Plan Review Details - Permit 18010627
Plan Review Stops For Permit 18010627
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-31 Cont ID  
Sent By jgomez Date 2018-01-31 Time 17:01 Rev Time 0.00
Received By jgomez Date 2018-01-31 Time 16:09 Sent To  
Notes
2018-01-31 16:10:02RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- PROVIDE SKYLIGHT CURRENT PRODUCT APPROVAL. PRODUCT
 APPROVAL FL2418-R9 SUBMITTED IS FOR THE 2014 CODE. THE
 CURRENT CODE IS THE FBC-6TH EDITION (2017). PROVIDE 2
 COPIES OF CURRENT PRODUCT APPROVAL. FAC 61G20-3.001.
  
 RESPONSE:
 1- SELF-AFFIRMATION LETTER SUBMITTED FROM THE
 PROFESSIONAL ENGINEER ROBERT J. AMORUSO IS REFERRING TO
 FLORIDA PRODUCT APPROVAL FL21896. THIS IS NOT THE SAME
 FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED WITH THE
 PERMIT APPLICATION. ENGINEER TO PROVIDE
 SELF-AFFIRMATION LETTER THAT MATCHES PRODUCT APPROVAL
 SUBMITTED OR PROVIDE CURRENT APPROVED PRODUCT APPROVAL
 FOR THE 2017 CODE VERSION.
  
 2- ENGINEER'S SELF-AFFIRMATION LETTER NEEDS TO HAVE THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. NOTE: DIGITALLY SIGNED DOCUMENTS ARE NOT
 ALLOWED BECAUSE THE PERMIT PACKAGE WAS NOT A DIGITAL
 SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-30 Cont ID  
Sent By jgomez Date 2018-01-30 Time 14:32 Rev Time 0.00
Received By jgomez Date 2018-01-30 Time 12:59 Sent To  
Notes
2018-01-30 11:52:16RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- PROVIDE SKYLIGHT CURRENT PRODUCT APPROVAL. PRODUCT
 APPROVAL FL2418-R9 SUBMITTED IS FOR THE 2014 CODE. THE
 CURRENT CODE IS THE FBC-6TH EDITION (2017). PROVIDE 2
 COPIES OF CURRENT PRODUCT APPROVAL. FAC 61G20-3.001.
  
 RESPONSE:
 1- SELF-AFFIRMATION LETTER SUBMITTED FROM THE
 PROFESSIONAL ENGINEER ROBERT J. AMORUSO IS REFERRING TO
 FLORIDA PRODUCT APPROVAL FL21896. THIS IS NOT THE SAME
 FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED WITH THE
 PERMIT APPLICATION. ENGINEER TO PROVIDE
 SELF-AFFIRMATION LETTER THAT MATCHES PRODUCT APPROVAL
 SUBMITTED OR PROVIDE CURRENT APPROVED PRODUCT APPROVAL
 FOR THE 2017 CODE VERSION.
  
 2- ENGINEER'S SELF-AFFIRMATION LETTER NEEDS TO HAVE THE
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. NOTE: DIGITALLY SIGNED DOCUMENTS ARE NOT
 ALLOWED BECAUSE THE PERMIT PACKAGE WAS NOT A DIGITAL
 SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By jgomez Date 2018-01-22 Time 12:19 Rev Time 0.00
Received By jgomez Date 2018-01-22 Time 11:29 Sent To  
Notes
2018-01-22 12:19:49RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- ENGINEER LETTER SUBMITTED FOR THE ROOF TO WALL
 CONNECTIONS NEED TO BE REVISED. ACCORDING TO SEC.
 R301.2.1.4 FBC-RESIDENTIAL 5TH EDITION (2014) THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE AS REQUIRED OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS.
  
 2- ROOF TILE ADHESIVE PRODUCT APPROVAL FL6332-R8
 SUBMITTED: CLEARLY MARK ON THE PRODUCT APPROVAL THE
 PADDY SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND THAT THIS BUILDING IS LOCATED IN
 EXPOSURE "D". COORDINATE WITH ITEM #1 ABOVE.
  
 3- PROVIDE SKYLIGHT CURRENT PRODUCT APPROVAL. PRODUCT
 APPROVAL FL2418-R9 SUBMITTED IS FOR THE 2014 CODE. THE
 CURRENT CODE IS THE FBC-6TH EDITION (2017). PROVIDE 2
 COPIES OF CURRENT PRODUCT APPROVAL. FAC 61G20-3.001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-31 Cont ID  
Sent By jgomez Date 2018-01-31 Time 17:18 Rev Time 0.00
Received By jgomez Date 2018-01-31 Time 16:10 Sent To  
Notes
2018-01-31 16:11:2401/31/18 RECEIVED E-MAIL FROM CONTRACTOR. LYNNE DEVOE
 (LEGACY CONTRACTING)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-30 Cont ID  
Sent By jgomez Date 2018-01-30 Time 14:47 Rev Time 0.00
Received By jgomez Date 2018-01-26 Time 13:25 Sent To  
Notes
2018-01-29 13:26:08RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By jgomez Date 2018-01-22 Time 12:20 Rev Time 0.00
Received By jgomez Date 2018-01-18 Time 10:21 Sent To I
Notes
2018-01-19 10:22:09SHILL