Plan Review Details - Permit 18020716
Plan Review Stops For Permit 18020716
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By hhall Date 2018-03-27 Time 09:54 Rev Time 0.00
Received By hhall Date 2018-03-27 Time 09:54 Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-02-27 Cont ID  
Sent By squinone Date 2018-02-27 Time   Rev Time 0.00
Received By squinone Date 2018-02-27 Time   Sent To M
Notes
2018-02-27 14:38:491. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-
 PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE
 HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL.
 SHOW HYDRANT FLOW TEST DATA RESULT ON THE PLANS.
  
 3. SUBMIT ESTIMATES FOR FIRE DEMAND, BOTH AVERAGE AND
 PEAK FLOW WITH PEAKING FACTOR. SHOW PROJECTED DEMANDS
 ON THE UTILITY PLAN SHEET.
  
 4. AS-BUILT SHOWS A 30-INCH SANITARY SEWER, NOT A
 28-INCH STORM DRAINAGE. CONTACT ENGINEERING SERVICES
 DEPARTMENT FOR AS-BUILT INFORMATION.
  
 5. ONE FIRELINE CANNOT SERVICE THREE DIFFERENT
 PROPERTIES. PLEASE SUBMIT A PERMIT FOR EACH PROPERTY
 AND EACH PROPERTY HAS TO HAVE ITS OWN PRIVATE FIRELINE.
  
 6. PRIVATE FIRELINES CANNOT BE CONSTRUCTED WITHIN
 CITY'S ALLEYWAY.
  
 7. SHOW SURVEY DATUM USED IN THE PLANS. CITY USES NGVD
 1929, PLEASE PROVIDE CONVERSION FOR NAVD 1988.
  
 8. SHOW EXISTING WATER AND SEWER SERVICE CONNECTIONS
 INCLUDE MATERIAL AND SIZE.
  
 9. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE
 THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM
 BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-22 Cont ID  
Sent By pleduc Date 2018-02-22 Time   Rev Time 0.00
Received By pleduc Date 2018-02-20 Time 16:52 Sent To ENG
Notes
2018-02-21 16:38:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE FIRE LINE SHALL BE INSTALLED PER NFPA 24 BY A
 LICENSED STATE OF FLORIDA UNDERGROUND CONTRACTOR.
  
  
 2) DO NOT COVER OVER PRIOR TO PRESSURE TEST AND FIRE
 INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-27 Cont ID  
Sent By cpuell Date 2018-03-27 Time 12:42 Rev Time 0.00
Received By cpuell Date 2018-03-19 Time 12:56 Sent To  
Notes
2018-03-20 12:56:38RESUB ROUTED TO ENGINEERING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-02 Cont ID  
Sent By hmoser Date 2018-03-02 Time 13:33 Rev Time 0.00
Received By hmoser Date 2018-02-16 Time 13:28 Sent To  
Notes
2018-02-20 13:28:40ROUTED TO FIRE INBOX
 **TRAVELLING WITH 18020718**

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-03-02 Cont ID  
Sent By hmoser Date 2018-03-02 Time 13:32 Rev Time 0.00
Received By hmoser Date 2018-03-02 Time 13:27 Sent To I
Notes
***NONE***