Plan Review Details - Permit 18010553
Plan Review Stops For Permit 18010553
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2018-11-27 Cont ID  
Sent By shill Date 2018-11-27 Time 10:20 Rev Time 0.00
Received By shill Date 2018-11-27 Time 10:20 Sent To  
Notes
2018-11-27 10:20:40PROFLEX SUPERSIM 90 PER CONTRACTOR
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2018-10-19 Cont ID  
Sent By shill Date 2018-10-19 Time 18:01 Rev Time 0.00
Received By shill Date 2018-10-19 Time 18:01 Sent To  
Notes
2018-10-19 18:14:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. TILE FLOOR IS NOTED ON THE PLAN. THE SAME SPEC
 SHEETS AND TEST REPORTS ARE STILL IN THE PACKAGE, NO
 NEW INFORMATION PROVIDED. SUPERSIM 90 IS SUGGESTED AS
 AN UNDERLAYMENT.
  
 IF YOU CHOOSE TO USE A DIFFERENT UNDERLAYMENT, SEE
 PREVIOUS FIVE COMMENT LISTS FOR THE TEST REPORTS
 REQUIRED.
  
 2. OK
  
 CONTRACTOR WAS SENT AN EMAIL. THE CONTRACTOR IS TO
 RESOLVE THIS VIA EMAIL RATHER THAN A RESUBMITTAL AT THE
 BUILDING DIVISION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 18:17 Rev Time 0.00
Received By shill Date 2018-09-22 Time 18:13 Sent To  
Notes
2018-09-22 18:20:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. TILE FLOOR IS NOTED ON THE PLAN. THE SAME SPEC
 SHEETS AND TEST REPORTS ARE STILL IN THE PACKAGE, NO
 NEW INFORMATION PROVIDED. SUPERSIM 90 IS SUGGESTED AS
 AN UNDERLAYMENT.
  
 IF YOU CHOOSE TO USE A DIFFERENT UNDERLAYMENT, SEE
 PREVIOUS FOUR COMMENT LISTS FOR THE TEST REPORTS
 REQUIRED.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471. PLANS ARE PREPARED BY TOM TWOMEY, PE
 BUT NOT SIGNED AND SEALED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 18:19 Rev Time 0.00
Received By shill Date 2018-08-09 Time 18:19 Sent To  
Notes
2018-08-09 18:22:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. ADVISE AS TO TYPE OF FLOORING PROPOSED, FBC 107.
  
 IF A FLOORING UNDERLAYMENT IS PROPOSED (FOR TILE OR
 OTHER RESILIENT FLOORING), ADVISE AS TO UNDERLAYMENT
 PROPOSED. THREE TEST REPORTS ARE REQUIRED.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 PROFLEX MSC90 WAS SUBMITTED. THE STC AND IIC TEST
 REPORTS INCLUDE A DROPPED GYPSUM CEILING.
 PROFLEX SUPERSIM 90 MAY BE A SUITABLE ALTERNATIVE;
 PLEASE INFORM AS TO TYPE OF FLOORING PROPOSED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 12:00 Rev Time 0.00
Received By shill Date 2018-07-08 Time 12:00 Sent To  
Notes
2018-07-08 12:01:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ADVISE AS TO TYPE OF FLOORING PROPOSED, FBC 107.
  
 IF A FLOORING UNDERLAYMENT IS PROPOSED (FOR TILE OR
 OTHER RESILIENT FLOORING), ADVISE AS TO UNDERLAYMENT
 PROPOSED. THREE TEST REPORTS ARE REQUIRED.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-13 Cont ID  
Sent By shill Date 2018-05-13 Time 11:56 Rev Time 0.00
Received By shill Date 2018-05-13 Time 11:50 Sent To  
Notes
2018-05-13 11:57:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ADVISE AS TO TYPE OF FLOORING PROPOSED, FBC 107.
  
 IF A FLOORING UNDERLAYMENT IS PROPOSED (FOR TILE OR
 OTHER RESILIENT FLOORING), ADVISE AS TO UNDERLAYMENT
 PROPOSED. THREE TEST REPORTS ARE REQUIRED.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 SINCE THIS IS A NEW COMMENT, THIS INFORMATION MAY BE
 PROVIDED VIA EMAIL FOR PRELIMINARY REVIEW.
  
 SINCE THIS IS A ONE PAGE PLAN WHICH FAILED ANOTHER
 TRADE, A THIRD BUILDING REVIEW IS REQUIRED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By jwitmer Date 2018-01-25 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2018-01-25 Time 06:57 Sent To  
Notes
2018-01-25 07:58:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010553
 ADD: 5600 N. FLAGLER DR. SUITE: 1009
 CONT: COLORS GROUP INC.
 TEL: 561-262-6303
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 25/ 2018
 ACTION: DENIED
  
 1) THE DESIGN PROFESSIONAL HAS DESIGNED THE PLANS TO
 THE WRONG CODE AND EDITION OF THE CODE. THE PLANS STATE
 THEY WERE DESIGNED TO THE 2014 FBC-RESIDENTIAL CODE.
 EFFECTIVE DEC. 31/2017 THE 6TH EDITION/ 2017 FLORIDA
 BUILDING CODE WAS ADOPTED STATEWIDE. PLEASE UPDATE
 PLANS. THIS IS A HIGHRISE BUILDING MULTI-UNIT R-2
 OCCUPANCY, NOT A SINGLE FAMILY RESIDENCE.
  
 2) THE WIND DESIGN REVERTS BACK TO THE 2010 FBC AND A
 EXPOSURE C, WE ARE UNDER THE 2017 FBC-B STILL ASCE
 7-10, EXPOSURE D. THIS CONDOMINIUM IS DIRECTLY ON THE
 INTERCOASTAL WATERWAY.
  
 3) THE DESIGNER OF RECORD HAS NOT LISTED HOW THE PLANS
 WERE DESIGNED UNDER THE 2017 EXISTING BUILDING CODE ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT.
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 4) SHEET A-1 NOTE # 4 INDICATES THE REMOVAL OF A
 PORTION OF THE DROP CEILING BUT NO INFORMATION IS GIVEN
 HOW THE REMAINING PORTION OF THE DROPPED CEILING IS TO
 BE FRAMED? TYPE OF FRAMING SUPPORTS, SIZE, SPACING,
 SPAN, DEFLECTION LIMITS, ANCHORAGE TO THE CEILING
 ABOVE, THICKNESS OF CEILING FINISH MATERIAL.
 2017 FBC-B TABLE 2506.2 STEEL STUDS NON-LOADING ASTM
 C645. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-09-02 Cont ID  
Sent By jpearson Date 2018-09-02 Time 09:44 Rev Time 0.00
Received By jpearson Date 2018-09-02 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-09 Cont ID  
Sent By ppetty Date 2018-07-09 Time 14:57 Rev Time 0.00
Received By ppetty Date 2018-07-09 Time 14:56 Sent To  
Notes
2018-07-09 14:46:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. OK
  
 NEW COMMENTS:
  
 4. OK
 5. OK
 6. OK
 7. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 10:12 Rev Time 0.00
Received By jpearson Date 2018-05-05 Time 10:12 Sent To  
Notes
2018-05-05 10:12:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 (NOT
 PROVIDED.)
  
 NEW COMMENTS:
  
 4. NEW NOTE PROVIDED FOR AFCI PROTECTION IS NOT CODE
 COMPLIANT. PER CODE: ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.12
 5. NOTE ADDED FOR TAMPER RESISTANT RECEPTACLES QUOTES
 NEC 406.11, WHICH DOES NOT APPLY TO THIS REQUIREMENT.
 PROVIDE CORRECTION. NEC 406.12
 6. IF DISHWASHER IS INSTALLED, PROVIDE GFCI PROTECTION
 FOR THE DISHWASHER. NEC 210.8(D)
 7. ALTERED BATH DOES NOT SHOW THE GFCI PROTECTED
 RECEPTACLE OUTLET ON A 20 AMP CIRCUIT REQUIRED WITHIN 3
 FEET OF BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-02-20 Cont ID  
Sent By jpearson Date 2018-02-20 Time 15:52 Rev Time 0.00
Received By jpearson Date 2018-02-20 Time 12:39 Sent To P
Notes
2018-02-20 15:52:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD. FS 471.003(2)(H);
 471.025; FBC 107.2.1
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2018-10-12 Cont ID  
Sent By pleduc Date 2018-10-12 Time   Rev Time 0.00
Received By pleduc Date 2018-10-12 Time 11:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-08-31 Cont ID  
Sent By pleduc Date 2018-08-31 Time   Rev Time 0.00
Received By pleduc Date 2018-08-31 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-07-03 Cont ID  
Sent By pleduc Date 2018-07-03 Time   Rev Time 0.00
Received By pleduc Date 2018-07-03 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By pleduc Date 2018-05-02 Time   Rev Time 0.00
Received By pleduc Date 2018-05-01 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-01-23 Cont ID  
Sent By pleduc Date 2018-01-23 Time   Rev Time 0.00
Received By pleduc Date 2018-01-22 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-10-19 Cont ID  
Sent By shill Date 2018-10-19 Time 18:15 Rev Time 0.00
Received By shill Date 2018-10-04 Time 16:27 Sent To  
Notes
2018-10-11 16:27:32ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 18:20 Rev Time 0.00
Received By shill Date 2018-08-29 Time 15:25 Sent To  
Notes
2018-08-30 15:26:04B04

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-09 Cont ID  
Sent By shill Date 2018-08-09 Time 18:23 Rev Time 0.00
Received By shill Date 2018-07-31 Time 14:53 Sent To  
Notes
2018-08-01 14:53:46RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 10:28 Rev Time 0.00
Received By tklarge Date 2018-06-29 Time 16:20 Sent To  
Notes
2018-07-02 16:20:23B09

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-14 Cont ID  
Sent By lcrespo Date 2018-05-14 Time 14:53 Rev Time 0.00
Received By lcrespo Date 2018-04-26 Time 11:02 Sent To  
Notes
2018-04-27 11:03:08B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-27 Cont ID  
Sent By lcrespo Date 2018-02-27 Time 16:49 Rev Time 0.00
Received By lcrespo Date 2018-01-17 Time 08:35 Sent To  
Notes
2018-01-19 08:35:21B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-01-25 Cont ID  
Sent By jwitmer Date 2018-01-25 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2018-01-25 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-05-02 Cont ID  
Sent By ccole Date 2018-05-02 Time 15:29 Rev Time 0.00
Received By ccole Date 2018-05-02 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-15 Cont ID  
Sent By ccole Date 2018-02-15 Time 16:26 Rev Time 0.00
Received By ccole Date 2018-02-15 Time 16:26 Sent To  
Notes
2018-02-15 16:30:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18010552
 2/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) CLARIFY IF ANY MECHANICAL ALTERATIONS ARE PROPOSED
 FOR THE PROJECT, AND PROVIDE A SCOPE OF WORK WITH
 CORRELATING DRAWINGS AND DETAILS, IF APPLICABLE.
 OTHERWISE PLEASE WRITE "NO MECHANICAL WORK" ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 11:09 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 11:08 Sent To  
Notes
2018-10-16 11:09:315TH REVIEW: FBC 2017 6TH EDITION
 PERMIT 18050533
 PLUMBING COMMENTS: APPROVED
  
 PREVIOUSLY APPROVED PLAN SHEET A-1 WAS VOIDED DUE TO
 RESUBMITTAL OF SAME SHEET FOR OTHER DISCIPLINES. NEW
 SHEET DID NOT CHANGE ANY PLUMBING. STAMPED, INITIALED
 AND DATED AS REVIEWED FOR COMPLIANCE.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-09-19 Cont ID  
Sent By shill Date 2018-09-19 Time 09:11 Rev Time 0.00
Received By jesmith Date   Time   Sent To  
Notes
2018-09-19 09:02:435TH REVIEW: FBC 2017 6TH EDITION
 PERMIT 18051383
 PLUMBING COMMENTS: APPROVED
  
 PREVIOUSLY APPROVED PLAN SHEET A-1 WAS VOIDED DUE TO
 RESUBMITTAL OF SAME SHEET FOR OTHER DISCIPLINES. NEW
 SHEET DID NOT CHANGE ANY PLUMBING. STAMPED, INITIALED
 AND DATED AS REVIEWED FOR COMPLIANCE.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 10:28 Rev Time 0.00
Received By jesmith Date 2018-09-19 Time 08:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-14 Cont ID  
Sent By lcrespo Date 2018-05-14 Time 14:53 Rev Time 0.00
Received By lcrespo Date 2018-05-14 Time 14:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-27 Cont ID  
Sent By lcrespo Date 2018-02-27 Time 16:47 Rev Time 0.00
Received By lcrespo Date 2018-02-27 Time 16:47 Sent To  
Notes
2018-02-27 16:54:17DENIED
  
 1. THE NOTE ON SHOWER INSTALLATION REFERS TO 2014
 FLORIDA BUILDING CODE RESIDENTIAL PLUMBING CODE, PLEASE
 MAKE REFERENCES TO 2017 FLORIDA BUILDING CODE PLUMBING
 SECTION 417 AND NOTE THE CORRECT COMPLIANCE FBC WPB A
 107.1 GENERAL PLAN APPLICATION.
 2. WHEN CHANGING TUB TO THE SHOWER WILL THERE BE A
 VALVE REPLACEMENT AND IF SO IT MUST COMPLY WITH 2017
 FBC P SECTION 424.3. PLEASE PROVIDE A SPECIFICATION FOR
 SHOWER VALVE TYPE THAT COMPLIES. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. REFRIGERATOR MUST BE EQUIPPED WITH HAMMER ARRESTOR
 2017 FBC P 604.9.
 4. SHOWER MEASUREMENT IS AT 30" PLUS 4" THAT MAKE THE
 TOILET IS 26", REFER TO 2017 FBC P 405.3.1 THAT STATE A
 WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER
 THAN 30 INCHES CENTER TO CENTER BETWEEN ADJACENT
 FIXTURES. THE SHOWER MAY BE SMALLER AS LONG AS IT
 COMPLIES WITH FBC P 417.4. SHOWER COMPARTMENT SHALL NOT
 BE LESS THAN 900 SQUARE INCHES. SHOWER WASTE OUTLET
 SHALL WITH FBC P 417.3, PLEASE PROVIDE SHOWER DRAIN
 DETAILS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. SHOWER LINING SHALL COMPLY WITH FBC P 417.2 LINERS
 SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD
 THE FIXTURE DRAINS AND BE SECURELY FASTENED TO THE
 WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET.
 6. A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  