Plan Review Details - Permit 18010778
Plan Review Stops For Permit 18010778
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-02-26 Cont ID  
Sent By jgomez Date 2018-02-26 Time 14:03 Rev Time 0.00
Received By jgomez Date 2018-02-26 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-02-21 Cont ID  
Sent By jgomez Date 2018-02-16 Time 19:33 Rev Time 0.00
Received By jgomez Date 2018-02-16 Time 18:15 Sent To  
Notes
2018-02-16 18:16:56RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- STORM SHUTTERS INSTALLATION SCHEDULE IS NOT CLEAR.
 SPECIFY SHUTTER MOUNTING CONDITIONS. MIAMI DADE IS NOT
 A MOUNTING CONDITION. SHUTTERS GLASS SEPARATION NEEDS
 TO BE REVISED. SEE TABLE 2 ON SHEET 5 OF 5 OF NOA
 DRAWINGS SUBMITTED. THE SHUTTERS SPAN DIMENSION IS NOT
 CLEAR IF THE STORM PANELS ARE MOUNTED VERTICALLY.
 REVISE ANCHOR SPACING BASED ON THE SUBSTRATE TO RECEIVE
 THE SHUTTERS (CONCRETE BLOCK). SEC. 107.2.1 CITY
 AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-07 Cont ID  
Sent By jgomez Date 2018-02-07 Time 12:40 Rev Time 0.00
Received By jgomez Date 2018-02-07 Time 12:04 Sent To  
Notes
2018-02-07 12:05:11RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- FLOOR PLAN SUBMITTED:
 A) ACCORDING TO PERMIT APPLICATION THE SCOPE OF WORK IS
 TO REPLACE ALL WINDOWS. AFTER METING WITH A.C EVANS IS
 NOT CLEAR IF ALL THE WINDOWS ARE GOING TO BE REPLACED.
 CLEARLY INDICATE ON FLOOR PLAN SUBMITTED WHICH ARE THE
 WINDOWS THAT ARE GOING TO BE BE REPLACED. ALSO, REVISE
 SCOPE OF WORK ON PERMIT APPLICATION TO MATCH PLANS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) LETTERING STATING BEDROOM EGRESS WINDOWS IS NOT
 CLEAR. PROVIDE CLEAR AND LEGIBLE LETTERING IDENTIFYING
 THE EGRESS WINDOWS. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- SINGLE HUNG PRODUCT APPROVAL:
 A) SINGLE HUNG FLORIDA PRODUCT APPROVAL FL21857
 SUBMITTED IS "PENDING THE FBC APPROVAL". NEED AN
 "APPROVED" APPLICATION STATUS. OR WINDOW MANUFACTURER
 MAY SUBMIT COMPLETE ORIGINAL SIGNED AND SEALED PRODUCT
 APPROVAL PACKAGE FOR BUILDING OFFICIAL REVIEW AND
 APPROVAL. NOTE: REVIEW TIME WILL DEPEND ON THE BUILDING
 OFFICIAL SCHEDULE. THIS PROCEDURE MAY TAKE A FEW DAYS.
 OR CONTRACTOR MAY SUBMIT ANOTHER PRODUCT APPROVAL THAT
 IS ALREADY APPROVED. FAC 61G203.001.
  
 B) PROVIDE COMPLETE PRODUCT APPROVAL, INCLUDING THE
 FLORIDA PRODUCT APPROVAL COVER PAGE SHOWING THE
 APPLICATION STATUTES AND CURRENT BUILDING CODE 2017.
 CHAPTER 553 FLORIDA STATUTE.
  
 C) PROVIDE LEGIBLE DRAWINGS. DRAWINGS SUBMITTED ARE TOO
 SMALL TO READ. PRINT DRAWINGS ON LANDSCAPE FORMAT SO
 DRAWINGS TAKE THE OVERALL SHEET AND ARE MORE LEGIBLE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- STORM SHUTTERS NOA 17-0118.08 SUBMITTED;
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE OR PROVIDE COMPLETE INSTALLATION IN ANY OTHER
 FORMAT THAT WILL HAVE ALL THE REQUIRED INFORMATION TO
 VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC.
 R301.1 FBC-RESIDENTIAL, 6TH EDITION (2017).
  
 B) PROVIDE LEGIBLE DRAWINGS. DRAWINGS SUBMITTED ARE TOO
 SMALL TO READ. PRINT DRAWINGS ON LANDSCAPE FORMAT SO
 DRAWINGS TAKE THE OVERALL SHEET AND ARE MORE LEGIBLE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- WINDOW MULLIONS:
 A) FLORIDA PRODUCT APPROVAL FL21844 SUBMITTED IS
 "PENDING THE FBC APPROVAL". NEED AN "APPROVED"
 APPLICATION STATUS. OR WINDOW MANUFACTURER MAY SUBMIT
 COMPLETE ORIGINAL SIGNED AND SEALED PRODUCT APPROVAL
 PACKAGE FOR BUILDING OFFICIAL REVIEW AND APPROVAL.
 NOTE: REVIEW TIME WILL DEPEND ON THE BUILDING OFFICIAL
 SCHEDULE. THIS PROCEDURE MAY TAKE A FEW DAYS. OR
 CONTRACTOR MAY SUBMIT ANOTHER PRODUCT APPROVAL THAT IS
 ALREADY APPROVED. FAC 61G203.001.
  
 B) CLEARLY SPECIFY MULLIONS SIZES TO BE USED TO VERIFY
 COMPLIANCE WITH SEC. R301.1 FBC-RESIDENTIAL.
  
 C) PROVIDE LEGIBLE DRAWINGS. DRAWINGS SUBMITTED ARE TOO
 SMALL TO READ. PRINT DRAWINGS ON LANDSCAPE FORMAT SO
 DRAWINGS TAKE THE OVERALL SHEET AND ARE MORE LEGIBLE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DRAFTING FEES
 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
 REVISE VALUATION AS REQUIRED. COORDINATE WITH NUMBER OF
 WINDOWS SHOWN ON PLANS TO BE REPLACED AND INCLUDE THE
 NEW WINDOWS SILLS SHOWN ON THE NORTH, EAST AND WEST
 ELEVATIONS ON SHEET 1 OF 2.
  
 6- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-24 Cont ID  
Sent By jgomez Date 2018-01-23 Time 18:26 Rev Time 0.00
Received By jgomez Date 2018-01-23 Time 18:09 Sent To  
Notes
2018-01-23 18:28:24RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE; FBC 6TH EDITION (2017).
  
 1- FLOOR PLAN SKETCH SUBMITTED:
 A) CLEARLY IDENTIFY ALL BEDROOMS OR SLEEPING AREAS TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 702.5 FBC-EXISTING BUILDING, 6TH EDITION (2017).
  
 B) CLEARLY SPECIFY EXISTING WINDOW TYPE AND SIZE AND
 PROPOSED WINDOW TYPE AND SIZE TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING. NOTE: INCLUDE THE WINDOW ROUGH OPENING.
  
 2- PROVIDE WINDOW CURRENT PRODUCT APPROVAL. NOA
 14-0722.07 SUBMITTED EXPIRED ON NOVEMBER 14, 2017.
 FAC 61G203.001.
  
 3- STORM SHUTTERS NOA 17-0118.08 SUBMITTED;
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE OR PROVIDE COMPLETE INSTALLATION IN ANY OTHER
 FORMAT THAT WILL HAVE ALL THE REQUIRED INFORMATION TO
 VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC.
 R301.1 FBC-RESIDENTIAL, 6TH EDITION (2017).
  
 B) PROVIDE COMPLETE DRAWINGS. DRAWINGS SUBMITTED ARE
 CUT AND MISSING PAGES. PROVIDE COMPLETE DRAWINGS THAT
 ARE PRINTED ON THE SAME PAGE. PRINT ON LANDSCAPE FORMAT
 SO DRAWINGS ARE LEGIBLE. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- PROVIDE WINDOW MULLION PRODUCT APPROVAL AS REQUIRED
 BY FAC 61G20-3.001 AND CLEARLY IDENTIFY MULLIONS SIZE
 TO BE USED TO VERIFY COMPLIANCE WITH SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS.
 REVISE VALUATION AS REQUIRED.
  
 6- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-02-26 Cont ID  
Sent By jgomez Date 2018-02-26 Time 14:04 Rev Time 0.00
Received By jgomez Date 2018-02-26 Time 13:40 Sent To  
Notes
2018-02-26 13:40:42CHARLES JACKSON REVISED THE SHUTTERS INSTALLATION
 SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-21 Cont ID  
Sent By jgomez Date 2018-02-16 Time 19:33 Rev Time 0.00
Received By jgomez Date 2018-02-14 Time 18:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-07 Cont ID  
Sent By jgomez Date 2018-02-07 Time 14:22 Rev Time 0.00
Received By jgomez Date 2018-02-05 Time 12:03 Sent To I
Notes
2018-02-07 12:04:0902/05/18 MET WITH CONTRACTOR. 1ST RE-SUBMITTAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-24 Cont ID  
Sent By jgomez Date 2018-01-23 Time 18:28 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 14:11 Sent To I
Notes
2018-01-23 14:11:24BLDG <5K