Plan Review Details - Permit 18011159
Plan Review Stops For Permit 18011159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By jgomez Date 2018-02-22 Time 19:09 Rev Time 0.00
Received By jgomez Date 2018-02-22 Time 18:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 07:47 Rev Time 0.00
Received By jgomez Date 2018-02-01 Time 18:52 Sent To  
Notes
2018-02-02 08:54:17RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- A) ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, 6TH
 EDITION (2017) THIS BUILDING IS LOCATED IN EXPOSURE "C"
 NOT "B" AS CIRCLED ON THE WIND LOAD CALCULATIONS
 SUBMITTED. BASED ON THE WIND LOAD CALCULATIONS
 SUBMITTED, THE DESIGN PRESSURES OF THE DOORS PRODUCT
 APPROVAL SUBMITTED (FL17184.5) DON'T MEET THE
 CALCULATED DESIGN PRESSURES. THEREFORE, NEED TO PROVIDE
 A PRODUCT APPROVAL THAT MEETS THE CALCULATED DESIGN
 PRESSURES.
  
 B) CALCULATIONS SUBMITTED ARE REFERENCING THE 2014
 BUILDING CODE. THE CURRENT CODE IS THE FBC 6TH EDITION
 (2017). REVISE AS REQUIRED. CHAPTER 553 FLORIDA
 STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-22 Cont ID  
Sent By jgomez Date 2018-02-22 Time 19:12 Rev Time 0.00
Received By jgomez Date 2018-02-20 Time 10:01 Sent To I
Notes
2018-02-21 10:01:42RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 08:37 Rev Time 0.00
Received By jgomez Date 2018-01-29 Time 11:32 Sent To I
Notes
2018-01-30 11:32:22BLDG<5K