND SANITARY ISOMETRIC DRAWINGS. PER WPB AMEND TO
 FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By gjohnson Date 2018-03-20 Time 11:27 Sent To ENG
Notes
2018-03-20 12:50:021ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW BATHROOM SHALL COMPLY WITH FBC ACC 213,
 PLEASE SHOW COMPLIANCE WITH FBC ACC 603.3, 604.2,
 604.3, 604.4, 604.5.1, 604.5.2, 604.7, 606.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2019-01-17 Time   Rev Time 0.00
Received By pgreilic Date 2019-01-15 Time 16:45 Sent To  
Notes
2019-01-17 13:14:13PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-09-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-09-19 Time 14:37 Sent To  
Notes
2018-09-19 14:38:25PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-03-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-14 Time 10:45 Sent To  
Notes
2018-03-14 10:46:361.) PROVIDE A SITE PLAN WITH DIMENSIONS OF EXISTING
 BUILDING, DIMENSIONS OF PROPOSED ADDITION, AND PROPOSED
 SETBACKS
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]