Plan Review Details - Permit 18011090
Plan Review Stops For Permit 18011090
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-02-16 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-14 Time 12:41 Sent To  
Notes
2018-02-15 12:41:29RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-02-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-06 Time 11:45 Sent To  
Notes
2018-02-07 11:45:42RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-26 Time 13:03 Sent To  
Notes
2018-01-29 13:04:09ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-02-16 Cont ID  
Sent By ccole Date 2018-02-16 Time 12:33 Rev Time 0.00
Received By ccole Date 2018-02-16 Time 12:33 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-02-12 Cont ID  
Sent By ccole Date 2018-02-12 Time 11:02 Rev Time 0.00
Received By ccole Date 2018-02-12 Time 11:00 Sent To  
Notes
2018-02-12 11:04:232ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18011090
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESCHECK ENERGY COMPLIANCE SUBMITTAL IS
 INCOMPLETE, AND IS ALSO UNDER THE OUTDATED 2014 CODE.
 PLEASE NOTE THAT THE FLORIDA ENERGY CODE SIXTH EDITION-
 2017 WENT INTO EFFECT JAN.1, 2018. THE ENERGY SUBMITTAL
 IS ALSO MISSING COMPLIANCE DATA FOR THE AC SYSTEM AND
 SHOWS "NAPLES, FLORIDA" AS THE PROJECT LOCATION. PLEASE
 REMOVE THE 2014 ENERGYGAUGE DISPLAY CARD FROM
  
 THE RESCHECK SUBMITTAL. THE DISPLAY CARD IS USED ONLY
 WHEN SUBMITTED AN ENERGYGAUGE COMPLIANCE REPORT.
  
 2) THE 10X6 TRANSFER GRILLS ARE UNDERSIZED FOR 150
 CFMS. THE GRILLS SHALL BE MINIMUM 75 SQ. INCHES-
 SECTION M1602 FBC-17 RESIDENTIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By ccole Date 2018-02-02 Time 14:43 Rev Time 0.00
Received By ccole Date 2018-02-02 Time 14:03 Sent To I
Notes
2018-02-02 14:52:511ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18011090
 2/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION R503.2 FBC-17 ENERGY CONSERVATION:
 THE NEW CONDITIONED HOUSE SHALL BE BROUGHT INTO FULL
 COMPLIANCE WITH THE CODE. PLEASE SUBMIT A CODE
 COMPLIANCE FORM- SEE TABLE R101.5.1.
  
 2) PROVIDE THE DIMENSIONS OF THE BEDROOM RETURN GRILLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  