Plan Review Details - Permit 18021046
Plan Review Stops For Permit 18021046
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-11-01 Cont ID  
Sent By skennedy Date 2018-11-01 Time 15:36 Rev Time 0.00
Received By skennedy Date 2018-11-01 Time 15:36 Sent To  
Notes
2018-11-01 16:04:58THE HORIZONTAL FLOOR ASSEMBLY IS TO BE MAINTAIN TO
 PROVIDE THE EXISTING DEGREE OF FIRE SEPARATION. IF THE
 FLOORING IS TO BE COVERED WITH ADDITIONAL FLOORING,
 PROVIDE A SOUND INSULATION SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-10-18 Cont ID  
Sent By jgomez Date 2018-10-18 Time 17:40 Rev Time 0.00
Received By jgomez Date 2018-10-18 Time 14:57 Sent To  
Notes
2018-10-04 16:59:26RESIDENTIAL (R2) ALTERATION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1) THE OWNER OR OWNER'S LEGALLY AUTHORIZED AGENT NEED
 TO CERTIFY AT THE BOTTOM OF THE ENERGY CALCULATIONS
 PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 2) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE
 APT ON THE SECOND FLOOR. NOTE: TENANT SEPARATION WALL
 DETAIL "F" ON SHEET S1A DOESN'T PROVIDE SPECIFICATIONS
 FOR APPROVED HORIZONTAL ASSEMBLY. IT ONLY SPECIFIES THE
 WALL ASSEMBLY UL-U311. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR APPROVED HORIZONTAL FIRE RATED
 ASSEMBLY AS REQUIRED . SEC. 420.3 FBC.
  
 RESPONSE:
 NEW DETAIL "G" ON SHEET S1A:
 A) THE TIME ASSIGNED FOR WOOD JOISTS IS 10 MINUTES NOT
 20 MINUTES. SEE TABLE 722.6.2(2). REVISE AS REQUIRED.
 NOTE: KEEP IN MIND THAT NEED TO GET 1 HOUR FIRE RATED
 HORIZONTAL ASSEMBLY. NEED TO REVISE ASSEMBLY TO MEET
 THE ONE HOUR FIRE RATING.
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE FLOOR
 ASSEMBLY SUB FLOORING AND FINISH FLOOR AS REQUIRED BY
 SEC. 722.6.2.4. FBC.
  
 C) PROVIDE COMPLETE SPECIFICATIONS FOR THE ADDITIONAL
 PROTECTION OF THE FLOOR ASSEMBLY AS REQUIRED BY SEC.
 722.6.2.4. FBC.
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR THE FASTENING OF
 THE FLOOR ASSEMBLY FRAMING MEMBERS AND MEMBRANES
 (PLYWOOD, GYPSUM BOARD ETC) AS REQUIRED BY SEC.
 722.6.2.6 FBC.
  
 E) THERE IS A FIRE NOTE ABOVE NEW DETAIL "G" THAT
 SPECIFIES 2 LAYERS OF 1/2" TYPE X GYPSUM BOARD.
 COORDINATE THIS INFORMATION WITH DETAIL G AND ALL WALL
 SECTIONS TO AVOID CONFUSION/DISCREPANCIES. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3) INFORMATION ON DRAWINGS NEED TO BE COORDINATED.
 INFORMATION ON TENANT SEPARATION HORIZONTAL ASSEMBLY
 DETAIL "G" NEEDS TO BE COORDINATED WITH CEILING
 INFORMATION ON ALL WALL SECTION DETAILS SHOWN ON SHEET
 S1 AND SHEET S1A. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4) CEILING INFORMATION UNDER THE EXISTING STAIRS DETAIL
 ON SHEET S1 WAS REVISED. PREVIOUS DETAIL SPECIFIED 2
 LAYERS OF 5/8" FIRE RATED GYPSUM BOARD. NEW DETAIL
 SPECIFIES ONLY ONE LAYER. CLARIFY/REVISE AS REQUIRED.
 NEED TO PROVIDE ONE HOUR FIRE RATED TENANT SEPARATION
 ASSEMBLY WITH THE ABOVE UNIT. SEC. 420.3 FBC.
 COORDINATE WITH ITEM #2 ABOVE.
  
 5) ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC.
 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE
 SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY.
 FLOORING UNDERLAYMENT
 SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 RESPONSE:
 ICC EVALUATION REPORT ESR-2540 SUBMITTED IS FOR 2X10
 WOOD JOIST FLOOR ASSEMBLIES. THIS DOESN'T MATCH
 EXISTING FLOOR FRAMING. PROVIDE COMPLIANCE WITH THE
 ABOVE A, B AND C SOUND INSULATION REQUIREMENTS.
 NOTE: COORDINATE WITH HORIZONTAL TENANT ASSEMBLY DETAIL
 G TO AVOID CONFLICTS/DELAYS.
  
  
 6) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES).
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NO PRODUCT APPROVAL WAS SUBMITTED. NEED PRODUCT
 APPROVAL AND SPECIFIC ASSEMBLY TO BE INSTALLED.
  
 B) ROOF TILE ADHESIVE REFERENCED IN ROOF TILE NOA
 15-0915.09 SUBMITTED. ROOF TILE ADHESIVE RTA-1
 SUBMITTED IS NOT THE ONE REFERENCED IN THE NOA FOR CLAY
 TILE. AND, CLEARLY MARK PADDY SIZE.
  
 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8) PROVIDE COMPLETE INFORMATION FOR THE FIRE RATING
 ASSEMBLY BELOW THE STAIRS AND BY THE PANTRY CLOSET ON
 FIRST FLOOR KITCHEN. SEC. 420.2 AND 420.3 FBC.
  
 RESPONSE:
 SPECIFIED ASSEMBLY DOESN'T PROVIDE 1 HOUR FIRE RATED
 ASSEMBLY. COORDINATE WITH ITEM #4 ABOVE.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 NOTE:
 ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-16 Cont ID  
Sent By jgomez Date 2018-07-16 Time 18:22 Rev Time 0.00
Received By jgomez Date 2018-07-13 Time 17:13 Sent To  
Notes
2018-07-17 09:30:38RESIDENTIAL (R2) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1 REVISE ENERGY CALCULATIONS SUBMITTED FOR APT. #1,
 APT. #2 AND APT. #3 (NOTE: COORDINATE INFORMATION ON
 ALL 3 APARTMENTS TO AVOID CONFLICTS/DELAYS):
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED OWNER'S NAME. NEED CORRECT BUILDER'S NAME.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT PROPERLY ADDRESSED. NEED CORRECT
 NAME OF THE OWNER AND THE BUILDER.
  
 B)APT #1 AND APT #2: REVISE ATTIC INFORMATION SHOWN ON
 PAGE 2 OF 4. THERE IS NO ATTIC ABOVE THIS APARTMENT.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT PROPERLY ADDRESSED. THERE IS NOT
 ATTIC ABOVE THIS APARTMENT. CONSEQUENTLY THERE IS NOT
 VENTED ATTIC EITHER. THERE IS AN APARTMENT ON THE
 SECOND FLOOR. REVISE AS REQUIRED. NOTE: COORDINATE AND
 REVISE INFORMATION ON ITEM #10 ON PAGE 1 OF 4. WHY ONE
 APARTMENT HAS INSULATION AND THE OTHER DOESN'T?.
 CLARIFY WHY INFORMATION ON APT. # 2 SAYS "NO ATTIC" AND
 INFORMATION ON APT #1 SAYS "FULL ATTIC". COORDINATE ALL
 INFORMATION TO AVOID UNNECESSARY CONFLICTS/DELAYS.
  
 C)CRAWLSPACE IN APT #1 AND APT #2: : CLARIFY WHY ONE
 APARTMENT HAS INSULATION AND THE OTHER DOESN'T?. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)APT #1 AND APT #2: : CLARIFY WHY THE WINDOW U-FACTOR
 AND SHGC FACTOR IS DIFFERENT ON EACH APARTMENT.
 TYPICALLY CONTRACTOR USES SAME WINDOWS WHEN REPLACING
 THEM. IF DIFFERENT WINDOWS ARE USED, THEN CLEARLY
 IDENTIFY EACH WINDOW. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 E) APT #3: CLARIFY WHY THERE IS NO INSULATION ON ITEM
 #8 ON PAGE 1 OF 4. COORDINATE WITH INFORMATION GIVEN ON
 APT #1 AND APT #2. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 F)APT #3: REVISE ROOF INFORMATION SHOWN ON PAGE 1 OF 4
 AND PAGE 2 OF 4. ACCORDING TO PLANS THE CEILING JOISTS
 ARE 2X6. THEREFORE, R-30 BATT INSULATION DOESN'T FIT.
 R-30 BATT INSULATION IS ABOUT 9-1/2" THICK. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)APT #3: REVISE ROOF INFORMATION SHOWN ON PAGE 2 OF 4.
 THERE IS ON GABLE AREA ON A FLAT ROOF. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR ALL APARTMENTS. SEC. R405.4.3
 FBC- ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR. THIS WILL BE DONE AT
 TIME OF INSPECTIONS.
  
 2- ENGINEER OF RECORD TO REVISE INSULATION INFORMATION
 SHOWN ON PLANS. R-30 BATT INSULATION IS 9-1/2" +/-
 THICK. IT DOESN'T FIT ON ROOF JOIST AND FLOOR JOISTS
 SIZES SHOWN ON PLANS. REVISE AS REQUIRED. NOTE:
 COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE
 APT ON THE SECOND FLOOR. REPEAT COMMENT. NOTE: TENANT
 SEPARATION WALL DETAIL "F" ON SHEET S1A DOESN'T PROVIDE
 SPECIFICATIONS FOR APPROVED HORIZONTAL ASSEMBLY. IT
 ONLY SPECIFIES THE WALL ASSEMBLY UL-U311. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR APPROVED
 HORIZONTAL FIRE RATED ASSEMBLY AS REQUIRED . SEC. 420.3
 FBC.
  
 4-SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW
 OPENING CONTROL DEVICES REQUIRED BY SEC. 702.4
 FBC-EXISTING BUILDING.
 NOTE: PROVIDE INFORMATION SHOWING COMPLIANCE WITH ASTM
 F2090.
  
 5- ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC.
 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE
 SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY.
 FLOORING UNDERLAYMENT
 SOUND INSULATION MATERIAL:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
 6-DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. REPEAT
 COMMENT. ENGINEER TO SPECIFY FASTENING. THIS IS NOT BY
 OTHERS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES).
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 B) ROOF TILE.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- BASED ON THE MECHANICAL PLANS SUBMITTED, PROVIDE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE A/C DUCTWORK
 IS GOING TO BE INSTALLED. REMEMBER THAT THERE IS A FIRE
 RATED FLOOR/CEILING ASSEMBLY SEPARATING THE APT ABOVE.
 SEC. 711 FBC-BUILDING.
 NEED PLANS AND SPECIFICATIONS FOR THE CONSTRUCTION OF
 THE SOFFITS FOR A/C WORK.
  
 10- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE
 REPLACEMENT OF EXTERIOR WOOD STUDS. SPECIFY ALL
 CONNECTORS. SEC. 1609.1 FBC.
  
 11-ROOF FRAMING PLAN ON SHEET S1A:
 A) PROVIDE COMPLETE SECTION/DETAIL AT CANOPY ENTRY FOR
 APT #2 AND APT #3. IT'S NOT CLEAR HOW THE ROOF IS
 SUPPORTED. FRONT ELEVATION CALLS FOR COLUMNS, BUT ROOF
 FRAMING DETAIL DOESN'T SPECIFY ANY. SEC. 1609.1 FBC.
  
 B) LEDGER INFORMATION SHOWN ON THE ROOF FRAMING PLAN
 DOESN'T MATCH LEDGER INFORMATION SHOWN ON SECTION 1 ON
 SAME SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 12- PROVIDE COMPLETE INFORMATION FOR THE FIRE RATING
 ASSEMBLY BELOW THE STAIRS AND BY THE PANTRY CLOSET ON
 FIRST FLOOR KITCHEN. SEC. 420.2 AND 420.3 FBC.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
 NOTE:
 ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By jgomez Date 2018-05-02 Time 18:24 Rev Time 0.00
Received By jgomez Date 2018-05-01 Time 15:48 Sent To  
Notes
2018-05-01 17:28:50RESIDENTIAL (R2) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 1(A)REVISE ALL ENERGY CALCULATIONS SUBMITTED.
 A)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED OWNER'S NAME. NEED CORRECT BUILDER'S NAME.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B) THIS IS NOT NEW CONSTRUCTION. REVISE ITEM #1. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C) WALL INSULATION R-VALUE SHOWN ON ITEM #9A DOESN'T
 MATCH PLANS. SEE WALL TYPE LEGEND ON SHEET CVR FOR
 EXTERIOR WALL SPECIFICATIONS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D) CLARIFY WHY THE FLOOR INFORMATION SHOWN ON PAGE 2 OF
 4 DOESN'T SHOW THE R-VALUE SPECIFIED FOR THE RAISED
 FLOOR ON PAGE 1 OF 4. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 E) REVISE ROOF INFORMATION SHOWN ON PAGE 2 OF 4. THERE
 IS NO ROOF ABOVE THIS APARTMENT. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 F) REVISE ATTIC INFORMATION SHOWN ON PAGE 2 OF 4. THERE
 IS NO ATTIC ABOVE THIS APARTMENT. SEC. R101.5.1.1.2
 FBC- ENERGY CONSERVATION.
  
 G) REVISE WALLS INFORMATION SHOWN ON PAGE 2 OF 4.
 ORIENTATION OF WALLS DON'T MATCH ACTUAL ORIENTATION OF
 BUILDING. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H) REVISE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4.
 ORIENTATION DOESN'T MATCH ACTUAL ORIENTATION OF
 BUILDING. ALSO, REVISE AREA AND OVERHANG DEPTH AND
 SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 I) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 IMPORTANT NOTES:
 (1) BASED ON THE ENERGY CALCULATIONS SUBMITTED, THIS
 PROJECT REQUIRES AN ENVELOPE LEAKAGE TEST REPORT WITH
 ENVELOPE LEAKAGE NO GREATER THAN 4.00 ACH50
 (R402.4.1.2)
  
 (2)LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 1(B) ENGINEER OF RECORD TO COORDINATE WITH ENERGY
 CALCULATIONS SUBMITTED. PROVIDE SPECIFICATIONS FOR THE
 INSULATION ON THE RAISED FLOOR AS SPECIFIED ON ITEM 8A
 OF THE ENERGY CALCULATIONS. SEC. R103.2 FBC- ENERGY
 CONSERVATION.
  
 ORIGINAL COMMENT:
 PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY
 SEC. 908 FBC-EXISTING BUILDING.
  
 2- SHEET CVR:
 A)THIS IS NOT "MULTI-FAMILY DETACHED RESIDENCE(R2)".
 THIS DOESN'T MAKE SENSE. IF THEY WERE DETACHED, THEN
 THEY WOULD BE SINGLE FAMILY RESIDENCES. THE BUILDING
 CODE IN EFFECT IS THE 2017 NOT 2014. ALTERATION LEVEL 3
 NEEDS TO COMPLY WITH CHAPTER 9. REVISE INFORMATION
 SHOWN ON "SCOPE OF WORK" AS REQUIRED.
  
 ORIGINAL COMMENT:
 THIS IS NOT A SINGLE FAMILY RESIDENCE. THIS IS
 MULTIFAMILY BUILDING (R2). REVISE ALL THE INFORMATION
 SHOWN ON THIS SHEET THAT REFERENCE THE SINGLE FAMILY
 RESIDENCE AND ALL CODE SECTIONS REFERENCED. NEED TO
 REFERENCE SECTIONS FROM THE FBC-BUILDING.
 SEC. 310.4 FBC-BUILDING
  
 B) ALL FIRE RATED PARTITIONS NEED TO PROVIDE CONTINUITY
 AS REQUIRED BY SEC. 708.4 FBC-BUILDING. REVISE ALL FIRE
 RATED WALLS ASSEMBLIES AS REQUIRED TO MATCH PROPOSED
 INSTALLATION. DETAIL "F" ON SHEET S1A IS UNFEASIBLE TO
 BUILD THE WAY IS SHOWN. INTERIOR GYPSUM BOARD CAN NOT
 GO THRU THE FLOOR ASSEMBLY. ALSO, BOTTOM AND TOP
 STRUCTURAL CONNECTIONS NEED MORE INFORMATION. CLEARLY
 SPECIFY ALL CONNECTORS SHOWING THE LOAD PATH (FOR
 EXAMPLE: TOP AND BOTTOM PLATES TO THE EXISTING
 STRUCTURAL FRAMING MEMBERS). NOTE: COORDINATE ALL WALL
 DETAILS WITH FIRE RATED BEARING WALLS AND NON BEARING
 WALLS TO MATCH PROPOSED INSTALLATION.
  
 ORIGINAL COMMENT:
 WALL TYPE LEGEND: FIRE RATED WALL "F" DOESN'T MATCH
 FIRE RATED WALL ON SHEET S2. REVISE AS REQUIRED. AND,
 PROVIDE COMPLETE AND CLEAR WALL SECTION THAT MATCHES
 PROPOSED INSTALLATION.
 NOTE: NEED TO PROVIDE COMPLETE DETAILS AND SPECS FOR
 ALL WALLS FOR TENANT SEPARATION BETWEEN APT #1 AND APT
 #2. INCLUDING THE BEARING WALLS. SEC. 703.1
 FBC-BUILDING. INCLUDING THE FOYER AREA THAT WAS DIVIDED
 TO ALLOW SEPARATE ENTRANCE TO APT ABOVE. COORDINATE
 WITH UL ASSEMBLY U305 SPECIFIED ON SHEET S2.
  
 C) COMPLIED. EXISTENT RAILING TO REMAIN.
  
 3- BEARING WALL DETAIL "G" ON SHEET S1 DOESN'T SEEM TO
 COMPLY WITH A BEARING WALL. IT IS BEARING ON PLYWOOD
 INSTEAD OF A SUPPORTING STRUCTURAL MEMBER. MISMATCHING
 METAL AND WOOD CONNECTORS?. THERE IS NO COORDINATION
 WITH FIRE RATED PARTITIONS SHOWN ON SHEET S1A. ALSO
 NEED TO COORDINATE WITH ITEM #2B ABOVE. CONNECTIONS AT
 TOP AND BOTTOM DON'T SEEM TO WORK THE WAY THEY ARE
 SPECIFIED. FIRST FLOOR DEMOLITION PLAN CALLS FOR
 EXISTING GIRDER BEAM BY THE STAIRWAY AREA. ACCORDING TO
 CITY RECORDS, THERE WAS A CONTINUOUS WALL IN THIS AREA
 NOT A BEAM. ENGINEER NEEDS TO CLEARLY IDENTIFY ALL
 BEARING WALLS AND CLEARLY PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING REINFORCEMENT AT THE ENDS OF
 PROPOSED OPENINGS.
  
 ORIGINAL COMMENT:
 INFORMATION ON BEARING WALLS IS NOT CLEAR AND IS
 INCOMPLETE. CLEARLY IDENTIFY ALL BEARING AND NON
 BEARING WALLS. BEARING WALL TO BE REMOVED AND HOW ARE
 THEY REINFORCED. COORDINATE DEMOLITION PLANS WITH
 PROPOSED PLANS. SEC. 907 FBC-EXISTING BUILDING.
 NOTE: CLARIFY WHY THE 18"X18" COLUMN DOESN'T ALIGN WITH
 COLUMN ABOVE?
  
 4- TYPICAL WINDOW OPENING FRAMING DETAIL SUBMITTED
 DOESN'T PROVIDE ANY INFORMATION FOR CONNECTORS AT THE
 TOP OF THE WALL AND WINDOW HEADER. IT DOESN'T PROVIDE
 THE LOAD PATH. ALSO, IT DOESN'T SHOW ANY FULL LENGTH
 STUDS AT THE ENDS OF THE OPENING.
  
 ORIGINAL COMMENT:
 CLEARLY IDENTIFY ALL EXTERIOR STRUCTURAL WALLS THAT ARE
 DAMAGED AND PROVIDE COMPLETE STRUCTURAL DETAILS
 IDENTIFYING THE STRUCTURAL FRAMING MEMBERS AND ALL
 CONNECTORS. TYPICAL STRAPPING PLAN ON SHEET S1 IS
 INSUFFICIENT. SEC. 907 FBC-EXISTING BUILDING.
  
 5- NO INFORMATION SUBMITTED FOR NEW COLUMNS SHOWN ON
 THE PROPOSED SOUTH ELEVATION.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 COLUMNS SHOWN ON SHEET S2. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. 1609 FBC-BUILDING.
  
 6- MISSING INFORMATION ABOUT ROOF SHEATHING SPECS AND
 FASTENING. BEAM CONNECTIONS, ETC.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR
 NEW ROOF SHOWN ON SHEET S2 ON PROPOSED SOUTH ELEVATION.
 SPECIFY ALL FRAMING MEMBERS, PLYWOOD, CONNECTORS, ETC.
 SEC. 1609 FBC-BUILDING.
  
 7- SAME NOTE APPEARS ON PROPOSED SOUTH ELEVATION.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 EXISTING 4X4 POST CAN BE REPAIR/FIX AS SPECIFIED ON
 PROPOSED SOUTH ELEVATION ON SHEET S2. SEC. 1609
 FBC-BUILDING.
  
 8- SHEET S1:
 A) REPEAT COMMENT. DETAIL F ON SHEET S1A REFERENCE ON
 THE RESPONSE LETTER DOESN'T PROVIDE THE COMPLETE
 SPECIFICATIONS FOR THE FLOOR/CEILING FIRE RATED
 ASSEMBLY AND THE DETAIL F NEEDS TO BE REVISED.
 COORDINATE WITH ITEM #2B ABOVE.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE
 APT ON THE SECOND FLOOR. SEC. 901.2 FBC-EXISTING
 BUILDING.
  
 B)WINDOW "C" DOESN'T COMPLY.
  
 ORIGINAL COMMENT:
 PROPOSED BEDROOM WINDOWS DON'T COMPLY WITH THE
 EMERGENCY ESCAPE AND RESCUE SEC. 1030 FBC-BUILDING
 (SEC. 702.5 FBC-EXISTING BUILDING).
  
 C) NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW
 CONTROL DEVICES REQUIRED BY SEC. 702.4 FBC-EXISTING
 BUILDING.
  
 D) NEED TO COORDINATE WITH ITEM #2B ABOVE. ALSO, NEED
 TO PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 NEW WALL WILL PROVIDE CONTINUOUS FIRE RATING ON BOTH
 SIDES OF THE WALL CONSIDERING THE EXISTING STAIRS. HOW
 THE EXISTING STAIRS WILL BE SUPPORTED. ALSO, NEED TO
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR FIRE
 SEPARATION OF KITCHEN AREA ON APT #1 AND APT ABOVE.
 INCLUDE BOTTOM OF STAIRS AND PANTRY AREA OF FIRST FLOOR
 KITCHEN.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE WALL SECTION FOR NEW WALL AT FOYER
 AREA SEPARATING APT #1 FROM APT ABOVE. SEC. 903.1
 FBC-EXISTING BUILDING.
  
 E)NOT ADDRESSED. RESPONSE LETTER REFERENCES DETAIL WALL
 G. THIS DETAIL DOESN'T APPLY TO THE REQUESTED ITEM.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE OPENING FRAMING DETAIL AND
 SPECIFICATIONS FOR NEW DOOR AT APT ABOVE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. 907 FBC-EXISTING
 BUILDING.
  
 F) STILL NOT CLEAR. SHOWING BOTH.
  
 ORIGINAL COMMENT:
 TYPICAL INTERIOR PARTITION DETAIL IS NOT CLEAR. IS IT A
 WOOD FRAMED WALL OR METAL FRAMED WALL. SEC. 107.2.1
 CITY AMENDMENTS.
  
 G)COMPLIED.
  
 9- SHEET S2:
 A) COMPLIED.
  
 B) REVISE SPECIFICATIONS: SPECIFY TWO LAYERS OF
 WATER-RESISTIVE BARRIER AS REQUIRED BY SEC. 2510.6
 FBC-BUILDING. AND, SPECIFY NO LESS THAN THREE COATS OF
 STUCCO AS REQUIRED BY SEC. 2512.1 FBC-BUILDING.
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 APPLICATION OF NEW STUCCO FINISH OVER EXISTING STUCCO
 FINISH AS SPECIFIED ON PROPOSED SOUTH ELEVATION. SEC.
 2510 FBC-BUILDING.
  
 10- COMPLIED.
  
 11- RESPONSE LETTER STATES R-13 INSULATION ON WALLS,
 R-30 INSULATION ON 1ST FLOOR CEILING. THERMAL
 INSULATION AND SOUND INSULATION ARE TWO DIFFERENT
 THINGS. NEED TO COMPLY WITH THE SOUND AND IMPACT
 INSULATION AS REQUIRED BY SEC. 1207. PROVIDE
 SPECIFICATIONS ON PLANS. NOTE: COPIES OF THE REQUIRED
 TESTING FOR SPECIFIC PRODUCTS TO BE INSTALLED MAY BE
 SUBMITTED LATER AS DEFERRED SUBMITTAL, BUT BEFORE
 INSTALLATION.
  
 ORIGINAL COMMENT:
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC.
 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE
 SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY AND
 TENANT SEPARATION WALLS AS REQUIRED BY SEC. 1207
 FBC-BUILDING.
  
 12- THE MINIMUM ATTACHMENT RESISTANCE (26.1 FT-LBF) OF
 ADHESIVE SELECTED ON PAGE 5 OF 6 OF NOA 16-0112.08
 SUBMITTED DOESN'T MEET THE MINIMUM ATTACHMENT
 RESISTANCE OF TABLE 2A OF FRSA 5TH EDITION (REVISED).
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED.
  
 13- SELECTED ASSEMBLY ON PAGE 28-29 OF NOA 14-1030.02
 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED SIGNED AND SEALED RAS 117
 CALCULATIONS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA.
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION.
  
 ORIGINAL COMMENT:
 FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609
 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117
 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION.
  
 A)SHEET S1 DOESN'T SHOW WINDOW MULLION DETAIL AS
 REFERENCED ON HE RESPONSE LETTER. CLEARLY IDENTIFY
 MULLION SIZE ON PRODUCT APPROVAL.
  
 ORIGINAL COMMENT:
 WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 B) NO SUBMITTED. PROVIDE ACTUAL PRODUCT APPROVAL LISTED
 ON THE NOA FOR ROOF TILE.
  
 ORIGINAL COMMENT:
 ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD ON ITEM #12 ABOVE. AND SPECIFY PADDY SIZE. SEE
 ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
  
 C)NEED PRODUCT APPROVAL FOR ALL CONNECTORS SPECIFIED ON
 ALL PLANS AND DETAILS NOT JUST THE ONES SHOWN ON THE
 ROOF FRAMING PLAN.
  
 ORIGINAL COMMENT:
 ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGN PROFESSIONAL TO LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 15- THERE ARE SOME PRODUCT APPROVALS THAT ARE NOT
 REVIEWED (ENTRY DOOR).
  
 ORIGINAL COMMENT:
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 16-NEW COMMENT:
 BASED ON THE MECHANICAL PLANS SUBMITTED, PROVIDE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE A/C DUCTWORK
 IS GOING TO BE INSTALLED. REMEMBER THAT THERE IS A FIRE
 RATED FLOOR/CEILING ASSEMBLY SEPARATING THE APT ABOVE.
 SEC. 711 FBC-BUILDING.
  
  
  
 NOTE:
 ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By jgomez Date 2018-03-15 Time 18:35 Rev Time 0.00
Received By jgomez Date 2018-03-15 Time 12:12 Sent To  
Notes
2018-03-15 13:52:22RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 908 FBC-EXISTING BUILDING.
  
 2- SHEET CVR:
 A) THIS IS NOT A SINGLE FAMILY RESIDENCE. THIS IS
 MULTIFAMILY BUILDING (R2). REVISE ALL THE INFORMATION
 SHOWN ON THIS SHEET THAT REFERENCE THE SINGLE FAMILY
 RESIDENCE AND ALL CODE SECTIONS REFERENCED. NEED TO
 REFERENCE SECTIONS FROM THE FBC-BUILDING.
 SEC. 310.4 FBC-BUILDING
  
 B) WALL TYPE LEGEND: FIRE RATED WALL "F" DOESN'T MATCH
 FIRE RATED WALL ON SHEET S2. REVISE AS REQUIRED. AND,
 PROVIDE COMPLETE AND CLEAR WALL SECTION THAT MATCHES
 PROPOSED INSTALLATION.
 NOTE: NEED TO PROVIDE COMPLETE DETAILS AND SPECS FOR
 ALL WALLS FOR TENANT SEPARATION BETWEEN APT #1 AND APT
 #2. INCLUDING THE BEARING WALL. SEC. 703.1
 FBC-BUILDING. INCLUDING THE FOYER AREA THAT WAS DIVIDED
 TO ALLOW SEPARATE ENTRANCE TO APT ABOVE. COORDINATE
 WITH UL ASSEMBLY U305 SPECIFIED ON SHEET S2.
  
 C) IT IS NOT CLEAR IF THE SECOND FLOOR BALCONY RAILING
 IS GOING TO BE REPLACED OR NOT. SEE 2ND FLOOR
 DEMOLITION PLAN AND 2ND FLOOR PROPOSED PLAN. SEC.
 107.2.1 CITY AMENDMENTS. NOTE: IF RAILING IS GOING TO
 BE REPLACE, THEN PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS.
  
 3- INFORMATION ON BEARING WALLS IS NOT CLEAR AND IS
 INCOMPLETE. CLEARLY IDENTIFY ALL BEARING AND NON
 BEARING WALLS. BEARING WALL TO BE REMOVED AND HOW ARE
 THEY REINFORCED. COORDINATE DEMOLITION PLANS WITH
 PROPOSED PLANS. SEC. 907 FBC-EXISTING BUILDING.
 NOTE: CLARIFY WHY THE 18"X18" COLUMN DOESN'T ALIGN WITH
 COLUMN ABOVE?
  
 4- CLEARLY IDENTIFY ALL EXTERIOR STRUCTURAL WALLS THAT
 ARE DAMAGED AND PROVIDE COMPLETE STRUCTURAL DETAILS
 IDENTIFYING THE STRUCTURAL FRAMING MEMBERS AND ALL
 CONNECTORS. TYPICAL STRAPPING PLAN ON SHEET S1 IS
 INSUFFICIENT. SEC. 907 FBC-EXISTING BUILDING.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 COLUMNS SHOWN ON SHEET S2. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. 1609 FBC-BUILDING.
  
 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW ROOF SHOWN ON SHEET S2 ON PROPOSED SOUTH
 ELEVATION. SPECIFY ALL FRAMING MEMBERS, PLYWOOD,
 CONNECTORS, ETC. SEC. 1609 FBC-BUILDING.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW EXISTING 4X4 POST CAN BE REPAIR/FIX AS SPECIFIED ON
 PROPOSED SOUTH ELEVATION ON SHEET S2. SEC. 1609
 FBC-BUILDING.
  
 8- SHEET S1:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FLOOR/CEILING ASSEMBLY FOR TENANT SEPARATION WITH THE
 APT ON THE SECOND FLOOR. SEC. 901.2 FBC-EXISTING
 BUILDING.
  
 B) PROPOSED BEDROOM WINDOWS DON'T COMPLY WITH THE
 EMERGENCY ESCAPE AND RESCUE SEC. 1030 FBC-BUILDING
 (SEC. 702.5 FBC-EXISTING BUILDING).
  
 C) SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW
 CONTROL DEVICES REQUIRED BY SEC. 702.4 FBC-EXISTING
 BUILDING.
  
 D) PROVIDE COMPLETE WALL SECTION FOR NEW WALL AT FOYER
 AREA SEPARATING APT #1 FROM APT ABOVE. SEC. 903.1
 FBC-EXISTING BUILDING.
  
 E) PROVIDE COMPLETE OPENING FRAMING DETAIL AND
 SPECIFICATIONS FOR NEW DOOR AT APT ABOVE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. 907 FBC-EXISTING
 BUILDING.
  
 F) TYPICAL INTERIOR PARTITION DETAIL IS NOT CLEAR. IS
 IT A WOOD FRAMED WALL OR METAL FRAMED WALL. SEC.
 107.2.1 CITY AMENDMENTS.
  
 G) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS,
 INCLUDING LOCATION FOR THE STAIRWAY HANDRAILS. SEC.
 805.9 FBC-EXISTING-BUILDING.
  
 9- SHEET S2:
 A) REVISE THE DESIGN DATA FOR WIND LOADS.
 (1)RESIDENTIAL CODE DOESN'T APPLY TO R2 GROUPS. SEC.
 310.4 FBC-BUILDING. (2) REVISE THE DESIGN PRESSURES TO
 CORRESPOND TO THE MEAN ROOF HEIGHT OF THIS BUILDING.
 SEC. 1609 FBC-BUILDING.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 APPLICATION OF NEW STUCCO FINISH OVER EXISTING STUCCO
 FINISH AS SPECIFIED ON PROPOSED SOUTH ELEVATION. SEC.
 2510 FBC-BUILDING.
  
 10- FIRE ALARM IS REQUIRED BY SEC. 804.4.1.7
 FBC-EXISTING BUILDING. PROVIDE COMPLETE SPECIFICATIONS.
  
 11- ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS,
 AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED BY SEC.
 801.3 FBC-EXISTING BUILDING. SHOW COMPLIANCE WITH THE
 SOUND TRANSMISSION FOR FLOOR/CEILING ASSEMBLY AND
 TENANT SEPARATION WALLS AS REQUIRED BY SEC. 1207
 FBC-BUILDING.
  
 12- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED.
  
 13- FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 RAS 117 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD ON ITEM #12 ABOVE. AND SPECIFY PADDY SIZE. SEE
 ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGN PROFESSIONAL TO LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 NOTE:
 ENGINEER OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO AVOID PLAN REVIEW FEES AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-09-22 Cont ID  
Sent By jpearson Date 2018-09-22 Time 14:49 Rev Time 0.00
Received By jpearson Date 2018-09-22 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-07-17 Cont ID  
Sent By jpearson Date 2018-07-17 Time 08:00 Rev Time 0.00
Received By jpearson Date 2018-07-17 Time 05:52 Sent To  
Notes
2018-07-17 07:45:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. ALL LOADS SUPPLIED ARE THE SAME FOR EACH PANEL
 EVEN THOUGH THERE ARE DIFFERENCES IN EACH UNIT. ALSO,
 THE PANEL SCHEDULE SHOWS 10 KW HEAT FOR THE AHU, BUT
 YOU HAVE INCLUDED 3.25 KW IN LOAD CALCULATION. THERE
 SHOULD BE ONE LOAD CALCULATION FOR ENTIRE SERVICE, AND
 THEN A LOAD CALCULATION FOR EACH SUB-PANEL ALSO. NEC
 220 (LOAD CALCULATION PROVIDED IS NOT CODE COMPLIANT.
 DEMAND FACTORS HAVE BEEN APPLIED TO EACH PANEL, AND
 THEN AGAIN BASED ON 220.84. THAT CODE SECTION EXPLAINS
 THAT THE LOADS ARE ALL ADDED TOGETHER AND THEN A DEMAND
 FACTOR IS APPLIED ONE TIME. PROVIDE ACCURATE LOAD
 CALCULATION.)
 2. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY
 SHOWS DISCONNECT A FEEDING NOTHING, DISCONNECT B
 FEEDING PANEL A, AND DISCONNECT C FEEDING PANEL B. ALSO
 NEED TO SHOW WIRE SIZE FOR SERVICE LATERAL. PROVIDE
 CORRECTIONS. NEC 215.5, 230, 250.50, 250.94, 408.30
 (THIS IS MOSTLY CORRECTED, BUT SHOWS A 130 AMP BREAKER
 FEEDING APARTMENT 3. THIS IS NOT A STANDARD FUSE SIZE
 PER 240.6. PROVIDE CORRECTION.)
 3. CORRECTED.
 4. PLAN SHOWS AFCI COVERAGE FOR SOME RECEPTACLE OUTLETS
 BUT NOT LIGHTING. THIS COVERAGE IS NOT TO CODE AND NOT
 COMPLETE. CODE REQUIRES: "BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED." PROVIDE CORRECTION. NEC 210.12 (NOTE
 PROVIDED FOR THIS IS IN CONFLICT WITH THE ABOVE
 STATEMENT. SOME AREAS WILL REQUIRE BOTH AFCI AND GFCI
 PROTECTION. THIS SHOULD ALSO BE REFLECTED IN PANEL
 SCHEDULE.)
 5. CORRECTED.
 6. PROVIDE ACCURATE PANEL SCHEDULES, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. ALL
 PANEL SCHEDULES PROVIDED ARE IDENTICAL EVEN THOUGH THE
 UNITS ARE DIFFERENT. CIRCUITS SHOULD HAVE UNIQUE
 IDENTIFICATION. NEC 210.8, 210.12, 215.5, 408.4 (AFCI
 PROTECTION NOT LISTED COMPLETELY.)
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
  
 NEW COMMENT:
  
 10. BE ADVISED THAT SOME OF THESE COMMENTS HAVE NOT
 BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
 (PLAN REVIEW FEE ADDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 17:11 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 16:16 Sent To  
Notes
2018-04-30 17:10:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. ALL LOADS SUPPLIED ARE THE SAME FOR EACH PANEL
 EVEN THOUGH THERE ARE DIFFERENCES IN EACH UNIT. ALSO,
 THE PANEL SCHEDULE SHOWS 10 KW HEAT FOR THE AHU, BUT
 YOU HAVE INCLUDED 3.25 KW IN LOAD CALCULATION. THERE
 SHOULD BE ONE LOAD CALCULATION FOR ENTIRE SERVICE, AND
 THEN A LOAD CALCULATION FOR EACH SUB-PANEL ALSO. NEC
 220 (NOT PROVIDED AS REQUESTED)
 2. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY
 SHOWS DISCONNECT A FEEDING NOTHING, DISCONNECT B
 FEEDING PANEL A, AND DISCONNECT C FEEDING PANEL B. ALSO
 NEED TO SHOW WIRE SIZE FOR SERVICE LATERAL. PROVIDE
 CORRECTIONS. NEC 215.5, 230, 250.50, 250.94, 408.30
 (NOT PROVIDED)
 3. PANEL C IS SHOWN IN 2 LOCATIONS, PROVIDE CORRECTION.
 FBC 107.2.1 (NOT CORRECTED)
 4. PLAN SHOWS AFCI COVERAGE FOR SOME RECEPTACLE OUTLETS
 BUT NOT LIGHTING. THIS COVERAGE IS NOT TO CODE AND NOT
 COMPLETE. CODE REQUIRES: "BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED." PROVIDE CORRECTION. NEC 210.12 (NOT
 PROVIDED)
 5. CORRECTED.
 6. PROVIDE ACCURATE PANEL SCHEDULES, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. ALL
 PANEL SCHEDULES PROVIDED ARE IDENTICAL EVEN THOUGH THE
 UNITS ARE DIFFERENT. CIRCUITS SHOULD HAVE UNIQUE
 IDENTIFICATION. NEC 210.8, 210.12, 215.5, 408.4 (NOT
 PROVIDED)
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 (NOT PROVIDED)
 8. CORRECTED.
 9. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1 (NOT PROVIDED)
  
 NEW COMMENT:
  
 10. BE ADVISED THAT SOME OF THESE COMMENTS HAVE NOT
 BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-06 Cont ID  
Sent By jpearson Date 2018-03-06 Time 07:26 Rev Time 0.00
Received By jpearson Date 2018-03-05 Time 16:14 Sent To  
Notes
2018-03-06 07:26:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. ALL LOADS SUPPLIED ARE THE SAME FOR EACH PANEL
 EVEN THOUGH THERE ARE DIFFERENCES IN EACH UNIT. ALSO,
 THE PANEL SCHEDULE SHOWS 10 KW HEAT FOR THE AHU, BUT
 YOU HAVE INCLUDED 3.25 KW IN LOAD CALCULATION. THERE
 SHOULD BE ONE LOAD CALCULATION FOR ENTIRE SERVICE, AND
 THEN A LOAD CALCULATION FOR EACH SUB-PANEL ALSO. NEC
 220
 2. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. PLAN CURRENTLY
 SHOWS DISCONNECT A FEEDING NOTHING, DISCONNECT B
 FEEDING PANEL A, AND DISCONNECT C FEEDING PANEL B. ALSO
 NEED TO SHOW WIRE SIZE FOR SERVICE LATERAL. PROVIDE
 CORRECTIONS. NEC 215.5, 230, 250.50, 250.94, 408.30
 3. PANEL C IS SHOWN IN 2 LOCATIONS, PROVIDE CORRECTION.
 FBC 107.2.1
 4. PLAN SHOWS AFCI COVERAGE FOR SOME RECEPTACLE OUTLETS
 BUT NOT LIGHTING. THIS COVERAGE IS NOT TO CODE AND NOT
 COMPLETE. CODE REQUIRES: ?BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION. NEC 210.12
 5. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13
 6. PROVIDE ACCURATE PANEL SCHEDULES, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. ALL
 PANEL SCHEDULES PROVIDED ARE IDENTICAL EVEN THOUGH THE
 UNITS ARE DIFFERENT. CIRCUITS SHOULD HAVE UNIQUE
 IDENTIFICATION. NEC 210.8, 210.12, 215.5, 408.4
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 8. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 9. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-09-21 Cont ID  
Sent By pleduc Date 2018-09-21 Time   Rev Time 0.00
Received By pleduc Date 2018-09-20 Time 15:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-03 Cont ID  
Sent By pleduc Date 2018-07-03 Time   Rev Time 0.00
Received By pleduc Date 2018-07-03 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-25 Cont ID  
Sent By pleduc Date 2018-04-25 Time   Rev Time 0.00
Received By pleduc Date 2018-04-24 Time 17:01 Sent To  
Notes
2018-04-25 13:15:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET S 1A - CALL-OUT DRAWING INDICATED AS DIAMOND G
 DOES NOT SHOW TYPE X DRYWALL ON THE CEILING. ALL
 CEILING AREAS SHALL BE TYPE X AS INDICATED IN CALL-OUT
 DRAWING DIAMOND F.
  
 PLEASE ENSURE ALL CEILING AREAS HAVE 1 HOUR FIRE RATED
 CONSTRUCTION FEATURES.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-20 Cont ID  
Sent By pleduc Date 2018-03-20 Time   Rev Time 0.00
Received By pleduc Date 2018-03-19 Time 11:19 Sent To  
Notes
2018-03-20 09:15:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CVR - THE PROPOSED PROJECT CHANGES A DUPLEX
 INTO A TRIPLEX CREATING A NEW APARTMENT BUILDING.
  
 PER NFPA 101, CHAPTER 3, DEFINITIONS
  
 3.3.36.3* APARTMENT BUILDING. A BUILDING OR PORTION
 THEREOF
 CONTAINING THREE OR MORE DWELLING UNITS WITH
 INDEPENDENT
 COOKING AND BATHROOM FACILITIES. (SAF-RES)
  
 PLEASE CORRECT.
  
  
 2) SHEET CVR - THERE IS NO APPLICABLE REFERNECED FIRE
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE
  
  
 3) SHEET S 1 - A FIRE SPRINKLER SYSTEM IS REQUIRED.
  
 PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS.
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH
 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 INSTALLED IN
 ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3
 AND 30.3.5.4. IN
 BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN
 ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION
 OF
 SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES,
 SHALL BE
 PERMITTED.
  
 PLEASE PROVIDE FOR THE REQUIREMENT AS WELL AS 61G
 DOCUMENTS PER FLORIDA STATUTE WITH THIS MASTER PERMIT.
  
  
  
 4) THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 SUPERVISED AND MONITORED.
  
 PER NFPA 101, CHAPTER 9, FIRE PREOTECTIONS SYSTEMS.
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY
 ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS
 SHALL BE INSTALLED
 AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE
 ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY
 SIGNAL SHALL BE
 PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE
 SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY
 QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED
 RECEIVING
 FACILITY.
 9.7.2.2 ALARM SIGNAL TRANSMISSION.
 9.7.2.2.1 WHERE SUPERVISION OF AUTOMATIC SPRINKLER
 SYSTEMS IS REQUIRED
 BY ANOTHER SECTION OF THIS CODE, WATERFLOW ALARMS SHALL
 BE TRANSMITTED
 TO AN APPROVED, PROPRIETARY ALARM-RECEIVING FACILITY, A
 REMOTE STATION, A
 CENTRAL STATION, OR THE FIRE DEPARTMENT.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND COMPLIANCE
 AS WELL AS SHOP DRAWING SUBMITTAL.
  
  
  
 5) SHEET S 1 - THERE ARE MULTIPLE DIAMOND SHAPED
 REFERNCES THAT DO NOT COINCIDE WITH ANY DRAWINGS OR
 SHEETS.
  
 PLEASE REVIEW AND PROVIDE THEIR DRAWING REFERENCES.
  
  
  
 6) SHEET S 1 - THERE APPEARS TO BE 1 HOUR RATED WALLS
 THAT INTERSECT WITH BEARING WALLS. THE BEARING WALLS DO
 NOT HAVE ANY RATING INDICATED.
  
 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL
 BE
 SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2.
 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF
 30.3.7.2,
 DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY
 WALLS AND
 FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE
 RESISTANCE RATING.
  
 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS
 SHALL BE
 SEPARATED FROM EACH OTHER BY WALLS AND FLOORS
 CONSTRUCTED AS FIRE
 BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE
 RATING.
  
 PLEASE REVIEW AND CORRECT WITH APPLICABLE RATED
 CONSTRUCTION AND LISTING.
  
  
  
 7) SHEET S 1 - THERE IS NO INDICATION OF ANY RATING OF
 THE STAIRWELL EXIT ACCESS.
  
 30.3.6 CORRIDORS.
 30.3.6.1 WALLS. EXIT ACCESS CORRIDOR WALLS SHALL COMPLY
 WITH
 30.3.6.1.1 OR 30.3.6.1.2.
 30.3.6.1.1 IN BUILDINGS NOT COMPLYING WITH 30.3.6.1.2,
 EXIT ACCESS
 CORRIDOR WALLS SHALL CONSIST OF FIRE BARRIERS IN
 ACCORDANCE WITH
 SECTION 8.3 THAT HAVE NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING.
 30.3.6.1.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 30.3.5.2, CORRIDOR WALLS SHALL HAVE A MINIMUM ?-HOUR
 FIRE
 RESISTANCE RATING.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 8) SHEET S 1 - THERE ARE NO REFERNECES TO ANY RATING
 FOR THE CEILING/FLOOR ASSEMBLY.
  
 30.3.7 SUBDIVISIONS OF BUILDING SPACES. BUILDINGS SHALL
 BE
 SUBDIVIDED IN ACCORDANCE WITH 30.3.7.1 OR 30.3.7.2.
 30.3.7.1 IN BUILDINGS NOT MEETING THE REQUIREMENT OF
 30.3.7.2,
 DWELLING UNITS SHALL BE SEPARATED FROM EACH OTHER BY
 WALLS AND
 FLOORS CONSTRUCTED AS FIRE BARRIERS HAVING A MINIMUM
 1-HOUR FIRE
 RESISTANCE RATING.
  
 30.3.7.2 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DWELLING UNITS
 SHALL BE
 SEPARATED FROM EACH OTHER BY WALLS AND FLOORS
 CONSTRUCTED AS FIRE
 BARRIERS HAVING A MINIMUM ?-HOUR FIRE RESISTANCE
 RATING.
  
 PLEASE REVIEW AND CORRECT.
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-18 Cont ID  
Sent By jgomez Date 2018-10-18 Time 17:44 Rev Time 0.00
Received By jgomez Date 2018-09-11 Time 11:05 Sent To I
Notes
2018-09-13 11:05:50B24

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 18:46 Rev Time 0.00
Received By gjohnson Date 2018-06-28 Time 14:53 Sent To  
Notes
2018-07-02 14:55:00B26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-14 Cont ID  
Sent By lmarchan Date 2018-05-14 Time 16:13 Rev Time 0.00
Received By lmarchan Date 2018-04-20 Time 14:30 Sent To  
Notes
2018-04-23 14:30:28B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-06 Cont ID  
Sent By lmarchan Date 2018-04-06 Time 15:50 Rev Time 0.00
Received By lmarchan Date 2018-02-26 Time 13:16 Sent To  
Notes
2018-02-27 13:16:27B12

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-11-01 Cont ID  
Sent By skennedy Date 2018-11-01 Time 10:37 Rev Time 0.00
Received By skennedy Date 2018-11-01 Time 10:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-10-12 Cont ID  
Sent By hmoser Date 2018-10-12 Time 10:41 Rev Time 0.00
Received By hmoser Date 2018-10-12 Time 09:48 Sent To B
Notes
2018-10-12 10:41:29PLAN DENIED
 REFER TO SECTION 61G15-23.002 FLORIDA STATUE. IF THE
 PLAN IS DRAWN ON
 ENGINEER PAPER IT MUST BE SIGNED AND SEALED BY THE
 ENGINEER.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-07-17 Cont ID  
Sent By cmontell Date 2018-07-17 Time 13:58 Rev Time 0.00
Received By cmontell Date 2018-07-17 Time 13:57 Sent To  
Notes
2018-07-17 13:55:42MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED TO SUBMIT 2 COPYS OF MECHANICAL PLANS (ONLY 1
 COPY SUBMITTED)
 2 - ANY DUCTS THROUGH PARTY WALLS NEED FIRE DAMPERS
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-03 Cont ID  
Sent By cmontell Date 2018-04-30 Time 12:43 Rev Time 0.00
Received By cmontell Date 2018-05-03 Time 15:37 Sent To  
Notes
2018-05-03 15:38:15NEED FIRE DAMPERS IN ALL DUCT PENETRATIONS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-05 Cont ID  
Sent By cmontell Date 2018-03-05 Time 15:08 Rev Time 0.00
Received By cmontell Date 2018-03-05 Time 15:05 Sent To  
Notes
2018-03-05 15:07:54MECHANICAL PLAN REVIEW FAIL
  
 1 - 2017 FLORIDA BUILDING CODE 107.1 GENERAL. ( NEED
 MCHANICAL PLANS )

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-11-01 Cont ID  
Sent By gjohnson Date 2018-11-01 Time 15:17 Rev Time 0.00
Received By gjohnson Date 2018-11-01 Time 15:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2018-09-27 Cont ID  
Sent By jesmith Date 2018-09-27 Time 14:53 Rev Time 0.00
Received By jesmith Date 2018-09-27 Time 14:41 Sent To  
Notes
2018-09-27 14:52:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 4TH REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. PLAN SHEET P-1 SHOWING WATER DISTRIBUTION IS MISSING
 FROM NEW SUBMITTAL. HAVING REVIEWED VOIDED P-1 SHEET
 REV 1, PLEASE NOTE THAT THE WATER DISTRIBUTION PLAN
 SHALL SHOW AN INDIVIDUAL COLD WATER SUPPLY WITH
 ACCESSIBLE VALVE PER FPC PL 606.1 (6) FOR EACH UNIT.
 THE DIAGRAM SHALL SHOW HOT AND COLD WATER DISTRIBUTION
 FOR EACH UNIT PER WPB FBC 702.1.
 A. PLEASE REVIEW RED LINED NOTES MADE ON VOIDED SHEET
 P-1 REV 1 FOR CLARIFICATION.
 2. ALL NEW SANITARY BRANCHES AND STACK(S) TO CONNECT,
 IN METHODS COMPLIANT WITH FBC PL 704.1 AND SECTION 706,
 TO THE EXISTING BUILDING DRAIN UPSTREAM OF THE EXTERIOR
 FOOTER AND NOTED AS SUCH ON THE SANITARY PLAN VIEW AND
 THE SANITARY ISOMETRIC PER WPB FBC 107.2.1.
 3. THE KITCHEN SINK IN APT #1 REQUIRES A VENT WHICH MAY
 BE AN AIR ADMITTANCE VALVE, RE-VENT OR THROUGH THE
 ROOF.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-08-02 Cont ID  
Sent By gjohnson Date 2018-08-02 Time 18:30 Rev Time 0.00
Received By gjohnson Date 2018-08-02 Time 18:00 Sent To  
Notes
2018-08-02 18:46:302ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE 2" LINE CONNECTING THE KITCHEN ON THE FIRST
 FLOOR SHALL BE VENTED BY A VENT THAT RUN THROUGH THE
 ROOF OR BE CONNECTED TO THE BUILDING DRAIN BEFORE
 EXITING BUILDING. PER FBC PL 904.1 AND MANUFACTURE
 SPECIFICATION.
  
 2. SHOW A COMPLETE BUILDING DRAIN ON THE FIRST FLOOR
 ISOMETRIC INCLUDING THE SOIL STACKS FROM SECOND FLOOR.
 PER WPB AMEND TO FBC 107.2.1.
  
 3. THE HORIZONTAL BRANCH DRAIN FOR THE WASHING MACHINE
 SHALL BE 3" IF USING AN AIR ADMITTANCE VALVE. PER
 MANUFACTURE INSTALLATION GUIDE.
  
 4. THE 3" SOIL STACKS THAT ARE RUNNING DOWN THROUGH THE
 EXTERIOR WALL MAR INTERFERE WITH THE WIDTH OF A 2 X 4
 WALL THE 3" FITTING ARE LARGER THAN THE INSIDE SPACE OF
 THE WALL ALSO WILL THE PIPE BE RUNNING DOWN THROUGH TH
 FOOTER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-04-27 Cont ID  
Sent By gjohnson Date 2018-04-27 Time 15:31 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 16:10 Sent To  
Notes
2018-04-27 15:31:002ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 2ND REQUEST 1. PROVIDE WATER ISOMETRIC FOR NEW BATHROOM
 ON 2ND FLOOR. WPB AMEND TO FBC 107.3.5.1.3(3)(13)
  
 2. THE SANITARY ISOMETRIC IS ONLY SHOWING THE WASHING
 MACHINE AND NEW BATHROOM ON 2ND FLOOR IS THIS THE ONLY
 NEW PIPING BEING DONE. WPB AMEND TO FBC 107.2.1
  
 3. ARE THE WATER HEATERS EXISTING TO REMAIN OR ARE THEY
 NEW PLEASE PLACE NOTE ON PLAN. WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By gjohnson Date 2018-03-14 Time 08:06 Rev Time 0.00
Received By gjohnson Date 2018-03-14 Time 07:23 Sent To  
Notes
2018-03-14 08:45:191ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE WATER ISOMETRIC SHOW EXISTING AND NEW. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. THE SOIL STACK FOR 2ND FLOOR IS NOT SHOWN ON 1ST
 FLOOR ISOMETRIC, THE LAUNDRY IS NOT SHOWN ON 2ND FLOOR
 ISOMETRIC SHOW ALL NEW AND EXISTING PIPING AND MARK IT
 AS EXISTING OR NEW. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. BACKFLOW REQUIRED ON WATER SERVICE SHOW ON WATER
 ISOMETRIC NEW OR EXISTING. PER WPB UTILITIES DEPARTMENT
 CROSS CONNECTION MANUAL
  
 4. THE COVER SHEET UNDER SCOPE OF WORK LISTED AS A
 SINGLE FAMILY HOME THIS DRELLING IS AN R2 OCCUPANCY PER
 FBC 310.4 PLEASE CLARIFY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status N Date 2018-11-01 Cont ID  
Sent By skennedy Date 2018-11-01 Time 10:47 Rev Time 0.00
Received By skennedy Date 2018-11-01 Time 10:46 Sent To  
Notes
2018-11-01 10:47:28ROOFING WILL BE BY DEFERRED SUBMITTAL.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2018-10-18 Cont ID  
Sent By jgomez Date 2018-10-18 Time 17:42 Rev Time 0.00
Received By jgomez Date 2018-10-18 Time 17:41 Sent To  
Notes
2018-10-18 17:44:271) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES).
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NO PRODUCT APPROVAL WAS SUBMITTED. NEED PRODUCT
 APPROVAL AND SPECIFIC ASSEMBLY TO BE INSTALLED.
  
 B) ROOF TILE ADHESIVE REFERENCED IN ROOF TILE NOA
 15-0915.09 SUBMITTED. ROOF TILE ADHESIVE RTA-1
 SUBMITTED IS NOT THE ONE REFERENCED IN THE NOA FOR CLAY
 TILE. AND, CLEARLY MARK PADDY SIZE.
  
 2) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 APPROVED:
 CLAY TILE NOA 15-0915.09

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2018-07-17 Cont ID  
Sent By jgomez Date 2018-07-17 Time 09:39 Rev Time 0.00
Received By jgomez Date 2018-07-17 Time 09:39 Sent To  
Notes
2018-07-17 09:40:181-- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION (NO FEES).
  
 A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 B) ROOF TILE.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
 2-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-05-02 Cont ID  
Sent By jgomez Date 2018-05-02 Time 18:21 Rev Time 0.00
Received By jgomez Date 2018-05-02 Time 18:21 Sent To  
Notes
2018-05-02 18:24:201- THE MINIMUM ATTACHMENT RESISTANCE (26.1 FT-LBF) OF
 ADHESIVE SELECTED ON PAGE 5 OF 6 OF NOA 16-0112.08
 SUBMITTED DOESN'T MEET THE MINIMUM ATTACHMENT
 RESISTANCE OF TABLE 2A OF FRSA 5TH EDITION (REVISED).
 REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY
 PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED.
  
 2- SELECTED ASSEMBLY ON PAGE 28-29 OF NOA 14-1030.02
 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED SIGNED AND SEALED RAS 117
 CALCULATIONS. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA.
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION.
  
 ORIGINAL COMMENT:
 FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609
 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117
 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 NOTE: THIS MAY BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL, BUT BEFORE INSTALLATION.
  
 A) NO SUBMITTED. PROVIDE ACTUAL PRODUCT APPROVAL LISTED
 ON THE NOA FOR ROOF TILE.
  
 ORIGINAL COMMENT:
 ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD ON ITEM #12 ABOVE. AND SPECIFY PADDY SIZE. SEE
 ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
  
  
 ROOF TILE NOA 16-0112.08
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jgomez Date 2018-03-16 Time 11:38 Rev Time 0.00
Received By jgomez Date 2018-03-16 Time 11:37 Sent To  
Notes
2018-03-16 11:40:131- FLAT ROOF NOA 15-1020.01 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609 FBC-BUILDING. IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 RAS 117 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. AND SPECIFY PADDY SIZE. SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
  
 APPROVED:
 1) ENTEGRA ROOF TILE NOA 16-0112.08
  

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-10-04 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-02 Time 16:45 Sent To  
Notes
2018-10-04 15:50:351.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2018-07-10 Time   Rev Time 0.00
Received By pgreilic Date 2018-07-06 Time 14:48 Sent To  
Notes
2018-07-10 09:29:371.) PROVIDE DEMENSIONS FOR ALL PROPOSED ROOMS
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-05-04 Time   Rev Time 0.00
Received By pgreilic Date 2018-05-04 Time 16:42 Sent To  
Notes
2018-05-04 16:43:13PLEASE INDICATE ON SITE PLAN/SURVEY IS BUILDING IS
 BEING EXPANDED. IF SO, PLEASE LABEL PROPOSED FRONT,
 REAR AND SIDE SETBACKS
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-04-06 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-05 Time 14:36 Sent To  
Notes
2018-04-06 10:42:011.) LABEL PROPOSED HEIGHT OF ALL ELEVATIONS
 2.) IS BUILDING FOOTPRINT BEING ALTERED? INDICATE ON
 PLAN IF SO
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy