Plan Review Details - Permit 18011090
Plan Review Stops For Permit 18011090 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-16 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-02-14 |
Time |
12:41 |
Sent To |
|
|
Notes |
2018-02-15 12:41:29 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-12 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-02-06 |
Time |
11:45 |
Sent To |
|
|
Notes |
2018-02-07 11:45:42 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-02 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-01-26 |
Time |
13:03 |
Sent To |
|
|
Notes |
2018-01-29 13:04:09 | ROUTED TO MECHANICAL INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2018-02-16 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-02-16 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-02-16 |
Time |
12:33 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-02-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-02-12 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-02-12 |
Time |
11:00 |
Sent To |
|
|
Notes |
2018-02-12 11:04:23 | 2ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL | | PERMIT #18011090 | | 2/12/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE RESCHECK ENERGY COMPLIANCE SUBMITTAL IS | | INCOMPLETE, AND IS ALSO UNDER THE OUTDATED 2014 CODE. | | PLEASE NOTE THAT THE FLORIDA ENERGY CODE SIXTH EDITION- | | 2017 WENT INTO EFFECT JAN.1, 2018. THE ENERGY SUBMITTAL | | IS ALSO MISSING COMPLIANCE DATA FOR THE AC SYSTEM AND | | SHOWS "NAPLES, FLORIDA" AS THE PROJECT LOCATION. PLEASE | | REMOVE THE 2014 ENERGYGAUGE DISPLAY CARD FROM | | | | THE RESCHECK SUBMITTAL. THE DISPLAY CARD IS USED ONLY | | WHEN SUBMITTED AN ENERGYGAUGE COMPLIANCE REPORT. | | | | 2) THE 10X6 TRANSFER GRILLS ARE UNDERSIZED FOR 150 | | CFMS. THE GRILLS SHALL BE MINIMUM 75 SQ. INCHES- | | SECTION M1602 FBC-17 RESIDENTIAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-02-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-02-02 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-02-02 |
Time |
14:03 |
Sent To |
I |
|
Notes |
2018-02-02 14:52:51 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18011090 | | 2/2/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REFER TO SECTION R503.2 FBC-17 ENERGY CONSERVATION: | | THE NEW CONDITIONED HOUSE SHALL BE BROUGHT INTO FULL | | COMPLIANCE WITH THE CODE. PLEASE SUBMIT A CODE | | COMPLIANCE FORM- SEE TABLE R101.5.1. | | | | 2) PROVIDE THE DIMENSIONS OF THE BEDROOM RETURN GRILLS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
|