Plan Review Details - Permit 18011037
Plan Review Stops For Permit 18011037
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 13:04 Rev Time 0.00
Received By rmcdouga Date 2018-03-08 Time 13:03 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-27 Cont ID  
Sent By rmcdouga Date 2018-02-27 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2018-02-27 Time 07:19 Sent To I
Notes
2018-02-27 07:46:17PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBER FOR THE 27 KW GENERAC (RG027) IS
 NOT LISTED ON THE AMERICAST GENERATOR PAD ENGINEERING
 THAT WAS SUBMITTED. THERE WERE NO 27 KW MODELS LISTED
 ON THE PAD ENGINEERING. FBC 301.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-13 Cont ID  
Sent By rmcdouga Date 2018-02-13 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-02-13 Time 18:59 Sent To  
Notes
2018-02-13 19:06:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD PLANS HAVE SEVERAL REFERENCES TO
 THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017).
  
 2) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 FLORIDA LICENSED ENGINEER'S SEAL AND HANDWRITTEN
 SIGNATURE AFFIXED PER FLORIDA STATUTE 471 AND FAC
 61G15-23.003.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By jleahy Date 2018-02-15 Time 10:48 Rev Time 0.00
Received By jleahy Date 2018-02-15 Time 10:48 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-02-27 Cont ID  
Sent By lcrespo Date 2018-02-27 Time 06:38 Rev Time 0.00
Received By lcrespo Date 2018-02-27 Time 06:25 Sent To  
Notes
2018-02-27 06:41:0002/27/18 APPROVED BY PLUMBING AND SENT TO ROBERT
 MCDOUGA AT BUILDING, LAC

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-02-20 Cont ID  
Sent By lcrespo Date 2018-02-20 Time 14:00 Rev Time 0.00
Received By lcrespo Date 2018-02-20 Time 14:00 Sent To  
Notes
2018-02-20 14:01:26DENIED
  
 1) GENERAC COMPLIES WITH THE NFPA (37) SEC 4.1.4 AND
 HAS CHANGED GUIDELINES FOR INSTALLATION OF THE
 GENERATOR YOU ARE INSTALLING TO 18 INCHES FROM THE BACK
 SIDE OF THE GENERATOR TO A STATIONARY WALL OR BUILDING
 AND NO WINDOWS OR OPENING IN THE WALL ARE PERMITTED
 WITHIN 5 FEET FROM ANY POINT OF THE GENERATOR. THE
 SPECIFICATION FOR THE MANUAL YOU SUMMITED IS FROM
 12/4/15 AND IT IS OUTDATED, PLEASE SUBMIT THE UPDATED
 ONES FROM 9/15/17 WHICH HAVE THE ABOVE CLEARANCES
 SPECIFIED. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2) THE APPLICABLE SIZING TABLES USED TO SIZE THE GAS
 ARE NOT THE 2017 FBC FG CODE, PLEASE PROVIDE UPDATED
 SHEETS TO REFLECT THE WORK BEING DONE. WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-08 Cont ID  
Sent By rmcdouga Date 2018-03-08 Time 13:04 Rev Time 0.00
Received By rmcdouga Date 2018-03-02 Time 08:08 Sent To  
Notes
2018-03-06 08:09:03RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-27 Cont ID  
Sent By rmcdouga Date 2018-02-27 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2018-02-22 Time 10:36 Sent To  
Notes
2018-02-23 10:36:23RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-23 Cont ID  
Sent By lcrespo Date 2018-02-20 Time 14:00 Rev Time 0.00
Received By lmarchan Date 2018-02-20 Time 14:00 Sent To  
Notes
2018-01-26 10:49:26ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2018-02-13 Cont ID  
Sent By PG Date 2018-02-13 Time 08:47 Rev Time 0.00
Received By pgreilic Date 2018-01-31 Time 13:34 Sent To  
Notes
2018-02-13 08:52:18LANDSCAPE SCREENING REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]