Plan Review Details - Permit 18010799
Plan Review Stops For Permit 18010799
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-26 Cont ID  
Sent By skennedy Date 2020-02-26 Time 14:10 Rev Time 0.00
Received By skennedy Date 2020-02-26 Time 14:10 Sent To  
Notes
2020-02-26 14:10:27DOOR PRODUCTS STILL NEEDED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-20 Cont ID  
Sent By skennedy Date 2020-02-20 Time 16:03 Rev Time 0.00
Received By skennedy Date 2020-02-20 Time 16:03 Sent To  
Notes
2020-02-21 14:18:52PA SUBMITTAL BY CONSULTANT CONTRACTOR IS DEFICIENT.
 ORIGINAL DESIGNER UNAVAILABLE. PERMIT EXPIRED AND FINAL
 DOOR & WINDOW PRODUCTS HAVE NOT BEEN ACCEPTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 10:47 Rev Time 0.00
Received By jgomez Date 2018-02-02 Time 09:59 Sent To  
Notes
2018-02-02 10:00:56RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EXTERIOR DOORS DRAWING NO JW142012FL SUBMITTED:
 A) THESE DOORS DON'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. NEED TO PROVIDE
 PRODUCT APPROVAL (2 COPIES) OF DOORS THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER ON SHEET
 A-1/3.
 SEC. R301.1 FB-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO DRAWING JW142012FL SUBMITTED.
 FAC 61G20-3.001
  
 2- CASEMENT WINDOWS NOA 14-0908.20 SUBMITTED: CLEARLY
 MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET
 A-1/3. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- SINGLE HUNG WINDOWS NOA 16-1003.01 SUBMITTED:
 CLEARLY MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING
 TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET
 A-1/3. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- FIXED WINDOWS NOA 17-0531.05 SUBMITTED:
 A) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR FIXED
 WINDOWS IF PLANS DON'T SPECIFY ANY FIXED WINDOWS. IF
 FIXED WINDOWS ARE GOING TO BE INSTALLED, THEN ENGINEER
 OF RECORD NEEDS TO REVISE PLANS ACCORDINGLY. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) IF INSTALLING FIXED WINDOWS, THEN CLEARLY MARK WHICH
 WINDOW SIZE AND GLASS TYPE IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD ON SHEET A-1/3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- NEED TO PROVIDE WINDOW MULLIONS PRODUCT APPROVALS (2
 COPIES) AS REQUESTED ON PROVISO. NOTE: CLEARLY SPECIFY
 WINDOW SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET A-1/3. SEC. R301.1 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-01-30 Cont ID  
Sent By fmittner Date 2018-01-30 Time 13:23 Rev Time 0.00
Received By fmittner Date 2018-01-30 Time 13:23 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-02 Cont ID  
Sent By jgomez Date 2018-02-02 Time 11:34 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 15:30 Sent To I
Notes
2018-01-23 15:30:19REVISION ROUTED TO FMITTNER VIA ZONING INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved