2018-01-31 12:06:26 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1- WIND LOAD CALCULATIONS SUBMITTED: |
| A) NEED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| |
| B) REVISE THE MINIMUM EDGE DISTANCE. ACCORDING TO |
| FOOTNOTE OF FIGURE R301.2(7) FBC-RESIDENTIAL, 6TH |
| EDITION (2017) THE MINIMUM EDGE DISTANCE "A" IS 4'-0" |
| IN ALL CASES NOT 3'-0". REVISE AS REQUIRED. |
| |
| 2- STORM PANELS FLORIDA PRODUCT APPROVAL FL11968-R4 |
| SUBMITTED; |
| A) THE MINIMUM PANEL LENGTH IS 3'-0". SEE NOTE BELOW |
| THE MAXIMUM DESIGN PRESSURES AND MAXIMUM PANEL LENGTH |
| TABLE. OPENINGS # 5 AND #13 DON'T COMPLY WITH THIS |
| REQUIREMENT. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B) THE FASTENER EDGE DISTANCE SPECIFIED ON THE SHUTTERS |
| INSTALLATION SCHEDULE DOESN'T MATCH FASTENER SPACING |
| SHOWN ON ALTERNATIVE DETAIL 1 ON SHEET 11 OF 14 OF |
| SHUTTER DRAWINGS SUBMITTED. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| C) TYPE OF TRACK SHOWN ON ALTERNATIVE DETAIL #4 ON |
| SHEET 11 OF 14 DOESN'T MATCH THE TYPE OF TRACK MARKED |
| ON SHEET 1A OF 14. REVISE AS REQUIRED TO MATCH AND |
| AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) CLARIFY WHY OPENING #12 IS NOT INCLUDED AT THE TOP |
| AND BOTTOM OF ALTERNATIVES #1 AND #4 ON SHEET 11 OF 14. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| E) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM |
| EMBEDMENT REQUIRED ON SHEET 11 OF 14. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| F) OPENINGS #1 AND #2 ARE LOCATED IN THE END ZONE #5. |
| COORDINATE WITH ITEM #1(B) ABOVE. REVISE AS REQUIRED, |
| INCLUDING THE DESIGN PRESSURES. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3- ACCORDION SHUTTERS OPENING #20. REVISE INSTALLATION |
| SCHEDULE SUBMITTED: |
| A) SPECIFICATIONS FOR TOP OF OPENING #20 ON SHEET 4 OF |
| 13 IS FOR CONCRETE CONSTRUCTION. THIS IS A WOOD FRAMED |
| HOUSE. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B) OPENINGS #20 SPECIFY ANCHOR TYPE "A" WITH A SPACING |
| OF 16" O.C. AT THE BOTTOM. ACCORDING TO ANCHOR SCHEDULE |
| TABLE ON PAGE 11 OF 13 OF ACCORDION SHUTTERS SUBMITTED |
| THIS ANCHOR REQUIRES 3.000PSI CONCRETE STRENGTH. IT |
| LOOKS LIKE THE FLOOR TRACK IS GOING TO BE MOUNTED ON |
| THE CONCRETE SLAB. TYPICALLY THE CONCRETE SLABS FOR |
| RESIDENTIAL PROJECTS ARE DESIGNED FOR 2500PSI CONCRETE |
| STRENGTH. REVISE THE ANCHOR TYPE AND SPACING OR PROVIDE |
| PROOF THAT THE CONCRETE STRENGTH IS 3.000PSI. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| C) THE FASTENER EDGE DISTANCE EXCLUDES THE STUCCO |
| FINISH. SEE NOTES ON ANCHOR SCHEDULE TABLE ON SHEET 11 |
| OF 13. ADD THE STUCCO THICKNESS AND REVISE INSTALLATION |
| SCHEDULE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM |
| EMBEDMENT REQUIRED ON ANCHOR SCHEDULE TABLE ON SHEET 11 |
| OF 13. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- SCOPE OF WORK SHOWN ON THE PERMIT APPLICATION |
| DOESN'T MATCH T INFORMATION SUBMITTED. PERMIT |
| APPLICATION SPECIFIES INSTALLATION OF 23 ACCORDION |
| SHUTTERS, WHILE INFORMATION SUBMITTED IS FOR |
| INSTALLATION OF ACCORDION SHUTTERS ON ONLY ONE OPENING |
| AND INSTALLATION OF STORM PANELS ON 19 OPENINGS. REVISE |
| SCOPE OF WORK ON THE PERMIT APPLICATION TO MATCH ACTUAL |
| SCOPE OF WORK TO AVOID CONFLICTS/DELAYS. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |