Plan Review Details - Permit 18020006
Plan Review Stops For Permit 18020006
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-08-15 Cont ID  
Sent By cthroop Date 2018-08-15 Time 16:08 Rev Time 0.00
Received By cthroop Date 2018-08-15 Time 15:21 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-07-03 Cont ID  
Sent By shill Date 2018-07-03 Time 17:40 Rev Time 0.00
Received By shill Date 2018-07-03 Time 17:40 Sent To  
Notes
2018-07-03 17:40:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC B 1609
  
 1. THE ENGINEER'S LETTER STATES THAT THE "COMPOSITE
 PANELS" HAVE NO PRODUCT APPROVAL.
  
 THE LETTER SHOULD BE SPECIFIC AS TO PRODUCT, AND THAT
 THE PRODUCT DOES HAVE AN NOA BUT FOR USE AS A WALL
 PANEL, NOT A ROOF PANEL. REVISE TO REFERENCE.
  
 2. THE LETTER STATES THAT THE PANELS ARE ADJUDGED
 "STRUCTURALLY EQUAL" TO METL-SPAN CFR PANELS. THE TWO
 PRODUCTS ARE DIFFERENT (FOAM DENSITY, STEEL GAGE);
 INCLUDE THE DIFFERENCES IN THE LETTER.
  
 3. THE LETTER STATES THAT THE PRODUCT WILL "SPAN 48"".
 IT IS NOT CLEAR WHERE THIS IS; THE ROOF PANEL NOA SPANS
 60", WALL SPAN DOES NOT APPEAR RELEVANT; CLARIFY OR
 REMOVE.
  
 4. THE LETTER SHOULD SPECIFICALLY STATE THAT THE WALL
 PANEL NOA IS ACCEPTABLE FOR USE AS A ROOF PANEL.
  
 5. THE PLANS APPEAR TO SHOW THE ROOF PANELS SECURED TO
 THE WALL PANELS WITH "TRIM" AND NO OTHER SUPPORT AT
 EACH END. SEE THE ROOF PANEL NOA, PAGE 3, HIGH EAVE
 DETAIL AND EVE DETAIL. THE INSTALLATION SHOULD BE
 CONSISTENT WITH THE NOA OR A DETAIL WITH SIMILAR
 SUPPORT PROVIDED.
  
 6. IT IS MY UNDERSTANDING THAT A ROOF COVERING WAS
 INSTALLED; PROVIDE ADDITIONAL INFORMATION - PRODUCT
 APPROVAL, METHOD OF INSTALLATION. REVISE PLAN TO
 INCLUDE THE ROOF COVERING.
  
 7. PROVIDE DESIGN PRESSURES FOR THE ROOF. SEE SHEET 1
 OF 3, ROOF PANEL NOA. REVISE PLAN TO PROPOSE PERLIN
 SUPPORT AS NEEDED FOR SPECIFIED DESIGN PRESSURES.
  
 8. SHEET 1, THE EXPANSION BOLT IS SHOWN GRAPHICALLY TOO
 CLOSE TO THE EDGE OF THE CONCRETE. REVISE TO SHOW
 DISTANCE OF EACH BOLT TO EDGE, AND DISTANCE BETWEEN
 BOLTS. PROVIDE THE PRODUCT APPROVAL FOR THE BOLTS SO
 REQUIRED SEPARATION AND EDGE DISTANCE CAN BE CONFIRMED.
 THE WAY THE DETAIL IS DRAWN, FAILURE OF THE CONCRETE AT
 THE TOP IS POSSIBLE.
  
 9. THE NOA FOR THE ROOF PANELS, HIGH EAVE DETAIL AND
 EAVE DETAIL, SHOW FASTENERS FROM "EAVE STRUCTURE BY
 OTHERS" TO THE WALL PANEL, BUT DOES NOT SPECIFY
 SPACING. REVISE PLAN TO INCLUDE.
  
 10. A MECHANICAL UNIT IS SHOWN ABOVE THE COOLER. HOW
 WILL THIS BE ACCESSED FOR SERVICE? FBC B TABLE 1607.1,
 IT APPEARS THAT THE ONLY ACCESS IS OVER THE TOP OF THE
 COOLER, BUT THE COOLER ROOF DOES NOT APPEAR TO BE
 DESIGNED FOR THE REQUIRED LOAD OF 300# PSF.
  
 11. FBC B TABLE 1607.1, REVISE PLAN TO CLARIFY THAT THE
 ROOF MEETS THE LIVE LOAD REQUIREMENT OF 20# PSF.
  
 12. AFTER PERMIT IS ISSUED AND INSTALLATION IS
 COMPLETE, AN ENGINEER'S INSPECTION AND LETTER/REPORT
 WILL BE REQUIRED DUE TO THE UNUSUAL NATURE OF THE
 CONSTRUCTION, FBC 110.3.9.
  
 13. FOR THE WALL PANELS, ON THE PRODUCT APPROVAL
 INDICATE
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-05 Cont ID  
Sent By cthroop Date 2018-05-05 Time 09:15 Rev Time 0.00
Received By cthroop Date 2018-05-05 Time 07:38 Sent To M
Notes
2018-05-05 09:52:59BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. JOB ADDRESS LISTED ON PLAN REVIEW REQUEST FORM IS
 538 NORTHWOOD RD. CORRECT ADDRESS FOR THIS PROJECTL IS
 3815 S DIXIE HWY. PLEASE CLARIFY.
 2. CONTRACTOR LISTED ON LATEST PLAN REVIEW REQUEST FORM
 IS EDRIK BANDEZ, GENERAL CONTRACTOR, CGC1522589.
 CONTRACTOR FOR MECHANICAL SUB-PERMIT IS EVID VALERO,
 CAC1817915. PLEASE CLARIFY.
 3. RESPONSE FROM METRO DESIGN GROUP IN RESPONSE TO PLAN
 REVIEW COMMENT DENYING THE USE OF KINGSPAN INSULATED
 PANELS TO BE USED FOR THE ROOF OF THE WALK-IN COOLER
 STATES "THE ROOF HAS BEEN INSTALLED AND INSPECTED UNDER
 THE BUILDING MASTER ROOFING PERMIT". NO RECORD CAN BE
 FOUND OF A PRODUCT APPROVAL FOR THESE COMPOSITE WALL
 PANELS BEING SUBMITTED AND/OR APPROVED FOR ANY PREVIOUS
 PERMIT. ALSO, THERE IS NO INSPECTION HISTORY THAT THESE
 INSULATED PANELS WRE INSPECTED AND APPROVED FOR THE
 APPLIED USE.
 PROVIDE SITE SPECIFIC ENGINEERING FOR THE KINGSPAN
 INSULATED PANELS TO BE USED AS A ROOF SYSTEM COMPONENT.
 DEMONSTRATE THAT THE PANELS, WHEN USED IN THIS
 APPLICATION, WILL MEET OR EXCEED THE ANTICIPATED WIND
 LOADS FOR THEIR LOCATION AND USE.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-19 Cont ID  
Sent By cthroop Date 2018-03-19 Time 11:32 Rev Time 0.00
Received By cthroop Date 2018-03-19 Time 10:59 Sent To  
Notes
2018-03-19 11:36:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMPOSITE WALL PANEL SYSTEM PER NOA 16-0706.08 IS
 NOT DESIGNED FOR USE AS HORIZONTAL MEMBERS. THEY ARE
 BEING USED AS A ROOF SYSTEM COMPONENT FOR THE PROPOSED
 COOLER.
 2. PER SECTION 5. OF THE NOA, THE WALL PANELS REQUIRE A
 STRUCTURAL SUPPORT SYSTEM.
 PLEASE CLARIFY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-12 Cont ID  
Sent By cthroop Date 2018-02-12 Time 07:52 Rev Time 0.00
Received By cthroop Date 2018-02-10 Time 11:06 Sent To  
Notes
2018-02-12 08:01:00BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN DESIGN IS BASED ON THE 2014 FBC 5TH ED. PROVIDE
 DESIGN BASED ON THE 2017 FBC 6TH ED.
 2. PLAN PAGE #1 REFERENCES NOA 13-0909.11. THIS NOA IS
 VOID AND THERE IS NO DESCRIPTION OF IT'S PURPOSE.
 3. PROVIDE NOA FOR COOLER DOORS.
 4. PROVIDE DESIGN AND NOA FOR RAIN COVER (ROOF) OF
 COOLER.
 5. PROVIDE DETAIL OR NOA FOR WALL BRACKET.
 6. PROVIDE FOUNDATION DETAIL.
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-08-15 Cont ID  
Sent By cthroop Date 2018-08-15 Time 16:08 Rev Time 0.00
Received By cthroop Date 2018-07-31 Time 14:43 Sent To  
Notes
2018-08-01 14:43:25RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-03 Time 09:37 Rev Time 0.00
Received By shill Date 2018-06-22 Time 13:15 Sent To  
Notes
2018-06-25 13:15:47RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-05-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-27 Time 13:32 Sent To  
Notes
2018-04-30 11:01:264/30 TO CT DESK
  
2018-04-02 18:46:084/2 ON SH DESK
  
  
2018-03-28 13:33:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-19 Cont ID  
Sent By cthroop Date 2018-03-19 Time 11:36 Rev Time 0.00
Received By cthroop Date 2018-03-07 Time 13:13 Sent To I
Notes
2018-03-08 13:13:49RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-02 Time 13:03 Sent To  
Notes
2018-02-02 13:03:07ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-08-07 Cont ID  
Sent By ccole Date 2018-08-07 Time 09:35 Rev Time 0.00
Received By ccole Date 2018-08-07 Time 09:28 Sent To B
Notes
2018-08-07 09:41:02PROVISO:
 MECHANICAL APPROVAL IS FOR THE WALK-IN COOLER
 REFRIGERATION SYSTEM ONLY.
 THE WALK-IN BOX HAS A BUILDING REVIEW PENDING.
 CCOLE- 8/7/18
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-07-09 Cont ID  
Sent By ccole Date 2018-07-09 Time 09:48 Rev Time 0.00
Received By ccole Date 2018-07-09 Time 09:48 Sent To I
Notes
2018-07-09 09:55:424TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18020006
 7/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE THE BUILDING REVIEW COMMENTS BY SAMANTHA
 HILL DATED 7/3/18 . MECHANICAL APPROVAL FOR THE WALKIN
 COOLER IS CONTINGENT ON ALL BUILDING REVIEW COMMENTS
 ADDRESSED, AND THE RESUBMITTAL OF CORRECTED PLANS AND
 DOCUMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-10 Cont ID  
Sent By ccole Date 2018-05-10 Time 15:39 Rev Time 0.00
Received By ccole Date 2018-05-10 Time 15:39 Sent To I
Notes
2018-05-10 16:30:423RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020006
 5/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE USE OF THE KINGSPAN 300 INSULATED WALL PANELS TO
 FORM THE ROOF OF THE WALK-IN COOLER IS STILL IN
 QUESTION BY THE BUILDING DEPARTMENT. AS PREVIOUSLY
 STATED IN THE1ST AND 2ND REVIEWS, THE ENGINEERING
 REPORT CONTAINED IN THE MIAMI-DADE NOA #16-0706.08
 INDICATES THE PANELS HAVE BEEN EVALUATED AS NON BEARING
 EXTERIOR WALL PANELS. THEY HAVE NOT BEEN EVALUATED AS A
 ROOF
  
 PANEL. IN RESPONSE, THE PROJECT MANAGER HAS SUBMITTED A
 DOCUMENT FROM THE MANUFACTURER TITLED "UNIFORM WIND +
 THERMAL LOAD". THIS STRUCTURAL ANALYSIS APPEARS TO BE
 FOR AN INDIVIDUAL WALL PANEL, AND DOES NOT ADDRESS THE
 USE OF THE PANEL AS A ROOF PANEL. FURTHER, THE ANALYSIS
 IS NOT SITE SPECIFIC AND IS NOT SIGNED AND SEALED BY A
 FLORIDA REGISTERED ENGINEER AS REQUIRED BY FLORIDA
  
 STAUTE 471, AND FAC 16G15-23.002.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-14 Cont ID  
Sent By ccole Date 2018-03-14 Time 17:36 Rev Time 0.00
Received By ccole Date 2018-03-14 Time 17:36 Sent To B
Notes
2018-03-14 18:02:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18020006
 3/14/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED IT BELOW WITH SOME ADDITIONAL INFORMATION:
  
 NOA #16-0706.08 PROVIDES ENGINEERING CERTIFICATION FOR
 THE THERMALSPAN 300 INSULATED METAL WALL PANELS. THERE
 ARE NO DETAILS OR CERTIFICATIONS ON THE NOA FOR THE
 ROOF PANELS, AND NO TYPICAL DETAILS ARE PROVIDED FOR
 ATTACHMENT AND SUPPORT OF ROOF PANELS.
  
 PLEASE REFER TO THE ENGINEERING REPORT & DRAWINGS FOR
 THE THERMALSPAN 300 INSULATED METAL WALL PANELS
 ATTACHED WITH THE NOA. ON PAGE 2 OF THE DOCUMENT SEE
 ITEM 3.0 EVALUATED USES, AND 4.0 ASSEMBLY DESCRIPTION.
 THE ENGINEER IS CLEARLY STATING THAT THESE PANELS ARE
 NON-LOAD BEARING AND CAN ONLY BE INSTALLED VERTICALLY.
 THE DRAWING ON PLAN SHEET 2 IS DEPICTING AN
  
 INSTALLATION INCONSISTENT WITH THE ENGINEERING
 CERTIFICATION, AND BEYOND THE LIMITATIONS OF USE FOR
 THE PANEL.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-08 Cont ID  
Sent By ccole Date 2018-02-08 Time 17:05 Rev Time 0.00
Received By ccole Date 2018-02-08 Time 17:05 Sent To B
Notes
2018-02-09 11:25:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18020006
 2/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1, DESIGN CRITERIA: THE FLORIDA BUILDING CODE
 SIXTH EDITION-2017 WENT INTO EFFECT ON JAN.1, 2017.
 THIS PERMIT APPLICATION AND PLANS WERE SUBMITTED AFTER
 THAT DATE. PLEASE UPDATE THE DESIGN PARAMETERS FOR THE
 PROJECT, AND THE DESIGN CRITERIA LISTED ON SHEET A1 TO
 BE IN COMPLIANCE WITH THE CURRENT CODES.
  
 2) SHEET 1: THE NOA #13-0909.11 HAS BEEN SUPERSEDED BY
 #16-0706.08. PLEASE SUBMIT COPIES OF THE NOA WITH
 APPROVAL STAMPS BY THE EOR.
  
 3) NOA #16-0706.08 PROVIDES ENGINEERING CERTIFICATION
 FOR NONBEARING EXTERIOR WALL PANELS. THERE ARE NO
 DETAILS OR CERTIFICATIONS ON THE NOA FOR THE ROOF
 PANELS, AND NO TYPICAL DETAILS ARE PROVIDED FOR
 ATTACHMENT ABND SUPPORT OF ROOF PANELS. PLEASE NOTE
 THAT THE NOA IS FOR THERMALSPAN 300 PANEL, BUT THE PLAN
 INDICATES ECO-FICIENT PANELS.
  
 4) PROVIDE AN ATTACHMENT DETAIL ON THE PLAN FOR THE
 VINYL RAIN COVER, AND SUPPORT A PRODUCT DATA SHEET
 APPROVED BY THE EOR.
  
 5) PROVIDE ENGINEERED DETAILS FOR THE WALL BRACKET.
 CLARIFY IF THE BRACKET IS TO BE SITE BUILT, OR IS THE
 BRACKET A MANUFACTURED PRODUCT THAT HAS A FL. PRODUCT
 APPROVAL OR A MIAMI-DADE NOA?
  
 6) SPECS FOR THE FJAF-0108-TAC-052 CONDENSER AND THE
 LSCO78TFC EVAPORATOR NOT SUBMITTED.
  
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR PENDING
 RESUBMITTAL OF CORRECTED PLANS AND DOCUMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  