Plan Review Details - Permit 18010743
Plan Review Stops For Permit 18010743
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-03-08 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-06 Time 14:05 Sent To  
Notes
2018-03-07 14:06:01RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-05 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-28 Time 12:53 Sent To  
Notes
2018-03-01 12:53:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-01-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-22 Time 14:05 Sent To  
Notes
2018-01-23 14:06:13ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-08 Cont ID  
Sent By ccole Date 2018-03-08 Time 17:44 Rev Time 0.00
Received By ccole Date 2018-03-08 Time 17:44 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-05 Cont ID  
Sent By ccole Date 2018-03-05 Time 10:01 Rev Time 0.00
Received By ccole Date 2018-03-05 Time 09:28 Sent To I
Notes
2018-03-05 10:20:402ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL, WEST PALM
 BEACH AMENDMENTS TO THE FBC
 PERMIT #18010743
 1/30/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) 2ND REQUEST FOR THE AC CONTRACTOR TO PROVIDE HIS/HER
 SIGNATURE ON THE PLAN- SECTION 107.2.1
  
 2) THE OWNER/AGENT MUST SIGN AND DATE THE ENERGYGAUGE
 FORM R405-2017.
  
 3) INDICATE HOW ACCESS TO THE AIR HANDLER IN THE ATTIC
 WILL BE PROVIDED- PLEASE SEE SECTION R403.3.3.6 FBC-17
 ENERGY CONSERVATION.
  
 4) THE 8" TRANSFER DUCT FROM THE MASTER BEDROOM IS
 UNDERSIZED PER SECTION M1602.3 FBC-17 RESIDIENTIAL.
  
 5) SHOW THE LOCATION OF THE NNEW AC CONDENSER ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By ccole Date 2018-01-30 Time 09:55 Rev Time 0.00
Received By ccole Date 2018-01-30 Time 09:55 Sent To I
Notes
2018-01-30 10:44:551ST REVIEW FBC-2017 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC
 PERMIT #18010743
 1/30/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC PLAN IS UNACCEPTABLE BECAUSE IT IS NOT
 LEGIBLE AND IS NOT DRAWN TO A MINIMUM 1/8" SCALE.-
 SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC. PLEASE
 PROVIDE A CLEAR LEGIBLE PLAN WITH ALL ROOMS AND SPACES
 IDENTIFIED.
  
 2) THE PLAN MUST BEAR THE NAME AND SIGNATURE OF THE
 CONTRACTOR WHO PREPARED THE DESIGN- SECTION 107.2.1
  
 3) THE PROJECT IS NOT AN "AC CHANGEOUT". THIS IS A NEW
 AC AND DUCTWORK INSTALLATION. PLEASE REMOVE THE
 CHANGEOUT FORM FROM THE FILE AND PROVIDE AN EQUIPMENT
 SCHEDULE ON THE PLAN THAT LISTS THE MAKE AND MODEL OF
 THE SYTEM, THE COOLING AND
  
 HEATING CAPACITIES, THE TOTAL SUPPLY CFMS, THE
 EFFICENCY RATING, AND ELECTRICAL DATA.
  
 4) PROVIDE THE SUPPLY CFMS AT EACH DIFFUSER LOCATION.
  
 5) THE COOLING AND HEATING EQUIPMENT SUMMARIES ON THE
 AC CALCULATIONS WERE LEFT BLANK. PLEASE PROVIDE THE
 REQUIRED INFORMATION- SECTION R403.7.1 FBC-14 ENERGY
 CONSERVATION.
  
 6) THE ENERGY FORM R405-2014 IS OUTDATED. THE FBC-17
 ENERGY CONSERVATION CODE TOOK EFFECT ON 1/1/18. PLEASE
 NOTE THE OWNER/AGENT MUST SIGN AND DATE THE FORM
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  