Plan Review Details - Permit 18021167
Plan Review Stops For Permit 18021167 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-03-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-03-07 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-03-07 |
Time |
11:11 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-03-01 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-03-01 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-03-01 |
Time |
11:13 |
Sent To |
I |
|
Notes |
2018-03-01 11:24:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | OVER. | | THERE IS NO HYDRAULIC CALCULATION SUBMITTED THAT SHOWS | | THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN. | | | | PLEASE PROVIDE CALCULATIONS DETAILS. | | | | | | 2) THERE ARE NO SPEC SHEETS FOR THE TYPE AND/OR SIZE OF | | THE FLEX DROP SPRINKLERS. | | | | PLEASE PROVIDE SHEETS THAT MATCH THE NEW HYDRAULIC | | CALCULATIONS. | | | | | | | | 3) THERE IS NO CEILING GRID DETAIL OR SPEC SHEETS THAT | | WILL SUPPORT THE NEW FLEX DROPS. THE DRAWING IS VERY | | LIMITED WITH NO SPEC SHEET BACKUP. | | | | PLEASE PROVIDE GREATER DETAIL AND SPEC SHEETS FOR THE | | BRACKET AND GRID. | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-03-08 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-03-08 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-03-05 |
Time |
11:11 |
Sent To |
|
|
Notes |
2018-03-06 11:11:56 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-03-01 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-03-01 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-02-27 |
Time |
09:11 |
Sent To |
|
|
Notes |
2018-02-28 09:11:44 | ROUTED TO FIRE INBOX |
|
|
|