Plan Review Details - Permit 18020012
Plan Review Stops For Permit 18020012
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-11-27 Cont ID  
Sent By tklarge Date 2018-11-27 Time 05:43 Rev Time 0.00
Received By tklarge Date 2018-11-27 Time 05:08 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-03-20 Cont ID  
Sent By tklarge Date 2018-03-20 Time 12:34 Rev Time 0.00
Received By tklarge Date 2018-03-20 Time 11:00 Sent To I
Notes
2018-03-20 12:06:371) THE SUBMITTED GAS PLAN IS A COPY OF A SIGNED AND
 SEALED PLAN BY AN ENGINEER.PLANS BEARING AND ENGINEER'S
 TITLE BLOCK SHALL ALSO HAVE AN ORIGINAL SIGNATURE AND
 SEAL PER THE FL. ADMIN. CODE 61G15-23.001. SUBMIT TWO
 COPIES OF THE GAS PLAN BEARING THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER.
 2) SHOW THE LOCATION OF THE METAL LOUVERS THAT ARE
 BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS
 CANNOT BE LOCATED IN AN EXTERIOR WALL THAT IS FIRE
 RATED AS THE FIRE RATING OF THE WALL MUST BE
 MAINTAINED.
 3) THE LOUVERS ARE NOT PERMITTED IN AN EXTERIOR WALL
 WITH A FIRE SEPARATION DISTANCE, TYPE OF CONSTRUCTION,
 AND WHETHER OR NOT THE BUILDING IS SPRINKLERED AS
 LISTED IN TABLE 705.8 OF 2017 FBC-BUILDING.SUBMIT ALL
 REQUIRED INFORMATION. SUBMIT A SITE PLAN SHOWING THE
 DISTANCE OF ALL EXTERIOR WALLS TO ADJACENT PROPERTY
 LINES. WPB AMEND. TO FBC SEC.107.2.1.
 4) SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS.
 5) THIS PLAN SHALL BE TAKEN TO THE ENGINEER OF RECORD
 TO BE SIGNED AND SEALED AND SUBMITTED AS CORRECTIONS
 ALONG WITH ALL OTHER CORRECTIONS UNDER THE MASTER
 PERMIT NUMBER 18020521. THIS GAS PERMIT CANNOT BE
 ISSUED UNTIL THE MASTER PERMIT HAS BEEN APPROVED.
 6) COPIES OF EQUIPMENT SPECIFICATIONS HAVE BEEN
 SUBMITTED FOR TWO DIFFERENT PIECES OF EQUIPMENT BY TWO
 DIFFERENT MANUFACTURERS. THE PLANS SHOW A ROTATING RACK
 OVEN BUT SPECS HAVE ALSO BEEN PROVIDED FOR A DOUBLE
 RACK OVEN. WHICH ONE IS BEING INSTALLED? CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-07 Cont ID  
Sent By lcrespo Date 2018-02-07 Time 06:26 Rev Time 0.00
Received By lcrespo Date 2018-02-07 Time 06:26 Sent To  
Notes
2018-02-07 06:28:58DENIED
  
 1. ON GAS NOTES, THE SPECIFICATION FOR PLUMBING CODE
 COMPLIANCE SAY 2014 FBC FUEL GAS ON PAGE P-3 BUT SHOULD
 IT REFER TO 2017 FBC FUEL GAS. RISER SHOWS 1 1/2" FROM
 THE METER, GAS NOTES SHOW 1-/2", THIS IS A TYPO THAT
 REQUIRES CORRECTION. PLEASE MAKE A NOTE TO REFLECT
 THESE CORRECTIONS. FBC WPB AMENDMENTS 107.2.1.
 2. SHOW WHAT TYPE OF PROTECTIVE COATING AGAINST
 CORROSION ON PIPE AND FITTINGS. 2017 FBC FUEL GAS SEC
 403.8, 404.11.
 3. SHOW DRIPS LEG AND LOCATIONS ON RISER DIAGRAM,
 SEDIMENT TRAP AND SLOPED PIPING 2017 FBC FUEL GAS SEC.
 408.1, 404.2, 404.3 AND 404.4.
 4. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 5. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC. 402.2 AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. 2017 FUEL
 GAS SEC.305.1.
 6. EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC FUEL
 GAS SEC. 304.9.3
 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM ON THE NEW CODE 2017 FBC
 FUE GAS TABLE 402.4. (1). TABLES SUBMITTED ARE 402.4(1)
 BUT GAS NOTES REFER TO 402.4(2) PLEASE CLARIFY.
 9. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH
 THE EXTERIOR WILL BE PROTECTED. 2017 FBC FUEL GAS SEC.
 404.7.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-27 Cont ID  
Sent By tklarge Date 2018-11-27 Time 05:44 Rev Time 0.00
Received By tklarge Date 2018-11-08 Time 13:28 Sent To  
Notes
2018-11-09 13:28:18RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-20 Cont ID  
Sent By tklarge Date 2018-03-20 Time 12:34 Rev Time 0.00
Received By tklarge Date 2018-03-20 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-07 Cont ID  
Sent By lcrespo Date 2018-02-07 Time 06:26 Rev Time 0.00
Received By cpuell Date 2018-02-01 Time 10:38 Sent To  
Notes
2018-02-02 10:38:41PLUMB<5K