Plan Review Details - Permit 18010784
Plan Review Stops For Permit 18010784
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-02-27 Cont ID  
Sent By jgomez Date 2018-02-27 Time 17:48 Rev Time 0.00
Received By jgomez Date 2018-02-27 Time 13:48 Sent To  
Notes
2018-02-27 17:49:49TALKED TO DAWN FROM NEW SOUTH WINDOWS TO DISCUSS
 ENGINEER LETTER FOR FLORIDA PRODUCT APPROVAL FL17472.2.
  
 JULIO,
 WE WILL BE USING 1 X 4 ON BOTH HORIZONTAL AND VERTICAL.
 THANK YOU
  
 DAWN RITTER
 PERMIT COORDINATOR
 IMAGE RESULT FOR NEW SOUTH WINDOWS
 NEW SOUTH WINDOW WPB
 2526 OKEECHOBEE BLVD
 WEST PALM BEACH, FL 33409
 TEL: 561.712.9000 | FAX: 561.478.4100
 [email protected]
 WWW.NEWSOUTHWINDOW.COM

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-02-26 Cont ID  
Sent By jgomez Date 2018-02-26 Time 18:17 Rev Time 0.00
Received By jgomez Date 2018-02-26 Time 17:54 Sent To  
Notes
2018-02-26 18:15:21RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 NOTE;
 FLORIDA PRODUCT APPROVAL FL15413.9 SUBMITTED IS THE
 SAME THAT WAS SUBMITTED ON THE SECOND REVIEW. SEE COPY
 OF COMMENTS BELOW. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS ALL THE CRITERIA FOR ALL HORIZONTAL AND
 VERTICAL MULLIONS BASED ON ALL THE WINDOW SIZES.
  
  
  
 RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- WINDOW MULLION PRODUCT APPROVAL FL15413- R5
 SUBMITTED: ACCORDING TO HORIZONTAL MULLION FL-15413.9
 THE MAXIMUM WINDOW FRAME HEIGHT IS 54". SEE SHEET 1 OF
 8 OF DRAWING SUBMITTED. THE DOUBLE HUNG WINDOW SIZE IS
 61.5". THEREFORE, THIS MULLION SIZE CAN NOT BE USED.
 PROVIDE ANOTHER PRODUCT APPROVAL THAT CAN BE USED.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-02-26 Cont ID  
Sent By jgomez Date 2018-02-26 Time 15:15 Rev Time 0.00
Received By jgomez Date 2018-02-26 Time 14:46 Sent To  
Notes
2018-02-26 15:00:20RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 1- WINDOW MULLION PRODUCT APPROVAL FL17472-R1 SUBMITTED
 IS FOR 2014 CODE VERSION. THE CURRENT CODE IS THE 2017
 CODE. PROVIDE 2 COPIES OF APPROVED PRODUCT APPROVAL FOR
 CURRENT CODE. CHAPTER 553 FLORIDA STATUTES.
  
 2- CLEARLY IDENTIFY SIZE OF MULLIONS TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL, 6TH EDITION (2017).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-02-14 Cont ID  
Sent By jgomez Date 2018-02-13 Time 17:18 Rev Time 0.00
Received By jgomez Date 2018-02-13 Time 17:17 Sent To  
Notes
2018-02-13 17:43:07RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 1- WINDOW MULLION PRODUCT APPROVAL FL15413- R5
 SUBMITTED: ACCORDING TO HORIZONTAL MULLION FL-15413.8
 THE MAXIMUM HORIZONTAL MULLION SPAN IS 72". SEE SHEET 1
 OF 9 OF DRAWING SUBMITTED. THE SIZE OF WINDOW #3 IS 73"
 X 23". THEREFORE, THIS MULLION SIZE CAN NOT BE USED.
 PROVIDE ANOTHER PRODUCT APPROVAL THAT CAN BE USED.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-05 Cont ID  
Sent By jgomez Date 2018-02-05 Time 17:39 Rev Time 0.00
Received By jgomez Date 2018-02-05 Time 17:13 Sent To  
Notes
2018-02-05 17:38:59RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 1- WINDOW MULLION PRODUCT APPROVAL FL15413- R5
 SUBMITTED: ACCORDING TO HORIZONTAL MULLION FL-15413.9
 THE MAXIMUM WINDOW FRAME HEIGHT IS 54". SEE SHEET 1 OF
 8 OF DRAWING SUBMITTED. THE DOUBLE HUNG WINDOW SIZE IS
 61.5". THEREFORE, THIS MULLION SIZE CAN NOT BE USED.
 PROVIDE ANOTHER PRODUCT APPROVAL THAT CAN BE USED.
 FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By jgomez Date 2018-01-24 Time 14:18 Rev Time 0.00
Received By jgomez Date 2018-01-24 Time 12:44 Sent To  
Notes
2018-01-24 14:21:06RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- REPLACEMENT OF BEDROOM WINDOWS EGRESS REQUIREMENTS:
 A) SKETCH SUBMITTED INDICATES THAT THE OPENING WHERE
 THE WINDOWS ARE GOING TO BE REPLACED IS LOCATED IN AN
 "OFFICE". ACCORDING TO CITY RECORDS THIS ROOM WAS
 DESIGNED AS BEDROOM #2. (MODEL "C" PERMIT #91BN02294).
 PLEASE REVISE INFORMATION ON SKETCH TO AVOID CONFLICTS.
 INDICATE THAT IS A BEDROOM. THIS ROOM MAY BE USED AS AN
 OFFICE, BUT IT NEEDS TO COMPLY WITH THE BEDROOM EGRESS
 REQUIREMENTS OF SEC. R702.5 FBC-EXISTING BUILDING, 6TH
 EDITION (2017).
  
 B) SPECIFY ACTUAL SIZE OF EXISTING 2-25 SINGLE HUNG
 WINDOWS AND SIZE OF ROUGH OPENING TO VERIFY COMPLIANCE
 WITH THE PROPOSED DOUBLE HUNG WINDOWS AS REQUIRED BY
 SEC. 702.5 FBC-EXISTING BUILDING. PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE PROPOSED
 DOUBLE HUNG WINDOW (36" X 61-1/2") WILL PROVIDE AN
 EQUAL OR GREATER WINDOW OPENING AREA THAN THE EXISTING
 2-25SH WINDOWS AS REQUIRED BY R702.5 FBC-EXISTING
 BUILDING, 6TH EDITION (2017).
  
 2- WINDOW MULLION PRODUCT APPROVAL FL7472-R2 SUBMITTED:
 A) THIS PRODUCT APPROVAL IS NOT APPROVED. THE STATUS OF
 THE PRODUCT APPROVAL SUBMITTED IS "VALIDATED". PROVIDE
 2 COPIES OF PRODUCT APPROVAL THAT IS "APPROVED" UNDER
 THE CURRENT 2017 FBC.
 FAC 61G20-3.001.
  
 B) CLEARLY SPECIFY SIZED OF ALL WINDOW MULLIONS TO BE
 USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
 SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION (2017).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-02-27 Cont ID  
Sent By jgomez Date 2018-02-27 Time 17:48 Rev Time 0.00
Received By jgomez Date 2018-02-27 Time 13:47 Sent To  
Notes
2018-02-27 13:48:39TALKED TO DAWN FROM NEW SOUTH WINDOWS TO DISCUSS
 ENGINEER LETTER FOR FLORIDA PRODUCT APPROVAL FL17472.2.
  
 JULIO,
 WE WILL BE USING 1 X 4 ON BOTH HORIZONTAL AND VERTICAL.
 THANK YOU
  
 DAWN RITTER
 PERMIT COORDINATOR
 IMAGE RESULT FOR NEW SOUTH WINDOWS
 NEW SOUTH WINDOW WPB
 2526 OKEECHOBEE BLVD
 WEST PALM BEACH, FL 33409
 TEL: 561.712.9000 | FAX: 561.478.4100
 [email protected]
 WWW.NEWSOUTHWINDOW.COM

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-02-26 Cont ID  
Sent By jgomez Date 2018-02-26 Time 18:17 Rev Time 0.00
Received By jgomez Date 2018-02-26 Time 17:53 Sent To  
Notes
2018-02-26 17:54:04RECEIVED E-MAIL FROM KIM STONE.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-26 Cont ID  
Sent By jgomez Date 2018-02-26 Time 15:15 Rev Time 0.00
Received By jgomez Date 2018-02-20 Time 10:16 Sent To  
Notes
2018-02-21 10:17:08RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-14 Cont ID  
Sent By jgomez Date 2018-02-13 Time 17:44 Rev Time 0.00
Received By jgomez Date 2018-02-12 Time 14:00 Sent To I
Notes
2018-02-13 14:00:29RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-05 Cont ID  
Sent By jgomez Date 2018-02-05 Time 18:43 Rev Time 0.00
Received By jgomez Date 2018-01-29 Time 14:19 Sent To I
Notes
2018-01-30 14:19:28RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-24 Cont ID  
Sent By jgomez Date 2018-01-24 Time 15:32 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 10:59 Sent To I
Notes
2018-01-23 11:00:05BLDG <5K