Plan Review Stops For Permit 18020891 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-04-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-25 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-25 |
Time |
13:20 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-03-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-26 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-26 |
Time |
07:02 |
Sent To |
I |
|
Notes |
2018-03-26 07:12:30 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | (PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED) | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE FLORIDA LICENSED ENGINEER WHO IS | | RESPOSIBLE FOR THE DESIGN OF THE POOL. FBC 471 AND FAC | | 61G15 | | | | 2) SUBMIT TWO SETS OF AN OVERALL SITE PLAN THAT CLEARLY | | SHOWS THE LOCATION OF THE PROPOSED POOL. FBC 107.2.1 | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-03-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-07 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-07 |
Time |
07:45 |
Sent To |
|
|
Notes |
2018-03-07 08:39:39 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE FLORIDA LICENSED ENGINEER WHO IS | | RESPOSIBLE FOR THE DESIGN OF THE POOL. FBC 471 AND FAC | | 61G15 | | | | 2) SUBMIT TWO SETS OF AN OVERALL SITE PLAN THAT CLEARLY | | SHOWS THE LOCATION OF THE PROPOSED POOL. FBC 107.2.1 | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-04-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-04-23 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-04-23 |
Time |
14:08 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-03-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-03-01 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-03-01 |
Time |
17:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2018-03-12 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-03-12 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-03-12 |
Time |
15:17 |
Sent To |
|
|
Notes |
2018-03-12 15:18:40 | A SEPARATE PERMIT SHALL BE REQUIRED FOR GAS AS A | | SEPARETE REVIEW. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-04-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-25 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-11 |
Time |
12:22 |
Sent To |
|
|
Notes |
2018-04-12 12:22:39 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-03-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-03-26 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-20 |
Time |
10:30 |
Sent To |
|
|
Notes |
2018-03-21 10:30:42 | RESUB ROUTED TO LCRESPO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-03-12 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-03-12 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-02-21 |
Time |
13:01 |
Sent To |
|
|
Notes |
2018-02-22 13:01:44 | ROUTED TO ZONING |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2018-04-18 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-04-18 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-04-18 |
Time |
11:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-03-26 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-03-21 |
Time |
17:18 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-03-21 |
Time |
17:18 |
Sent To |
|
|
Notes |
2018-03-21 17:19:45 | REVIEW COMMENTS | | | | 1) THE PLANS ARE REQUIRED TO BE SIGNED, SEALED AND | | DATED BY THE FLORIDA LICENSED ENGINEER WHO IS | | RESPOSIBLE FOR THE DESIGN OF THE POOL. FBC 471 AND FAC | | 61G15 | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | [email protected] | | 561-805-6720 | | | | | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-03-12 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-03-08 |
Time |
17:54 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-03-08 |
Time |
17:53 |
Sent To |
|
|
Notes |
2018-03-12 15:15:41 | 3/12/2018 **1ST REVIEW DENIED ** | | | | 1. SIGNATURE OF AN ARCHITECT-ENGINEER IS REQUIRED, NOT | | IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE | | 61G15-23.001, FLORIDA STATUTE 471. | | 2. WHAT IS THE TURNOVER TIME OF THE POOL VOLUME PER DAY | | FBC B 454.1.6.2 | | 3. PLEASE PROVIDE THE MANUFACTURES SPECIFICATION FOR | | THE MAIN DRAIN GRATE AND SPA DRAIN GATE TO VERIFY | | COMPLIANCE WITH ASME/ANSI A112.19.8 COMPLIANT | | COVER/GRATE | | 4. THE MINIMUM GPM OF 73 GPM SHOWN ON SHEET 1 FOR THE | | POOL IS VALID FOR A BATHING LOAD OF 15 PERSONS. YOU | | LIST THE BATHING LOAD AS 20 PERSONS WHICH REQUIRES A | | MINIMUM FLOW OF 1000 GPM PER FBC B SEC. 454.1.1.1 | | SIZING, PLEASE CLARIFY THIS. | | 5. PLEASE PROVIDE MANUFACTURES SPECIFICATION ON PUMP | | AND HEATER FBC B SEC. 454.1.6.5.14 HEATERS. | | 6. PLEASE PROVIDE A COMPLETE PIPING DIAGRAM WPB | | AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL | | PLUMBING. | | 7. IF THE PUMP IS LOCATED ABOVE THE WATER LEVEL OF THE | | POOL, THE PUMP SHALL BE SELF-PRIMING FBC 454.1.6.5.4. | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | A SEPARATE PERMIT AND REVIEW SHALL BE REQUIRED FOR GAS. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR /PLUMBING PLAN REVIEW | | [email protected] | | 561-805-6720 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-06-18 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2018-06-18 |
Time |
11:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-04-13 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2018-04-13 |
Time |
13:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-02-28 |
|
|
Cont ID |
|
Sent By |
PG |
Date |
2018-02-28 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2018-02-28 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|