Plan Review Details - Permit 18020832
Plan Review Stops For Permit 18020832
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-27 Cont ID  
Sent By cthroop Date 2018-04-27 Time 09:54 Rev Time 0.00
Received By cthroop Date 2018-04-27 Time 08:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-16 Cont ID  
Sent By cthroop Date 2018-04-16 Time 15:27 Rev Time 0.00
Received By cthroop Date 2018-04-13 Time 16:39 Sent To  
Notes
2018-04-16 16:48:15BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN PAGE A-1 WALL LEGEND D STATES DOOR TO BE
 REMOVED AT MEZZANINE. NOTE AT DOOR STATES TO USE WALL
 TYPE A FOR DOOR INFILL. THERE IS ALSO A SETION OF WALL
 TO BE INFILLED WITH WALL TYPE A ADJACENT TO DOOR D.
 WALL SECTION A TERMINATES AT SECOND FLOOR DECK, SEE
 DETAIL 1, A-1. PROVIDE DETAIL FOR WALL THAT TERMINATES
 AT ROOF DECK. THESE WALLS SHALL BE 1 HOUR RATED.
  
 2. COVER PAGE DETAIL 1, CS-1 SHOWS CEILING INSULATION
 R-38 HELD WITH STRAPPING. PLAN PAGE A-1 SHOWS ICYNENE
 SPRAY FOAM TO ENTIRE DECK. PLEASE CLARIFY. IF ICYNENE
 IS USED, STATE R VALUE AND PROVIDE ICC-ES REPORT. ALSO
 IDENTIFY TYPE OF THERMAL BARRIER TO BE USED FOR THE
 ICYNENE PRODUCT.
  
 3. PROVIDE CURRENT REFERENCE STANDARD FOR THERMAX
 INSULATION TO BE USED AS WALL INSULATION. MIAMI DADE
 NOA 02-0703.03 REFERENCED IN THE TECHNICAL DATA
 PROVIDED FOR INSULATED WALLS HAS EXPIRED.
  
 4. PLATFORM LIFT -
 4A. PROVIDE LEGIBLE PLAN. PRINT TOO SMALL TO READ.
 4B. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS
 WITH FASTENER SCHEDULE TO MEET EXISTING SITE
 CONDITIONS,
 4C. PROVIDE ELEVATION DRAWING OF PLATFORM LIFT SITE
 CONDITIONS. SHOW ELEVATION OF FINISHED FLOOR, TOP OF
 STAIRS, TOP OF CONCRETE SLAB AND PAVEMENT.
  
 5. MECHANICAL DESIGNER TO DEMONSTRATE THE NEW
 MECHANICAL CURB WILL COMPLY WITH THE DESIGN PARAMETERS
 SPECIFIED ON PLAN PAGE S-1 BY THE STRUCTURAL ENGINEER
 OF RECORD.
 5A. PER NOTE 9, PLAN PAGE M-2, DESIGNER TO SPECIFY TYPE
 AND SIZE OF FASTENERS AT MECHANICAL CURB TO ROOF
 ATTACHMENT.
  
 6. OVERHEAD DOOR PARAMENTERS TO BE PLACED ON DOOR
 SCHEDULE. DESIGNER TO REVIEW AND APPROVE PRODUCT
 APPROVALS.
  
 7. ADA PARKING DETAIL PROVIDED FOR YOUR REVIEW AND USE.
  
 NOTE: WELDER CERTIFICATIONS TO BE ON-SITE AT TIME OF
 INSPECTION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By jwitmer Date 2018-03-13 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2018-03-13 Time 08:59 Sent To  
Notes
2018-03-13 15:09:022017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020832
 ADD: 1306 ALLENDALE RD.
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC.
 TEL: 561-625-4545
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 13/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET:
 1A) LIST THIS BUILDING TYPE AS TYPE IA-UNPROTECTED.
 PLEASE REVIEW THE 2017 FBC-B TABLE 601 ALL OF THE
 STRUCTURAL ELEMENTS HAVE A RATING WITH THE EXCEPTION OF
 NONBEARING INTERIOR WALLS. PLEASE CORRECT THE HOURLY
 FIRE RATINGS.
  
 1B) THE PLANS INDICATE THE OCCUPANCY AS A S-2 AND FBC-B
 TABLE 1004.1.2 INDICATES FOR WAREHOUSES THE ALLOWABLE
 FLOOR AREA PER OCCUPANT IS 500 SQ. FT. THE PLANS
 INDICATE THE SQUARE FOOTAGE 1ST FLOOR FOR THE STORAGE
 OCCUPANCY IS 6,555 SQ. FT. AND AN OCCUPANT LOAD OF 13.
 PLEASE NOTE THE ACTUAL OCCUPANT LOAD IS 13.11 OR 14
 OCCUPANTS, YOU ALWAYS ROUND UP, OCCUPANTS ONLY COME AS
 A WHOLE. SEE BOAF INTERPRETATION # 5479.
  
 1C) THERE IS A DISCREPANCY BETWEEN THE SQUARE FOOTAGE
 GIVEN BY THE DESIGNER OF RECORD AND THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE. THEY HAVE THE 1ST
 FLOOR STORAGE AT 8698 SQ. FT. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) THE GENERAL NOTES # 14 LIST THE 2014 FLORIDA
 EXISTING BUILDING CODE, PLEASE UPDATE TO THE 2017
 FLORIDA FAMILY OF CODES WAS ADOPTED STATEWIDE ON DEC.
 31/ 2017. PLEASE UPDATE PLANS.
  
 1E) THE PLANS INDICATE THIS IS A ONE STORY BUILDING,
 PLEASE UPDATE THE PLANS TO ALSO INCLUDE EITHER A
 MEZZANINE OR A 2ND FLOOR.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 1F) SHEET A-1 CONTRADICTING NOTES, THIS AREA NO WORK IN
 CONTRACT BUT THERE IS A NOTE F WHICH INDICATES THE
 REMOVAL OF THE STEEL MEZZANINE. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) PLEASE NOTE THE SUBMITTED PLAN INDICATES $452,287.00
 DOLLARS IN VALUE. PLEASE NOTE ONLY ONE PERMIT
 APPLICATION WAS SUBMITTED FOR INTERIOR RENOVATION OF
 EXISTING WAREHOUSE/ OFFICE FACILITY, INCLUDING MAJOR
 ADA UPGRADES AND MINOR SITE CHANGES TO ACCOMMODATE A
 NEW GENERATOR. SEPARATE PERMITS ARE REQUIRED FOR,
 GENERATORS, RACK STORAGE OVER THE HEIGHT OF 5 FOOT 9
 INCHES. PLANS ARE NOT CLEAR IF THE ACCESSIBLE PARKING
 SPACE IS NEW OR EXISTING. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 PLEASE NOTE SINCE THERE WILL BE OTHER PERMITS REQUIRED
 THAT MAY HAVE THEIR VALUE INCLUDED UNDER THIS PERMIT,
 PLEASE BACK OUT THAT VALUE SO THE BUILDING DEPARTMENT
 DOES NOT DOUBLE DIP.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
  
  
 3A) SHEET A-1 SHOWS A NEW INTERIOR METAL STUD WALL,
 WALL TAG A. THE DETAIL INDICATES THE WALL IS TO BE
 BUILT TO SPECIFICATION GA WP-1200. PLEASE PROVIDE THIS
 WALL TYPE ON THE PLANS, OUR FIELD INSPECTORS WILL NOT
 HAVE A GYPSUM ASSOCIATION BOOK TO SEE THE LIMITATIONS.
 PLEASE PROVIDE AT WHAT HORIZONTAL LOAD THE WALL IS TO
 BE DESIGNED TOO? ALSO THE PLANS DO NOT INDICATE WHAT
 THE HEIGHTS OF THE STUDS HAVE TO BE TO REACH THE ROOF
 DECK LEVEL; THERE IS A MEZZANINE LEVEL JUST ADJACENT TO
 THE NEW PROPOSED WALL.
 2017 FBC-B 1607.14 INTERIOR WALLS AND PARTITIONS.
  
 3B) PLEASE NOTE THIS SAME WALL TYPE HAS A NOTE AT THE
 BOTTOM OF THE WALL TAG A THAT STATES CONTRACTOR TO
 SUBMIT TEST NUMBER AND SPECIFICATION OF SAME. GA
 WP-1200 OR EQUAL.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3: W.P.B. ADMINISTRATIVE
 CODE/2010 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 3C) A NOTE ON WALL TYPE A INDICATES THE USE OF 5/8 INCH
 TYPE X DRYWALL, THERE IS ANOTHER NOT INDICATING THE
 ATTACHMENT OF 1 ? X 2 DIAMOND PATTERN9 GAUGE EXPANDED
 METAL TO THE EXTERIOR OF THE ROOM, IS THIS A SECURITY
 SCREEN AND TO THE EXTERIOR SIDE OF WHICH ROOM?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
  
 4A) SHEET A-1 SHOWS DETAILS OF A LIFT SPECIFICATION BUT
 THE PLANS DO NOT SHOW TO WHICH ASME STANDARD IT IS
 CERTIFIED UNDER , ASME A18.1 ACCESSIBILITY CODE 410.1
 PLATFORM LIFTS OR ASME A17.1 408.1 LULA LIFTS, LIMITED
 USE/ LIMITED APPLICATION ELEVATOR.
  
 4B) WITH THE PLACEMENT / LOCATION OF THE LIFT IT WOULD
 APPEAR THE LIFT IS NOT TO BE USED TO GAIN ACCESS TO THE
 OFFICE BUT TO THE WAREHOUSE?
  
 5) 107.2.1.3: W.P.B. ADMINISTRATIVE CODE/2010 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION" PLEASE SHOW
 HOW THE INSULATION IS TO BE INSTALLED TO STAY IN PLACE?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6A) SHEET A-1 SHOWS THE WALL TAG E ON ALL EXTERIOR
 WALLS. ON THE INTERIOR SIDE OF ALL EXTERIOR WALLS
 INSTALL 1 ? INCH THERMAX RIGID INSULATION. PLEASE
 PROVIDE INSTALLATION INSTRUCTIONS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 6B) SHEET A-1 SHOWS THE WALL TAG E ON ALL EXTERIOR
 WALLS. ON THE INTERIOR SIDE OF ALL EXTERIOR WALLS
 INSTALL 1 ? INCH THERMAX RIGID INSULATION. PLEASE SHOW
 HOW COMPLIANCE WITH THE 2017 FBC-B 2603.4 THERMAL
 BARRIER OR EXCEPTION WILL BE MET.
 2017 FBC-B 2603.4 THERMAL BARRIER.
  
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.9,
 FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF A
 BUILDING BY AN APPROVED THERMAL BARRIER OF 1/2-INCH
 (12.7 MM) GYPSUM WALLBOARD OR A MATERIAL THAT IS TESTED
 IN ACCORDANCE WITH AND MEETS THE ACCEPTANCE CRITERIA OF
 BOTH THE TEMPERATURE TRANSMISSION FIRE TEST AND THE
 INTEGRITY FIRE TEST OF NFPA 275. COMBUSTIBLE CONCEALED
 SPACES SHALL COMPLY WITH SECTION 718.
  
 FBC-B 2603.4.1 THERMAL BARRIER NOT REQUIRED. THE
 THERMAL BARRIER SPECIFIED IN SECTION 2603.4 IS NOT
 REQUIRED UNDER THE CONDITIONS SET FORTH IN SECTIONS
 2603.4.1.1 THROUGH 2603.4.1.14.
  
 7) SHEET M-2 SHOWS ROOF TOP CURBS AND ROOFTOP HVAC
 UNITS, FOR REFERENCE ONLY. THE NOTE STATES THAT FOR
 ATTACHMENT PURPOSES TO BE VERIFIED BY A STRUCTURAL
 ENGINEER. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 8) PLEASE NOTE FOR A DESIGN PROFESSIONAL TO DESIGN THE
 ANCHORAGE FOR ROOF TOP EQUIPMENT THE WIND DESIGN
 CRITERIA MUST ALSO BE KNOWN.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 8.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 8.2. RISK CATEGORY.
  
 8.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 8.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 8.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 9) WELDED OR BOLTED CONNECTIONS THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-13 Cont ID  
Sent By jleahy Date 2018-04-13 Time 15:47 Rev Time 0.00
Received By jleahy Date 2018-04-13 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-27 Cont ID  
Sent By jleahy Date 2018-03-27 Time 07:46 Rev Time 0.00
Received By jleahy Date 2018-03-27 Time 07:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-04-30 Cont ID  
Sent By pleduc Date 2018-04-30 Time   Rev Time 0.00
Received By pleduc Date 2018-04-27 Time 15:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-10 Cont ID  
Sent By pleduc Date 2018-04-10 Time   Rev Time 0.00
Received By pleduc Date 2018-04-09 Time 16:15 Sent To  
Notes
2018-04-10 12:07:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A GAS GENERATOR AND GAS REGULATOR IS INDICATED.
 THESE ARE NO APPROVED UNDER THIS PERMIT.
  
 THESE INSTALLATIONS SHALL BE UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE ENSURE ALL MANUFACTURES SPEC ARE PROVIDED AND A
 SITE PLAN SHOWING ALL OPENINGS WITH DIMENSIONS FROM THE
 EXHAUST.
  
 IF THE GENERATOR WILL BE POWERING ANY LIFE SAFETY
 SYSTEM, ENSURE IT MEETS THE REQUIREMENTS OF NFPA 110.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-26 Cont ID  
Sent By pleduc Date 2018-02-26 Time   Rev Time 0.00
Received By pleduc Date 2018-02-26 Time 11:20 Sent To  
Notes
2018-02-26 11:25:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A GAS GENERATOR AND GAS REGULATOR IS INDICATED.
 THESE ARE NO APPROVED UNDER THIS PERMIT.
  
 THESE INSTALLATIONS SHALL BE UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE ENSURE ALL MANUFACTURES SPEC ARE PROVIDED AND A
 SITE PLAN SHOWING ALL OPENINGS WITH DIMENSIONS FROM THE
 EXHAUST.
  
 IF THE GENERATOR WILL BE POWERING ANY LIFE SAFETY
 SYSTEM, ENSURE IT MEETS THE REQUIREMENTS OF NFPA 110.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-04 Cont ID  
Sent By eschneid Date 2018-05-04 Time 10:48 Rev Time 0.00
Received By eschneid Date 2018-04-25 Time 15:28 Sent To  
Notes
2018-04-26 15:28:21C07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-04-17 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-04 Time 13:59 Sent To  
Notes
2018-04-05 13:59:09C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-27 Cont ID  
Sent By jleahy Date 2018-03-27 Time 07:46 Rev Time 0.00
Received By jleahy Date 2018-02-20 Time 15:52 Sent To  
Notes
2018-02-21 15:53:06C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-13 Cont ID  
Sent By jwitmer Date 2018-03-13 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2018-03-13 Time 15:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-01 Cont ID  
Sent By skennedy Date 2018-05-01 Time 11:11 Rev Time 0.00
Received By skennedy Date 2018-05-01 Time 11:11 Sent To Z
Notes
2018-05-01 11:11:48M & E TO COORDINATE RTU1 W/ S.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By ccole Date 2018-04-17 Time 12:20 Rev Time 0.00
Received By ccole Date 2018-04-17 Time 12:19 Sent To I
Notes
2018-04-17 12:25:422ND REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING CODE
 PERMIT #18020832
 4/17/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 & S-1: THE RTU-1 LOCATION AND IT'S
 POSITION ON THE ROOF AS SHOWN ON THE PLANS DO NOT
 MATCH. PLEASE NOTE THAT THAT IF THE UNIT IS LOCATED
 LESS THAN 10' FROM THE ROOF EDGE (AS SHOWN ON S-1), A
 42" HIGH PARAPET OR GUARD IS REQUIRED IN ACCRODANCE
 WITH SECTION 301.11.
  
 2) M-2 & S-1: THE CURB AND RTU INSTALLATION DETAILS-
 TYPES, SIZES, AND SPACINGS OF ANCHORS, STRAPS, AND
 FASTENERS AS SHOWN IN THE PLANS ARE IN CONFLICT. PLEASE
 CORRECT.
  
 3) REFER TO BUILDING REVIEW COMMENTS AND RESOLVE THE
 CONFLICT WITH THE WALL AND ROOF INSULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By ccole Date 2018-03-16 Time 15:59 Rev Time 0.00
Received By ccole Date 2018-03-16 Time 15:55 Sent To  
Notes
2018-03-16 16:11:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18020832
 3/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE INPUT DATA REPORT ATTACHED WITH THE FLORIDA
 ENERGYGAUGE COMPLIANCE REPORT LISTS R-VALUES FOR THE
 WALLS AND ROOF, AND DIRECTIONAL ORIENTATIONS FOR THE
 WALLS THAT DO NOT MATCH WITH THE ARCHITECTURAL PLANS.
 THE ARCHITECT OF RECORD MUST REVIEW THE ENERGY REPORT,
 MAKE CORRECTIONS, AND THEN PROVIDE HIS CERTIFICATION
 SIGNATURE ON PAGE 4 OF THE REPORT.
  
 2) M-2: THE RTU INSTALLATION DETAILS ARE INCOMPLETE: A)
 PROVIDE THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE
 WITH SECTION1609 FBC-17 BUILDING. B) PROVIDE ENGINEERED
 STRUCTURAL DRAWINGS FOR CREATING THE RTU ROOF OPENINGS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-22 Cont ID  
Sent By gjohnson Date 2018-03-22 Time 16:17 Rev Time 0.00
Received By gjohnson Date 2018-03-22 Time 12:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-04 Cont ID  
Sent By eschneid Date 2018-05-04 Time 10:47 Rev Time 0.50
Received By eschneid Date 2018-05-04 Time 10:47 Sent To PC
Notes
2018-05-04 10:48:50GENERATOR AND ENCLOSURE REQUIRE SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-12 Cont ID  
Sent By eschneid Date 2018-04-12 Time 10:40 Rev Time 0.25
Received By eschneid Date 2018-04-12 Time 10:40 Sent To  
Notes
2018-04-12 10:42:34FAILED
  
 1) REPEAT COMMENT: THE VALUE OF THE CONSTRUCTION
 ($452,287) EXCEEDS 50% OF THE STRUCTURE'S VALUE
 ($474,990) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S
 OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(B) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. THE SITE DOES NOT CONFORM TO ARTICLE XIV, SO
 PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A SEPARATE
 LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL BE
 SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO
 CONFORMITY.
  
 A. NOTE: GOOGLE STREET VIEW SHOWS A PALM TREE IN THE
 AREA OF THE PROPOSED ADA LIFT. NO ACCOUNTING HAS BEEN
 SHOW FOR ITS REMOVAL.
  
 2) REPEAT COMMENT: THE REQUIRED LANDSCAPE UPGRADES WILL
 AFFECT THE LAYOUT SHOWN ON THE SITE PLAN. PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT, A SEPARATE PARKING LOT
 STRIPING PERMIT IS REQUIRED.
  
 3) A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR.
 PLEASE NOTE THAT THE GENERATOR IS REQUIRED TO BE
 SCREENED IN ACCORDANCE WITH SECTION 94-315 OF THE ZLDR.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-03-09 Cont ID  
Sent By ES Date 2018-03-09 Time 11:13 Rev Time 0.75
Received By eschneid Date 2018-03-08 Time 16:48 Sent To  
Notes
2018-03-09 11:19:41FAILED
  
 1) THE VALUE OF THE CONSTRUCTION ($452,287) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($474,990) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, SO PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 A. NOTE: GOOGLE STREET VIEW SHOWS A PALM TREE IN THE
 AREA OF THE PROPOSED ADA LIFT. NO ACCOUNTING HAS BEEN
 SHOW FOR ITS REMOVAL.
  
 2) THE REQUIRED LANDSCAPE UPGRADES WILL AFFECT THE
 LAYOUT SHOWN ON THE SITE PLAN. PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT, A SEPARATE PARKING LOT
 STRIPING PERMIT IS REQUIRED.
  
 3) A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR.
 PLEASE NOTE THAT THE GENERATOR IS REQUIRED TO BE
 SCREENED IN ACCORDANCE WITH SECTION 94-315 OF THE ZLDR.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]