2018-02-15 14:07:23 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. VALUE LISTED ON PERMIT APPEARS LOW. PROVIDE COPY OF |
| SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, TO |
| INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 |
| 2. RISER DIAGRAM IS CONFUSING. WILL THERE BE A SERVICE |
| AT EACH BUILDING ON THIS PROPERTY? HOW MANY METER CANS |
| AND DISCONNECTS WILL THERE BE FOR THE PROPERTY? PROVIDE |
| COMPLETE RISER DIAGRAM SHOWING THE EXISTING SERVICE AS |
| WELL AS THE NEW SERVICE DETAILS FOR ALL SERVICES AT |
| THIS ADDRESS, INCLUDING UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30 |
| 3. CONDUIT BETWEEN METER AND MAIN BREAKER PANEL SHOULD |
| NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| CORRECTION. NEC 250.6 |
| 4. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. A NOTE |
| WILL SUFFICE. NEC 210.12; FBC RE E3902.16 |
| 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| 7. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN |
| ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE |
| EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. |
| PROVIDE CORRECTION. NEC 250.56 |
| 8. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| CORRECTION. NEC 210.11(C)(3) |
| 9. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) |
| 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |