Plan Review Details - Permit 18021167
Plan Review Stops For Permit 18021167
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-07 Cont ID  
Sent By pleduc Date 2018-03-07 Time   Rev Time 0.00
Received By pleduc Date 2018-03-07 Time 11:11 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By pleduc Date 2018-03-01 Time   Rev Time 0.00
Received By pleduc Date 2018-03-01 Time 11:13 Sent To I
Notes
2018-03-01 11:24:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
 THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS
 THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN.
  
 PLEASE PROVIDE CALCULATIONS DETAILS.
  
  
 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF
 THE FLEX DROP SPRINKLERS.
  
 PLEASE PROVIDE SHEETS THAT MATCH THE NEW HYDRAULIC
 CALCULATIONS.
  
  
  
 3) THERE IS NO CEILING GRID DETAIL OR SPEC SHEETS THAT
 WILL SUPPORT THE NEW FLEX DROPS. THE DRAWING IS VERY
 LIMITED WITH NO SPEC SHEET BACKUP.
  
 PLEASE PROVIDE GREATER DETAIL AND SPEC SHEETS FOR THE
 BRACKET AND GRID.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-08 Cont ID  
Sent By cpuell Date 2018-03-08 Time 10:28 Rev Time 0.00
Received By cpuell Date 2018-03-05 Time 11:11 Sent To  
Notes
2018-03-06 11:11:56RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-01 Cont ID  
Sent By cpuell Date 2018-03-01 Time 15:23 Rev Time 0.00
Received By cpuell Date 2018-02-27 Time 09:11 Sent To  
Notes
2018-02-28 09:11:44ROUTED TO FIRE INBOX