Plan Review Details - Permit 18020938
Plan Review Stops For Permit 18020938
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-14 Cont ID  
Sent By shill Date 2018-06-14 Time 17:57 Rev Time 0.00
Received By shill Date 2018-06-14 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 18:36 Rev Time 0.00
Received By shill Date 2018-05-22 Time 15:28 Sent To  
Notes
2018-05-22 18:37:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 AS PLANS SUBMITTED FIRST REVIEW WERE SEVERELY
 DEFICIENT, THIS IS AN ENTIRELY NEW REVIEW.
  
 1. ALS1.1 SHOWS AN "EXISTING TENANT" ADJACENT TO TENANT
 2. THIS AREA IS BEING USED AS COMMON SPACE, ASSEMBLY
 OCCUPANCY. EITHER REVISE 16090638, OR INCLUDE THIS
 SPACE IN THIS PERMIT, OR SUBMIT A SEPARATE PERMIT FOR
 THIS SPACE, OR PROVIDE THE PERMIT OR REVISION NUMBER
 WHERE THIS HAS ALREADY BEEN REVIEWED, FBC 107. A PERMIT
 IS REQUIRED FOR A CHANGE OF OCCUPANCY.
  
 2. BASED ON RESPONSE LETTER, A REVISION SHOULD HAVE
 BEEN SUBMITTED UNDER 16090638 TO INDICATE THAT THE
 AMENITIES ASSOCIATED WITH THE SPIN STUDIO WERE NOT
 INSTALLED. AS THAT PERMIT IS VERY CLOSE TO C.O., BUT
 THE BUILDING PERMIT RECORD SHOULD CORRECTLY REFLECT
 WORK DONE, INCORPORATE THE INFORMATION INTO THIS PLAN
 (WORK SHOWN UNDER 16090638 FOR THIS SPACE WAS NOT
 DONE), FBC 107.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By jwitmer Date 2018-02-28 Time 10:55 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 16:11 Sent To  
Notes
2018-02-28 10:55:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020938
 ADD: 1401 CLARE AVENUE, SUITE :
 CONT: TIM GIVENS BUILDING & REMODELING
 TEL: 561-533-5828
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 28/ 2018
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS NOR THE PERMIT APPLICATION
 PROVIDE WHICH SUITE WORK IS TO BE COMPLETED UNDER THIS
 PERMIT.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE SUBMITTED PLANS STATE THERE ARE 4 SHEETS 1 OF 4
 FOR EXAMPLE, MISSING SHEET 2 OF 4 IN ALL THREE SETS.
 107.2.1.3 ADDITIONAL INFORMATION.
  
 3) PLEASE BE AWARE UNDER PERMIT 16090638/ REVISION
 17011285 (AS BUILT PLANS) THIS UNIT WAS CLASSIFIED AS A
 BUSINESS OCCUPANCY WITH AN EXISTING HANDICAPPED
 RESTROOM AND A COUNTER WITH BREAKROOM SINK. THE
 SUBMITTED PLANS DO NOT SHOW THIS ARRANGEMENT NOR DO
 THEY SHOW A DEMOLITION PLAN WITH THE REMOVAL OF THESE
 SYSTEMS NOR IS THERE A DEMOLITION PERMIT FOR THIS UNIT
 SHOWING THE REMOVAL OF THESE ELEMENTS.
 FURTHER MORE ADDITIONAL WORK HAS OCCURRED MAKING A TENT
 EFFECT(POLES, CANVAS AND ELECTRICAL FIXTURES AND HUNG
 LIGHTING), AT THE DOUBLE DOOR ENTRY AND CANVAS ON
 WALLS. 4 X THE FEE WILL BE CHARGED AGAINST THIS PERMIT
 FOR WORK COMPLETED WITHOUT THE BENEFIT OF A PERMIT.
  
 109.4 WORK COMMENCING BEFORE PERMIT ISSUANCE. ANY
 PERSON WHO COMMENCES ANY WORK ON A BUILDING, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEM BEFORE
 OBTAINING THE BUILDING OFFICIAL?S APPROVAL OR THE
 NECESSARY PERMITS SHALL BE SUBJECT TO A PENALTY FEE IN
 ADDITION TO THE REQUIRED PERMIT FEES, AS SET IN
 APPROVED SCHEDULE OF FEES.
  
 4) SINCE UNDER THE AS BUILT REVISION 17101285 THE
 TENANT SPACE IN QUESTION WAS NO LONGER A VANILLA BOX AN
 OCCUPANCY WAS ASSIGNED (BUSINESS) AND UNISEX RESTROOM
 WAS SHOWN ON THE PLANS. THIS IS NOW CONSIDERED A CHANGE
 OF OCCUPANCY AND WILL NEED TO COMPLY WITH THE 2017
 EXISTING BUILDING CODE SECTION
 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. WHERE THE
 OCCUPANCY CLASSIFICATION OR GROUP OF A PORTION OF AN
 EXISTING BUILDING IS CHANGED, SECTION 1012 SHALL APPLY.
  
 THE PLANS ARE NOT DISCLOSING THE MINIMUM INFORMATION
 FOR COMMERCIAL BUILDING PLAN REVIEW FOR BUILDINGS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLES 504.3, TABLE 504.4 & TABLE 506.2).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 FIRE SPRINKLERED OR NOT?
 IS FIRE SPRINKLERS REQUIRED?
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES/ WALLS AND CEILING (FLAME
 SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION MISSING RESTROOMS.
 SPECIAL SYSTEMS: (VERTICAL ACCESSIBILITY)
 ELEVATORS
 ESCALATORS
 LIFTS
  
 5) THE SUBMITTED PLAN WAS CREATED BY AN INTERIOR
 DECORATOR MARGARET B KAYWELL ID 0005475THE SCOPE OF THE
 PROJECT FAR EXCEEDS THE LIMITATIONS OF THIS LICENSE.
  
 5A) MISSING REQUIRED STATEMENT ON THE PLANS: 481.2131.
 A REGISTERED INTERIOR DESIGNER SHALL CONTAIN A
 STATEMENT THAT THE DOCUMENT IS NOT AN ARCHITECTURAL OR
 ENGINEERING STUDY, DRAWING, SPECIFICATION, OR DESIGN
 AND IS NOT TO BE USED FOR CONSTRUCTION OF ANY
 LOAD-BEARING COLUMNS, LOAD-BEARING FRAMING OR WALLS OF
 STRUCTURES, OR ISSUANCE OF ANY BUILDING PERMIT, EXCEPT
 AS OTHERWISE PROVIDED BY LAW.
  
 5B) FLORIDA STATUTE 481.2131(1). UNDER THE DEFINITIONS
 481.203 FOR INTERIOR DESIGN(8) ?INTERIOR DESIGN?
 SPECIFICALLY EXCLUDES THE DESIGN OF OR THE
 RESPONSIBILITY FOR ARCHITECTURAL AND ENGINEERING WORK,
 EXCEPT FOR SPECIFICATION OF FIXTURES AND THEIR LOCATION
 WITHIN INTERIOR SPACES. AS USED IN THIS SUBSECTION,
 ?ARCHITECTURAL AND ENGINEERING INTERIOR CONSTRUCTION
 RELATING TO THE BUILDING SYSTEMS? INCLUDES, BUT IS NOT
 LIMITED TO, CONSTRUCTION OF STRUCTURAL, MECHANICAL,
 PLUMBING, HEATING, AIR-CONDITIONING, VENTILATING,
 ELECTRICAL, OR VERTICAL TRANSPORTATION SYSTEMS, OR
 CONSTRUCTION WHICH MATERIALLY AFFECTS LIFESAFETY
 SYSTEMS PERTAINING TO FIRESAFETY PROTECTION SUCH AS
 FIRE-RATED SEPARATIONS BETWEEN INTERIOR SPACES,
 FIRE-RATED VERTICAL SHAFTS IN MULTISTORY STRUCTURES,
 FIRE-RATED PROTECTION OF STRUCTURAL ELEMENTS, SMOKE
 EVACUATION AND COMPARTMENTALIZATION, EMERGENCY INGRESS
 OR EGRESS SYSTEMS, AND EMERGENCY ALARM SYSTEMS.
 UNDER COMMENT # 4 THESE ARE THE AREAS NOT SHOWN ON THE
 PLAN, AND UNDER THE INTERIOR DESIGN LICENSE NOT IN THE
 SCOPE OF THEIR LICENSURE.
  
 6) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THIS TENANT
 SPACE SHOWING BOTH A MEANS OF EGRESS AS WELL AS THE
 ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY. PLEASE
 INCLUDE THE ADJACENT TENANT SPACE WHERE YOU HAVE TO GO
 THROUGH THE ADJACENT TENANT SPACE TO AN EXIT. PROVIDE
 THE TYPE OF OCCUPANCIES ADJACENT TO THE MERCANTILE
 OCCUPANCY. PLEASE ALSO INCLUDE COMMON PATH OF TRAVEL
 AND EXIT ACCESS TRAVEL TO THE EXIT DISCHARGE.
 2017 FBC-B TABLE 1006.2.1. PLEASE BE AWARE THAT FOR AN
 ACCESSIBLE MEANS OF EGRESS YOU ARE AT 79 FEET FROM THE
 FURTHEST POINT IN THE TENANT SPACE TO THE DOUBLE ENTRY
 DOORS. YOU STILL HAVE TO GO THROUGH A SECOND TENANT
 SPACE BEFORE YOU GET TO AN EXIT DISCHARGE.
 TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE.
  
 7)2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 (2).EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
  
 8) PLEASE NOTE WITH THE CITY BUILDING INSPECTORS BEING
 AT THE SITE AT PICTURES WERE TAKEN OF A CANVAS TENT
 LIKE CEILING ASSEMBLY AND CANVAS ON THE TENANT WALLS
 PLEASE PROVIDE COMPLIANCE WITH TEXTILE WALL AND CEILING
 COVERINGS.
  
 8A) 2017 FBC-B 803.5 TEXTILE WALL COVERINGS. WHERE USED
 AS INTERIOR WALL FINISH MATERIALS, TEXTILE WALL
 COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR
 NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND
 CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED
 IN THE MANNER INTENDED FOR USE, USING THE PRODUCT
 MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR
 803.1.4.
  
 8B) 2017 FBC-B 803.6 TEXTILE CEILING COVERINGS. WHERE
 USED AS INTERIOR CEILING FINISH MATERIALS, TEXTILE
 CEILING COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR
 NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND
 CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED
 IN THE MANNER INTENDED FOR USE, USING THE PRODUCT
 MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 803.1.2 OR 803.1.4.
  
 8C) SHOW COMPLIANCE WITH FBC-B 803.11 INTERIOR FINISH
 REQUIREMENTS BASED ON GROUP.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE
 THERE MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW
 PLANS AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-13 Cont ID  
Sent By jpearson Date 2018-06-13 Time 07:57 Rev Time 0.00
Received By jpearson Date 2018-06-13 Time 07:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 10:24 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 10:24 Sent To  
Notes
2018-05-20 10:24:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. VALUE STATED ON PERMIT APPLICAITON APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 (NOT PROVIDED.)
  
 NEW COMMENTS:
  
 4. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By jpearson Date 2018-03-01 Time 06:56 Rev Time 0.00
Received By jpearson Date 2018-03-01 Time 06:15 Sent To  
Notes
2018-03-01 06:56:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
 2. A FULL REVIEW IS NOT POSSIBLE AT THIS TIME DUE TO A
 SUBSTANTIAL LACK OF INFORMATION. FBC 107.2.1
 3. VALUE STATED ON PERMIT APPLICAITON APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-07 Cont ID  
Sent By pleduc Date 2018-06-07 Time   Rev Time 0.00
Received By pleduc Date 2018-06-06 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-18 Cont ID  
Sent By pleduc Date 2018-05-18 Time   Rev Time 0.00
Received By pleduc Date 2018-05-16 Time 17:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-02-27 Cont ID  
Sent By pleduc Date 2018-02-27 Time   Rev Time 0.00
Received By pleduc Date 2018-02-26 Time 12:31 Sent To  
Notes
2018-02-27 10:52:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 1 OF 4 - IS THIS AN OCCUPANCY CLASSIFICATION
 CHANGE?
  
 PLEASE PROVIDE THE EXISTING OCCUPANCY CLASSIFICATION
 AND PROPOSED ONE.
  
  
  
  
 2) SHEET 1 OF 4 - THERE IS NO INDICATION OF COMPLIANCE
 OR REVIEW OF COMLAINCE WITH ANY FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMNTS OF THE
 FLORIDA FIRE PREVENTION CODE, 2015 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLAINACE AND
 REVIEW.
  
  
  
  
 3) SHEET 1 OF 4 - THERE APPEARS TO BE ADJACENT
 OCCUPANCY WALL SEPARATION.
  
 PLEASE PROVIDE THE ADJACENT OCCUPANCIES AND THE
 REQUIRED FIRE RATING SEPARATION PER THE FFPC.
  
  
  
  
 4) SHEET 1 OF 4 - THERE IS NO INDICATION OF A DOOR
 SCHEDULE.
  
 PLEASE PROVIDE A DOOR SCHEDULE INCLUDING LOCKS AND
 HARDWARE AND ENSURE IT MEETS THE REQUIREMENT OF THE
 FFPC INCLUDING MEANS OF EGRESS.
  
  
  
  
  
 5) THERE IS NO SHEET 2 OF 4.
  
 PLEASE REVIEW AND PROVIDE OR ACCOUNT FOR.
  
  
  
  
 5) SHEET 3 OF 4 - THERE IS NO INDICATION OF EXIT
 SIGNAGE.
  
 NFPA 101 CHAPTER 36, NEW MERCANTILE OCCUPANCIES
 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 36.2.10 MARKING OF MEANS OF EGRESS. WHERE AN EXIT IS
 NOT
 IMMEDIATELY APPARENT FROM ALL PORTIONS OF THE SALES
 AREA, MEANS OF
 EGRESS SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION
 7.10.
  
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE
 SHALL BE
 PROVIDED TO MEET ALL OF THE FOLLOWING CRITERIA, UNLESS
 OTHERWISE
 PROVIDED IN 7.10.1.4:
 (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR
 REQUIRING AN
 EXIT SIGN.
 (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT.
 (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1,
 AMERICAN
 NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS
 AND
 FACILITIES.
  
  
 PLEASE PROVIDE PER FFFC, NFPA 101, CHAPTER 36 & 7 MEANS
 OF EGRESS.
  
  
  
  
 6) THERE ARE NO INCIATIONS OF ANY EXISTING OR PROPOSED
 FIRE SPRINKLER OR FIRE ALARM SYSTEMS.
  
 PLEASE REVIEW AND PROVIDE AND APPLICABLE NOTE ON SHEET
 1 OF 4.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-14 Cont ID  
Sent By shill Date 2018-06-14 Time 17:57 Rev Time 0.00
Received By shill Date 2018-06-01 Time 14:52 Sent To  
Notes
2018-06-04 14:52:56B27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-23 Cont ID  
Sent By tklarge Date 2018-05-23 Time 10:31 Rev Time 0.00
Received By tklarge Date 2018-05-10 Time 10:47 Sent To  
Notes
2018-05-14 10:48:03B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-03 Cont ID  
Sent By lcrespo Date 2018-03-03 Time 13:31 Rev Time 0.00
Received By lcrespo Date 2018-02-22 Time 10:29 Sent To  
Notes
2018-02-23 10:29:29B27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 12:47 Rev Time 0.00
Received By shill Date 2018-05-22 Time 12:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By jwitmer Date 2018-02-28 Time 10:54 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 16:11 Sent To  
Notes
2018-02-28 10:54:03BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 14:12 Rev Time 0.00
Received By ccole Date 2018-05-15 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By ccole Date 2018-02-28 Time 16:32 Rev Time 0.00
Received By ccole Date 2018-02-28 Time 16:32 Sent To  
Notes
2018-02-28 16:44:141ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18020938
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW.
 PLEASE NOTE THAT THE APPROVED PLANS UNDER PERMIT
 #16090638 SHOWED THIS SPACE TO BE A BUSINESS OCCUPANCY.
 PLEASE PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 NEW MERCANTILE OCCUPANCY, AND A DUCT LAYOUT PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By tklarge Date 2018-05-23 Time 10:31 Rev Time 0.00
Received By tklarge Date 2018-05-23 Time 10:31 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-03 Cont ID  
Sent By lcrespo Date 2018-03-03 Time 13:30 Rev Time 0.00
Received By lcrespo Date 2018-03-03 Time 13:30 Sent To  
Notes
2018-03-03 13:31:38DENIED
  
 1. ALL PLUMBING MUST COMPLY WITH FLORIDA BUILDING CODE
 2017 6TH EDITION
  
 2. SIGNATURE OF AN ARCHITECT ENGINEER IS REQUIRED (OR
 SEAL, OR TITLE BLOCK, OR ALL THREE) ARE NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
  
 3. PAGE 2 OF 3 IS MISSING AND MAY BE NEEDED FOR
 INFORMATION PROVIDED WPB AMENDMENTS TO THE FBC 107.1
 GENERAL PLANS AND APPLICATION.
  
 4. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS INTERIOR
 BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. WHAT LEVEL OF ALTERATION IS IT 2017 FBC BUILDING
 CODE.
  
 6. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO
 2017 FBC P TABLE 403.1
  
 7. PLEASE IDENTIFY ALL USE OF ROOMS ON PLANS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. WHAT IS THE PURPOSE OF THE SINK, IS THE SINK NEW OR
 EXISTING AND TEMPERED WATER FOR PUBLIC HAND WASHING
 FACILITIES WILL BE REQUIRED 2017 FBC P 607.1.
  
 9. HOT WATER AND COLD NOT SHOW AND ITS SOURCE, SIZING,
 DISTRIBUTION, WATER HAMMER, WITH IN ACCORDANCE 2017 FBC
 P SEC. 604, PLEASE PROVIDE A LAYOUT AND RISER FBC WPB
 AMENDMENTS TO THE 107.5.1.3 (13) PLUMBING RISER DIAGRAM
 REQUIRED.
  
 10. A GREASE TRAP MAY BE REQUIRED ALONG WITH SIZING, A
 SEPARATE PERMIT AND APPLICATION WILL BE NEED IF SO 2017
 FBC P 1003.1.
  
 11. THERE IS NO CLEAN OUT AT THE 4? CONNECTION OF THE
 BUILDING 2017 FBC P 708.1.3 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION.
  
 END OF COMMENTS.
  
 NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS
 MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  