Plan Review Details - Permit 18010605
Plan Review Stops For Permit 18010605
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-27 Cont ID  
Sent By thunt Date 2018-02-27 Time 05:41 Rev Time 0.00
Received By thunt Date 2018-02-22 Time 10:09 Sent To  
Notes
2018-02-23 10:10:06RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-08 Cont ID  
Sent By thunt Date 2018-02-08 Time 06:59 Rev Time 0.00
Received By thunt Date 2018-02-06 Time 13:15 Sent To  
Notes
2018-02-07 13:15:43RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 06:37 Rev Time 0.00
Received By thunt Date 2018-01-18 Time 10:42 Sent To I
Notes
2018-01-19 10:43:03PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-02-27 Cont ID  
Sent By thunt Date 2018-02-27 Time 05:41 Rev Time 0.00
Received By thunt Date 2018-02-27 Time 05:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-02-08 Cont ID  
Sent By thunt Date 2018-02-08 Time 06:54 Rev Time 0.00
Received By thunt Date 2018-02-08 Time 06:54 Sent To  
Notes
2018-02-08 06:58:5902/08/2018 2ND PLUMBING REVIEW**DENIED**
  
 1) THE INLET SIZE OF THE INTERCEPTOR IS UNDERSIZED AND
 SHALL BE 3? FBC-P 710.1(2) AS YOU NOW HAVE 8 DFU ON A
 2? LINE. THE SIZING OF THE ACTUAL DRAIN PIPING IS ALSO
 UNDERSIZED.
  
 2) SHOW THE DEVELOP PIPING LENGTH OF EACH SECTION OF
 PIPING. FBC 107.2.1
  
 3) THE NEW FLOOR PLAN NOW SHOWS A HAND SINK. 2-COPIES
 ARE REQUIRED AND THE FOLLOWING COMMENTS WILL NEED TO BE
 ADDRESSED. FBC-P 107.2.1
  
 A) THE HAND SINK IS REQUIRED TO BE TRAPPED AND VENTED
 FBC-P 1002.1
  
 B) THE HAND SINK MUST BE INCLUDED IN YOUR GREASE
 INTERCEPTOR SIZING CALCULATION. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-22 Cont ID  
Sent By thunt Date 2018-01-22 Time 06:35 Rev Time 0.00
Received By thunt Date 2018-01-22 Time 06:35 Sent To  
Notes
2018-01-22 06:37:0701/22/2018 PLUMBING 1ST REVIEW*DENIED**
  
 PROVIDE HOW YOU DETERMINED THE REQUIRED SIZE OF THE NEW
 GREASE INTERCEPTOR. PROVIDE SIZING AND COMPY WITH
 1003.3.4.1 AND 1003.3.6
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  