Plan Review Details - Permit 18010481
Plan Review Stops For Permit 18010481
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-01 Cont ID  
Sent By rmcdouga Date 2018-03-01 Time 19:37 Rev Time 0.00
Received By rmcdouga Date 2018-03-01 Time 19:37 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-13 Cont ID  
Sent By rmcdouga Date 2018-02-13 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2018-02-13 Time 18:18 Sent To I
Notes
2018-02-13 18:25:02PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT) THE GENERATOR PAD PLANS HAVE
 SEVERAL REFERENCES TO THE FBC FIFTH EDITION (2014). THE
 FBC SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-01-30 Cont ID  
Sent By rmcdouga Date 2018-01-30 Time 18:58 Rev Time 0.00
Received By rmcdouga Date 2018-01-30 Time 18:49 Sent To  
Notes
2018-01-30 18:58:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD PLANS HAVE SEVERAL REFERENCES TO
 THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017).
  
 2) THE MODEL NUMBER FOR THE 16 KW GENERAC GENERATOR
 FROM THE MANUFACTURER'S SPECIFICATIONS THAT WERE
 SUBMITTED IS NOT ON THE PAD PLANS THAT WERE SUBMITTED.
 FBC 107.2.1
  
 3) THE GENERATOR PAD AND ANCHORING PLANS ARE REQUIRED
 TO HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-02 Cont ID  
Sent By jleahy Date 2018-02-02 Time 16:13 Rev Time 0.00
Received By jleahy Date 2018-02-02 Time 16:12 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-02-05 Cont ID  
Sent By tklarge Date 2018-02-05 Time 11:19 Rev Time 0.00
Received By tklarge Date 2018-02-05 Time 11:19 Sent To I
Notes
2018-02-05 11:20:27GAS REVIEW PERFORMED UNDER #18010194.TKL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-01 Cont ID  
Sent By rmcdouga Date 2018-03-01 Time 19:37 Rev Time 0.00
Received By rmcdouga Date 2018-02-22 Time 10:37 Sent To  
Notes
2018-02-23 10:37:55RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-13 Cont ID  
Sent By rmcdouga Date 2018-02-13 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2018-02-12 Time 11:00 Sent To  
Notes
2018-02-13 11:00:34RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-05 Cont ID  
Sent By tklarge Date 2018-02-05 Time 11:20 Rev Time 0.00
Received By tklarge Date 2018-01-16 Time 10:47 Sent To  
Notes
2018-01-17 10:47:17ROUTED TO FIRE INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-01-30 Cont ID  
Sent By PG Date 2018-01-30 Time 15:18 Rev Time 0.00
Received By pgreilic Date 2018-01-22 Time 14:35 Sent To  
Notes
2018-01-30 15:20:411.) LANDSCAPE SCREENING REQUIRED FOR FINAL INSPECTION
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]