Plan Review Details - Permit 18011034
Plan Review Stops For Permit 18011034
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By cthroop Date 2018-03-16 Time 15:58 Rev Time 0.00
Received By cthroop Date 2018-03-15 Time 15:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-22 Cont ID  
Sent By cthroop Date 2018-02-22 Time 08:16 Rev Time 0.00
Received By cthroop Date 2018-02-21 Time 15:46 Sent To  
Notes
2018-02-22 08:27:45BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED BARREL TILE
 ROOF SYSTEM.
 3. IDENTIFY MODEL OF DOOR TO BE INSTALLED FROM PRODUCT
 APPROVAL FL 16094-R6.
 4. PRODUCT APPROVAL FL 21837-R1 HAS NO MODELS THAT ARE
 IMPACT RESISTANT RATED. IF ANY OF THESE DOORS ARE
 INSTALLED PROVIDE CITY OF WEST PALM BEACH SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 5. THERE ARE TWO NARRATIVES FOR THE ROOF SHEATHING OF
 THE NEW ENTRY PORCH ROOF. ONE NARRATIVE REQUIRES 5/8"
 CDX, THE OTHER REQUIRES 1/2" CDX. PLEASE CLARIFY.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PROVIDE COMPLETED CITY OF WEST PALM BEACH ? SCHEDULE
 FOR INSTALLATION OF OPENING PROTECTIVE DEVICES AND
 ASSEMBLIES
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By jpearson Date 2018-03-12 Time 12:21 Rev Time 0.00
Received By jpearson Date 2018-03-12 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-09 Cont ID  
Sent By jpearson Date 2018-02-09 Time 15:48 Rev Time 0.00
Received By jpearson Date 2018-02-09 Time 15:48 Sent To  
Notes
2018-02-09 15:48:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE DETAILS OF SERVICE FOR MAIN HOUSE.
 PROVIDE CORRECTION AND/OR CLARIFICATION. FBC 107.2.1;
 NEC 230.2; FBC RE E3601.2
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1
 3. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS IN THE
 CARRIAGE HOUSE. NEC 225.31, 225.32
 5. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN
 GARAGE, INCLUDING THE GARAGE DOOR OPENER. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D); FBC RE E3902.10
 9. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. INCLUDE ALL LOADS, CURRENTLY THE WASHERS
 AND DRYERS ARE NOT INCLUDED. NEC 215.2, 220, 408.30;
 FBC RE E3602.2
 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 FBC RE E3706.2, E3902
 11. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-02-02 Cont ID  
Sent By fmittner Date 2018-02-02 Time 11:12 Rev Time 0.00
Received By fmittner Date 2018-02-02 Time 11:12 Sent To  
Notes
2018-02-02 11:13:21PENDING HPB APPROVAL 2/27/17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-16 Cont ID  
Sent By cthroop Date 2018-03-16 Time 15:58 Rev Time 0.00
Received By cthroop Date 2018-02-27 Time 14:06 Sent To I
Notes
2018-02-28 14:06:54R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-22 Cont ID  
Sent By cthroop Date 2018-02-22 Time 08:27 Rev Time 0.00
Received By cthroop Date 2018-01-25 Time 13:44 Sent To I
Notes
2018-01-26 13:44:41R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-02-22 Cont ID  
Sent By cthroop Date 2018-02-22 Time 07:24 Rev Time 0.00
Received By cthroop Date 2018-02-21 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By cmontell Date 2018-02-15 Time 16:21 Rev Time 0.00
Received By cmontell Date 2018-02-15 Time 16:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 09:40 Rev Time 0.00
Received By gjohnson Date 2018-02-14 Time 11:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-15 Cont ID  
Sent By fmittner Date 2018-03-15 Time 08:45 Rev Time 0.00
Received By fmittner Date 2018-03-14 Time 10:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-02-02 Cont ID  
Sent By fmittner Date 2018-02-02 Time 11:12 Rev Time 0.00
Received By fmittner Date 2018-02-02 Time 11:12 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved